air requirements Flashcards
what is considered low volume and high volume installations
low volume = under 400,000 btuh, high volume = over 400,000 btuh
what tables are air requirements sized from
8.1, 8.2, 8.3 8.4
if you have an appliance with a draft control and one without, but they both comply with being air tight, what do you do?
first size the one with draft control from the relevant table. then add the mbhs together and size from table without draft control. whatever is bigger is the answer
when sizing air requirements if a duct length is between 20 and 50 ft, what do you do?
increase the size by one size
if a building doesnt comply with being airtight how do you size a round duct?
find the answer from table 8.3 or 8.4 and then find the round duct equiv on 8.1 or 8.2 depending if there is a damper or not