AC Gen Flashcards
1
Q
Require of V?
A
- 450V
- Line vari less than 1%
- SS V between 57-63hz
- Transient V vari max of 7.5% for 25% load go off & 15% for go on load
- Time of recovery to 1% of final V ,less than 1 sec
2
Q
Req of Hz?
A
- 60hz
- ss Hz vari 3.5-4%
- TRansient hz vari for 25% load changes +- 2.5%
- Time of recovery for transients to within 1%
3
Q
Operation of brushless gen
A
- PM rotates shaft 1200
- PMG supplies exciter by the AVR
- AVR supplies DC V to exciter stator
- Exciter rotor produces AC V
- Goes into rectifier AC-DC
- DC onto gen rotor inducing mag field
- Inducing EMF In stator
- 450v,3ph,60hz to swbd
- AVR monitors v output by sample line from gen stator
4
Q
Fault cond on rectifier
A
- Open-V fall,Excit overld,damg diodes,sup brkr open
- Short-V fall,AVR comp,diode strain,gen off within 30 mins
5
Q
Gen rounds
A
- Monthly-VA records,Bearings,water,vent grills
- Dailies-Bearings,air temp,oil temp,leaks,diode fail,heaters not on.
6
Q
AVR Modules & what do?
A
- 17 FU=improve HF 160hz sup
- 1 EC=connects 160hz to mosfets
- 28 CU output con=provides firing pulses to mosfets
- 169p output power amp=4 mosfets
- 41 mu=ensure param
- 1PN=shut dn
- 1 UF interfce=provides V + hz to avr modules
- 168p Low v pwr supp=24VDc to modules
- 1CU comp unit=compares actual v to des