Year 2 H6 Flashcards
Define: Overload
moderate increase in current beyond normal rated current value
Some problems caused by overload
Annealing
Rapid oxidation
burning insulation
cracking insulation
Some causes of overload
octopus effect
improper size equipment
worn-out or seized motor bearing
excessive mechanical load
Define: Overcurrent
may range from 6 to many 100 times the normal rated current. fast
An overcurrent can result when:
A motor starts
Short cct occurs
Short cct
larger-than-normal current that flows outside the normal current path.
parallel path of low resistance
Ground fault
another form of short cct. It is a short cct to ground. GFCIs, and GFI
The effects of short ccts
Mechanical forces: bent bus bars and equipment
Thermal energy: I^2R x t
Voltage rating of a protective device is to
Quickly extinguish the arc after the fuse element melts or the cct breaker opens
Prevent the open-cct voltage from restriking
Interrupting rating
max short-cct current an overcurrent device can safely interrupt without damaging itself
time-delay fuses must be marked
with the letter D for delay
non-time delay fuses must be marked
with the letter P for low melting point
inverse time-current characteristic curve
shows that the higher the current, the quicker the fuse opens
a fuse my occasionally open when
ambient temp is high
excessive vibration
loose or dirty connection
When replacing a fuse make sure and observe the correct
voltage rating
Current rating
Interrupting-capacity rating
Time-current characteristics