A/C troubleshooting / symptoms Flashcards
What could cause high superheat?
4
- starving txv
- restricted orfice tube
- restricted receiver dryer
- low charge
What could cause low superheat?
flooding txv or orfice tube
What could cause high subcooling?
4
- excess charge
- low ambient air temperature
- air flow through the condenser is high
- restricted receiver dryer
What could cause low subcooling?
3
- low charge
- flooding txv
- restricted flow through the condenser
A failing compressor will show up as?
TQ / IP question
A low pressure on the high side and a high pressure on the low side.
What kind of subcooling should you see at the condenser?
10-20*F
All systems
What kind of superheat should you see at the evaporator?
6-12*F on txv systems
0-4*F on orfice tube systems
What should the static high side pressure be?
2 - 2.5x the ambient air temperature
On a clutch cycling system, what should the static low side pressure be?
15-30 psi on txv systems
20-45 psi on orfice tube systems
On a variable displacement system, what should the static low side pressure be?
29psi + or - 1psi (28-30psi)
txv and orfice tube
Low side pressure lower than normal could be caused by:
2
- insufficient refrigerant entering the evaporator
- too much refrigerant is being removed from the evaporator
Low side pressure higher than normal could be caused by:
2
- excessive refrigerant entering the evaporator
- not enough refrigerant is being removed from the evaporator
Symptoms of a low refrigerant charge:
5
- low side pressure lower than normal, may indicate a vacuum
- high side pressure lower than normal
- higher than normal superheat
- lower than normal sub-cooling
- outlet duct temperature warmer than normal
Symptoms of air in the system:
6
- low side pressure normal to higher than normal
- high side pressure higher than normal, may be very high depending on the amount of non-condensable gas
- normal to slightly higher superheat
- lower than normal sub-cooling
- outlet duct temperature warmer than normal
- when checking static gauge pressure, you may see higher than normal ambient pressures
Symptoms of excessive refrigerant charge:
5
- low side pressure normal to higher than normal
- high side pressure higher than normal
- normal superheat
- higher than normal sub-cooling
- outlet duct temperature warmer than normal
Symptoms of moisture in the system:
5
- low side pressure normal to lower than normal
- high side pressure normal then drops below normal after extended operation
- normal superheat at first then becomes excessive after extended operation
- normal to higher than normal sub-cooling
- outlet duct temperatures normal at first then becomes warmer after extended operation
When testing an A/C system, if you cant get the compressor to cycle off, what can you do to manipulate the system?
lower the fan speed to lower the heat load
If both static pressures are lower than the corresponding pressure/temperature chart, what could be the cause?
its probably a low charge
What would cause both static pressures to be around 20psi higher than normal?
an azeotrope
What is static pressure?
gauges hooked up but the system is not running