2016 Flashcards
State the test voltage used for carrying out an insulation resistance
test on three-phase, 400V, electrical equipment incorporating MIMS
elements.
● 500 V
● d.c.
State the minimum permitted test result for the insulation resistance
test on the electrical equipment.
0.01MΩ
State what is meant by the term pull-out torque as it applies to an
a.c. induction motor.
The maximum value of torque the motor can produce.
An electrical installation has a prospective short-circuit current rating of 3.7 kA when measured at the switchboard. There are rewireable fuses on the
switchboard.
State ONE reason why the rewireable fuses need to be replaced.
Because rewireable fuse have a maximum rupturing capacity of 1 kA
State what occurs to an a.c. induction motor if the load torque
exceeds the pull-out torque.
The motor will stall
A single-phase induction motor is being installed in a circular saw bench.
State ONE reason why a capacitor-start motor is used rather than a splitphase motor.
This type of motor develops higher starting torque under load.
Measurements from a single-phase light industrial electrical installation
show the following:
● 235V
● 70A
● 15.2 kW
Calculate the power factor of the circuit.
235 x 70 = 16450 VA
= 15200 / 16450
= 0.9241
A single-phase induction motor is being installed in a ventilation fan for a ducted air conditioning system.
State ONE reason why a capacitor-start capacitor-run motor is used rather than a split-phase motor.
Any ONE of:
● It runs a lot quieter
● It develops a higher running torque
● It develops a higher starting torque
Define the term current rating as it applies to HRC fuses.
This is the maximum current that the
fuse is designed to carry continuously
without deterioration
Define the term breaking (or rupturing) capacity as it applies to
HRC fuses.
The maximum fault current the fuse can safely interrupt.
State the TWO main functions of a ballast (choke) in a fluorescent light
fitting.
● To limit the current flowing through the electrode and tube.
● To produce a high voltage when the
starter opens to start the tube glowing.
(i) State ONE precaution that could be taken when using an insulation
resistance tester, set on the 500V d.c. range, to carry out an
insulation resistance test on electrical equipment containing semiconductor devices.
State ONE reason why you would take the precaution stated in (i).
(i) Any ONE of:
● Disconnect semi-conductor devices
● Bridge out between phase and
neutral
(ii) The voltage of the test instrument may be damage the semi-conductor devices.
Define the term direct light distribution as it applies to a light fitting.
Any ONE of:
● The light from the fitting is thrown
directly onto the surface being
illuminated.
● 90% to 100% of the light is directed in a specific direction.
● There is no obstruction or shading
between the light source and the surface being illuminated.
Describe the method by which a rotating magnetic field effect is
created in a single-phase split-phase induction motor.
● The start winding and the run
winding are physically
displaced.
● The start winding and the run
winding have different
impedances.
● This causes a phase
displacement between the
start winding current and the
run winding current
● Creating a rotating magnetic
field effect.
Explain why a single-phase capacitor-start induction motor has a higher starting torque when compared to a single-phase split-phase induction motor?
● The capacitor increases the
difference in the impedances
between the start winding and
run winding.
● This causes a larger phase
displacement between the
start winding current and the
run winding current
● Creating a stronger rotating
magnetic field
If an external starting relay is to be used for a single-phase, split-phase
induction motor, which winding will it switch?
The start (or auxiliary) winding.
State the reason why transformers are rated in kVA.
Because kVA is the maximum current
rating stated regardless of the pf of the load to be connected.
Explain the reason why a 500 kVA transformer at Scott Base, Antarctica
can be operated more heavily loaded than an identical 500 kVA transformer installed in Wellington.
The transformer at Scott Base can
dissipate more heat than the
transformer in Wellington because the ambient temperature is lower.
A three-phase, 10 kW pump motor needs repairing. The motor has been
isolated and cables disconnected. The motor cables are still connected to the DOL starter.
State TWO precautions which must be taken to ensure the safety of
persons and property while the work site is left unattended.
Any TWO of:
● The cable must be made electrically
safe.
● Protect the cables to prevent damage
● Prevent access to the cables.
● Prevent access to the cables.
● Replace the danger tag with an out-ofservice tag.
Describe how isolating three-phase electrical equipment is different from switching off that three-phase electrical equipment.
Isolating means:
● that the motor has been deliberately
disconnected from the electricity supply
● and precautions taken to prevent
reconnection
Switched off means:
that the electricity ceases to be supplied to the motor
Describe THREE methods of preventing the reconnection of the electricity supply to an isolated fixed-wired, three-phase machine that is being worked on.
Any THREE of:
● Lock open the isolating switch.
● Lock open the MCBs or fuses.
● Disconnect the circuit supplying the
electrical equipment.
● Use an access permit or “hold card”
system.
Describe the circumstances where a danger tag is used.
Where there is a possibility of personal
danger through the supply being restored.
A voltage test using the prove-test prove method is being carried out on the supply side of a three-phase main switch to see if a switchboard is isolated.
What tests need to be made to clearly establish that isolation has taken place.
● Test between each phase and earth.
● Test between each phase and neutral.
A three-phase, 400V workshop has been completely rewired. The work included all final subcircuits including a fixed wired, single-phase 2 kW water heater with a MIMS element. There was no change to the mains, main earthing system or
switchboard.
(a) An insulation resistance test is required to be carried on the new work and the installation has been isolated.
(ii) The water heater has been disconnected before testing of the
electrical installation commences.
State the THREE other actions that need to be taken before insulation
resistance testing can commence.
● Disconnect the MEN link
● Disconnect the main neutral
● Turn all switches and circuit breakers to the ON position