Wk 3 Flashcards
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1004.6) The occupant load of seating booths shall be based on
one person for each _ inches of booth seat length measured at the
backrest of the seating booth.
24”
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1005.7.1) Doors. Door when fully opened shall not reduce the
required width by more than _ inches
7”
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section Table 1006.2.1) Maximum Common Path of Egress Travel
Distance in a Educational (Group E) Occupancy is_ feet
75ft
According to Book 57 (The 2020 Los Angeles Fire Code- Chapter 10
Section 1006.2.1.1) Three or more exist access doorways. An occupant
load of 500 requires how many exit access doorways?
2
- According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1008.2.1) llumination under normal power. The means of egress
illumination level shall be not less than___ footcandle(s) at the walking
surface.
1 footcandle
According to Book 57 (The 2020 Los Angeles Fire Code- Chapter 10
Section 1008.3.4) Duration> The emergency power system shall provide
power for a duration not less than_ minutes and shall consist of
storage batteries, unit equipment or an on site generator.
90 minutes
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1008.3.3 ) Rooms and Spaces. In the event of power supply
failure, an emergency electrical system shall automatically illuminate all
of the following areas: Electrical Rooms, Fire Command Centers, Fire
Pump Rooms, Generator Rooms and Public Restrooms with an area
greater than_ square feet?
300 sq ft
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1009.3.2) Stairway Width for accessible egress. Stairways shall
have a clear width of _ inches minimum between handrails.
48”
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1011.3 Headroom) Stairways shall have a minimum clearance of
not less than _ inches measured vertically from a line connecting the
edge of nosing.
80”
According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1010.1.10.1) Where panic or fire exit hardware is installed, the
maximum unlatching force shall not exceed _ pounds
15lbs
According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.33.17) Stairway Identification Signs shall be
square with a minimum dimension of __ inches
12”
According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.22.04) Permit. A special permit is required
for storage, display, sale, or other use of Christmas Trees within buildings
where more than_ trees are located.
10
According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.80.09) Spray Booths, A permit is required to
erect, install or relocate spray booths or spray tunnel with any dimension
greater than_ feet
3ft
According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, (Section 57.138.13 Fire Department Connection Signs )
Fire Hose Cabinets that contain a fire extinguisher shall also be identified
with a sign stating “‘Fire Extinguisher* with letter no less than__ inches
on contrasting background.
3 “
According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, (Section 57.30.05) Table 30-B Permits: A Permit is
required for Class IA Flammable liquid in quantities greater than
Gallons
60 gallons
According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Six out of ten fatal home fires
start between the hours of_&?
9pm & 6am
According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Detectors are approved to
give an area coverage equivalent to a_ foot diameter.
25 ft
According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: A Smoke Detector can be
moved __ feet from a bedroom door and still provide coverage.
12.5 ft
According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Only Smoke Detectors
Approve by
can be sold or installed in California
California State Fire Marshal’s Office
According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: All Detectors must meet the
following listing to be approved for use in California?
UL 217
According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) According the
DB11-14 the Los Angeles Fire Department responds to over
Automatic Alarms per month.
1000
According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) According to DB 11
-14 Automatic Alarm Data will be collected on a
basis and a
report of the worst offenders will be provided to the FPB.
Monthly
According to the Los Angeles Fire Department Library. Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) The duration of the
Autoratic Alarm Reduction Program was
6 months
According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) When the fire
department arrives to an Intrusion alarm with no additional activations
the responding Officer is required to provide
with specified
information via email
On Duty OCD Battalion Commander
According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) The Automatic
Alarm Reduction consists of Elements.
3
ACCORDING TO TB 01 2- AUTOMATIC SPRINKLER SYSTEMS, Records *
show that_ of all fires in
sprinklered buildings are extinguished or satisfactorily held in check by
the sprinkler system.
96%
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, NBFU
Bulletin No. 270 suggests that
one of the first fire alarm engine companies responding should lay.
into the fire department
connection.
Two 2 1/2” lines
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, it is
suggested that companies
maintain a list of sprinklered buildings in their district. This information can
be obtained
from the_, which are filed behind the_ in the company files.
