2015 Canadian Electrical Code, part I - tables Flashcards
Allowable ampacities for single unshielded copper conductors, rated not more than 5000 V, in free air
(based on an ambient temperature of 30 °C)
Table 1
Allowable ampacities for not more than three copper conductors, rated not more than 5000 V and
unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
Table 2
Allowable ampacities for single unshielded aluminum conductors, rated not more than 5000 V, in free air
(based on an ambient temperature of 30 °C)
Table 3
Allowable ampacities for not more than three aluminum conductors, rated not more than 5000 V and
unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
Table 4
Correction factors applying to Tables 1, 2, 3, and 4 (ampacity correction factors for ambient
temperatures above 30 °C)
Table 5A
Correction factors for Tables 1 and 3 (where from two to four single conductors are present and spaced
less than 25% of the largest cable diameter)
Table 5B
Ampacity correction factors for Tables 2 and 4
Table 5C
Current rating correction factors where spacings are maintained (in ventilated and ladder-type cable
trays)
Table 5D
Maximum number of 600 V thermoset conductors without a jacket, Types R90XLPE, RW75XLPE,
RW90XLPE, and RPV90, of one size in trade sizes of conduit or tubing
Table 6A
Maximum number of 1000 V thermoset conductors without a jacket, Types R90XPLE, RW75XLPE,
RW90XLPE, and RPV90, of one size in trade sizes of conduit or tubing
Table 6B
Maximum number of 600 V thermoset conductors with a jacket, Types R90XPLE, RW75XLPE, RW90XLPE,
R90EP, RW9075EP, RW90EP, and RPV90, of one size in trade sizes of conduit or tubing
Table 6C
Maximum number of underground conductors, Types RWU90XLPE, TWU, and TWU75, of one size in
trade sizes of conduit or tubing
Table 6D
Maximum number of 1000 V and 2000 V thermoset conductors without a jacket, Type RPVU90, of one
size in trade sizes of conduit or tubing
Table 6E
Maximum number of 1000 V and 2000 V thermoset conductors with a jacket, Type RPVU90, of one size
in trade sizes of conduit or tubing
Table 6F
Maximum number of 2000 V thermoset conductors without a jacket, Type RPV90, of one size in trade
sizes of conduit or tubing
Table 6G
Maximum number of 1000 V thermoset conductors with a jacket, Type RPV90, of one size in trade sizes
of conduit or tubing
Table 6H
Maximum number of 2000 V thermoset conductors with a jacket, Type RPV90, of one size in trade sizes
of conduit or tubing
Table 6I
Maximum number of thermoplastic conductors, Types TW and TW75, of one size in trade sizes of
conduit or tubing
Table 6J
Maximum number of thermoplastic conductors, Types TWN75 and T90 NYLON, of one size in trade
sizes of conduit or tubing
Table 6K
Radius of conduit or tubing bends
Table 7
Maximum allowable per cent conduit and tubing fill
Table 8
Cross-sectional areas of rigid metal conduit
Table 9A
Cross-sectional areas of flexible metal conduit
Table 9B
Cross-sectional areas of rigid PVC conduit
Table 9C
Cross-sectional areas of rigid Type EB1 PVC conduit and rigid Type DB2/ES2 PVC conduit
Table 9D
Cross-sectional areas of rigid RTRC conduit marked IPS
Table 9E
Cross-sectional areas of rigid RTRC conduit marked ID
Table 9F
Cross-sectional areas of metallic liquid-tight flexible conduit
Table 9G
Cross-sectional areas of non-metallic liquid-tight flexible conduit
Table 9H
Cross-sectional areas of electrical metallic tubing
Table 9I
Cross-sectional areas of electrical non-metallic tubing
Table 9J
Dimensions of stranded conductors for calculating conduit and tubing fill
Table 10A
Dimensions of photovoltaic cable for calculating conduit and tubing fill
Table 10B
Dimensions of solid conductors for calculating conduit and tubing fill
Table 10C
Dimensions of DLO cable for calculating conduit and tubing fill
Table 10D
Conditions of use, voltage, and temperature ratings of flexible cords, heater cords, tinsel cords, equipment wires, Christmas-tree cords, portable power cables, elevator cables, stage lighting, and festoon cables
Table 11
Allowable ampacity of flexible copper conductor cord and equipment wire (based on an ambient
temperature of 30 °C)
Table 12
