Yup Flashcards

1
Q

Can A RP be installed Vertically?

A

Yes, If approved

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of A DCVA bleed-off valve?

A

SO Valve 1 is leaking

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Do i need a bleed-off valve to test a PVB or SRPVB?

A

Only if SO 1 is passing by in the closed position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the testing procedural step that is common to the RP, DCVA, PVB and SRPVB?

A

Attach High side Hose to TC #2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Prior to recording air inlet fully open requires_____________. (PVB)

A

Draining water from the Valve body (completely)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the differential pressure between CV 1 and RVOP?

A

Buffer/ Minimum 3psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When testing a DCVA using a sight tube how long is the tube?

A

36”(must be able to have 28” of water above the centerline of downstream TC’s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When testing a DCVA using a sight tube how high is water in the tube for CV to pass?

A

Must be hold 28” above centerline of TC 3 or 4 for 2 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When performing test #1 on CV 1 of a DCVA where is the vertical tube connected?

A

TC - 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When performing test # 2 on CV 2 of a DCVA where is the tube connected?

A

TC-4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When testing a DCDA what are the requirements?

A

2 forms and record all pressure losses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How Does a PVB check valve work?

A

Closes in the direction of flow maintaining a 1 PSI differential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If CV 2 failed while testing a RP what would the gauge read?

A

RV opening point pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the purpose of flushing Test Cocks?

A

To remove any foreign material or debris

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is happening if while testing a DCVA after you open TC 3 water flows continuously?

A

SV 1 leaks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A CV in a static condition is ________.

A

Closed

17
Q

When applying a backpressure to a CV 2 on a RPBA you notice a slight drop in ◇ p, what is the cause?

A

Disc compression

18
Q

What is the size of a differential test gauge?

A

4.5”

19
Q

Why does low flow water go through the bypass only on detector assemblies ?

A

Lower ◇ p across 3/4” bypass than main assembly.