1. NBC Flashcards
The ADA/ABA Guidelines limit the projection of any construction element ot a maximum of
4 in
When selecting a fire extinguisher cabinet, the most critical feature is the
projection distance from the wall
True or false. Glazing is required for fire extinguisher cabinets
false. glazing is not required nor is their a size requirements if glazing is present
the height of a fire extinguisher cabinet must be amaximum
48 in AFF for unobstructed forward reach and side reach
the mazimum allowable height between landings or floors is
12 ft
Model codes prescribe a minimum corridor width of ___in an office exit corridor serving an occupant load of 55
44 in
What agency originally set the requirements for safety glazing in buildings
consumer product safety comimission
the consumer product safety commission originally set requirements of safety glazing whic are codified in the Code of Federal Regulations
according to model codes interior finish requirements for woodwork are most stringent for
A recessed shelving
B cornice molding
C built in furniture
D wainscoating
D wanscoating
-model building coades regulate wainscoating as an interior finish material subject to a Class A, B, or C flame spead rating depending on occupancy, location in the building, and presence or absence of sprinklers.
Sinch wainsoting could be restricted to a Class A flame rating, it is the most stringently regulated item
for a front approach to an in-swinging door (pull side) there must be a minimum of
18 in on the latch side of the door
a fire rated gypsum board partition must always consist of
type x gypsum board
full height construction
attachement according to resting laboratory standards
what is the building code requirement for pairs of exit doors with astragals
coordinator
a coordinator prevent the door lead with the astragal from closing before the other leaf, so the pair of doors seals properly
how much fire protection rated glazing (wire glass) is permitted in a 1.5 hour rated door in an exterior wall
no glazing is permitted
all glazing in fire rated doors must be
either 1/4 in wire glass or ceramic glazing
a 1.5 hour rated door that is not in a n exterior wall is permitted to have how much glazzing
100 sq in of glazing
a 3/4 rated door is permitted to have much glazing
1296 sq in
a 20 min rated door is allowed to have how much glazing
amount of glazing is not limited
ceramic glazing must comply with
NFPA 80
Standard for fire doors and other opening protectives
the requirement that limited fire extinguisher cabinets from projecting into a space more than 4 in is a standard of
ADA/ABA
according tot eh ADA/ABA guidleines, the ratio of accessible parking spaces to total parking spaces is
1:25 up to 200 spaces, with an additional accessible space for each additional 100 parking spaces up to 500
Above 500 spaces, accessible spaces are determined as a percentage of the total parking spaces provided
what does it mean when a building material is not combistible
a material will not ignite and burn when subject to fire
restrictions on surface finishes in all model codes are based primarily on
loaction in the building and occupancy
construction type refers to
fire resistance ratings of various building components
what is the minimu clear width for an accessible door
32 in
no objects greater than 4 in can protrude into an accessible route if the lower edge of the object is greater than ___ in AFF
27 in AFF
a safe pedestrian walk should not have a slope exceeding ___in/ft perpendicular to the direction of travel
1/4
Model codes limit the areas of the individual exterior wall panels using standard unit glass blcok to
144 sq ft
standard unit glass block is hallow and has a specified thickness of 3 7/8 in
solid glass block is limited to and are of ___ sq ft for both interior and exterior walls.
100 square ft
interior standard unit glass block walls are limited to and area of
250 sq ft