Allowable ampacities for portable copper conductor power cables (amperes per conductor)
Table 12A
Temperature correction factor
Table 12B
Conductor rating correction factor
Table 12C
Layering correction factor
Table 12D
Allowable ampacities for Type DLO cables in a permanent installation in cable tray
Table 12E
Rating or setting of overcurrent devices protecting conductors
Table 13
Watts per square metre and demand factors for services and feeders for various types of occupancy
Table 14
Bending radii — High-voltage cable
Table 15
Minimum size conductors for bonding conductors
Table 16A
Minimum size conductors for system bond jumpers and bonding conductors where busbars are
used
Table 16B
Conditions of use and maximum allowable conductor temperature of wires and cables other than flexible cords, portable power cables, and equipment wires
Table 19
Spacings for conductors
Table 20
Supporting of conductors in vertical runs of raceways
Table 21
Space for conductors in boxes
Table 22
Number of conductors in boxes
Table 23
Minimum insulation resistances for installations
Table 24
Overcurrent trip coils for circuit breakers and overload devices for protecting motors
Table 25
Determining conductor sizes for motors for different requirements of service
Table 27
Determining conductor sizes in the secondary circuits of motors
Table 28
Rating or setting of overcurrent devices for the protection of motor branch circuits
Table 29
Minimum clearances for bus support and rigid conductors
Table 30
Minimum horizontal separations of line conductors attached to the same supporting structure
Table 31
Vertical isolation of unguarded live parts
Table 32
Horizontal clearances from adjacent structures (including protuberances)
Table 33
Vertical ground clearances for open line conductors
Table 34
Spacing for switches and fuses assembled in the field (not of the metal-enclosed type)
Table 35
Maximum allowable ampacity for aluminum conductor neutral supported cables
Table 36A
Maximum allowable ampacity for copper conductor neutral supported cables
Table 36B
Motor supply conductor insulation minimum temperature rating, °C (based on an ambient temperature of 30 °C)
Table 37
Minimum permitted size for 3-wire 120/240 V and 120/208 V service conductors for single dwellings and feeder conductors supplying single dwelling units of row housing of apartment and similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C
Table 39
External tapered threads for rigid metal conduit
Table 40
Minimum size of bonding jumper for service raceways
Table 41
Minimum conductor size for concrete-encased electrodes
Table 43
Three-phase ac motors
Table 44
Single-phase ac motors
Table 45
Size of conduit for mobile homes
Table 48
Transformers rated over 750 V having primary and secondary overcurrent protection
Table 50
Minimum size of bare copper grounding conductor
Table 51
Tolerable touch and step voltages
Table 52
Minimum cover requirements for direct buried conductors, cables, or raceways
Table 53
Minimum working space around electrical equipment having exposed live parts
Table 56
Allowable ampacities for Class 2 copper conductors (based on an ambient temperature of 30 °C)
Table 57
Ampacities of up to four insulated copper conductors in raceway or cable for short-time-rated crane and hoist motors (based on an ambient temperature of 30 °C)
Table 58
Minimum size of protector grounding conductor for communications systems
Table 59
Minimum buried cable horizontal separations from pools
Table 61
Feeder demand factors for elevators
Table 62
Hazardous areas for propane dispensing, container filling, and storage
Table 63
Hazardous locations at NGV fuelling facilities
Table 64
Enclosure selection table for non-hazardous locations
Table 65
Ampacities of bare or covered conductors in free air, based on 40 °C ambient, 80 °C total conductor temperature, and 610 mm/s wind velocity
Table 66
Clearance requirements of installed heating systems
Table 67
Maximum conductor length measured from the supply side of the consumer’s service to the furthest point of utilization on a circuit using 90 °C rated copper conductors at 30 °C ambient temperature for 120 V single-phase ac circuits (2-wire circuits) when used in dwelling units
Table 68