F-316s, F-173s
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS “Junior
systems” may be encountered
from time to time which are designed to provide simple, inexpensive
protection for light hazard
occupancies where not over_or__ sprinklers are likely to
likely to operate.
3, 4
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, A
“Junior System” is a loop of three-
fourths of an inch or one inch of copper tubing fitted with small orifice
(one-fourth of an inch or
three-eighths of an inch) sprinklers. They will discharge about _as
much water as the
standard one-half inch sprinkler.
One-Half 1/2
TB #149-RESIDENTIAL SPRINKLER SYSTEMS, states As of January
1, 2011, the State of California is
requiring the installation of residential fire sprinklers in all new one- and
two-family dwellings and
manufactured homes. This mandate uses the NFPA 13D standard that
includes new construction of
garages, patios extending_ from house and unattached structures
greater than
4’, 200 sq ft
ACCORDING TO TB #149- RESIDENTIAL SPRINKLER SYSTEMS, The
International Association of Fire
Chiefs (IAFC) report that approximately 3,000 civilians perish annually
from fire, with nearly two-
thirds of those deaths occurring at
Home
TB #149-RESIDENTIAL SPRINKLER SYSTEMS states sprinkler head
temperatures range from.
degrees and cover a minimum area of,
135 to 175; 12’x12
ACCORDING TO TB #149- RESIDENTIAL SPRINKLER SYSTEMS which
entity plan checks and
approves the installation of residential sprinklers?
Plumbing/Mechanical Engineering Division of LADBS
TB #149-RESIDENTIAL SPRINKLER SYSTEMS STATES LADBS
requires a (minimum) water demand
capable of flowing
for a period of
Two Heads; ten minutes
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1012.2)
Ramps used as part of a means of egress shall have a running slope not
steeper than
vertical in 12 units horizontal (8-percent slope).
One unit
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1013.1)
Exit sign placement in an exit access corridor or exit passageway shall be
within how
many feet?
100 ft
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1013.6.2)
The face of an exit sign illuminated from an external source shall have an
intensity of not less
then how many foot-candles?
5 foot-candles (54 lux)
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1013.6.3)
Illuminated exit signs shall ensure continued illumination for a duration of
not less than
how many minutes in case of primary power loss?
90 mins
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
secion 1015.7 1oof
access) guards shall be provided if the roof hatch is located within how
many feet of a
roof edge?
10 ft
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
Table 1017.2)
Occupancies A, E, F-1, M, R, and S-1 without a sprinkler system require an
exit access travel distance
of 200 feet. The occupancies with a sprinkler system require a travel
distance of how many
feet?
250 ft
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1020.4
Dead ends) Where more than one exit or exit access doorway is required,
the exit
access shall be arranged such that dead-end corridors do not exceed
how many feet in
length?
20 ft
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1023.2)
Interior exit stairway and ramp enclosures shall have a fire-resistance
rating of not less
than _ _ where connecting four stories or more.
2 hours
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1023.2)
Interior exit stairway and ramp enclosures shall have a fire-resistance
rating o not less
than _ _ where connecting less than four stories.
1 hour
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10
section 1030.3)
Emergency escape and rescue openings shall have the bottom of the
clear opening not
greater than_ inches measured from the floor.
44 inches
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS,
DIVISION 1, SECTION 3.07 ()
CLEARANCES, No combustible material shall be placed or stored within
how many feet of any
building or structure?
10 feet
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS,
DIVISION 1, SECTION 320, FIRE
SAFETY PERSONNEL, the owners and operators of any tent used as a
place of assemblage shall
provide at least one fire life safety person in every tent having a capacity
of_persons and
one additional qualified person for each - additional persons or fraction
thereof.
500, 1000
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS,
DIVISION 1, SEC 568, TABLE 2,
extinguishers with a 2-A and 4-A rating for low, moderate, and high class
A hazards shall have a
maximum travel distance of how many feet?
75 ft
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS,
DIVISION 1, SEC 904.2(h)
TESTING AND MAINTENANCE REQUIREMENTS, who shall be consulted
to avoid unnecessary
disturbance of normal building operation at time of testing and
maintenance?
Building Management
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS,
DIVISION 1, SEC 904.2(c)
TESTING AND MAINTENANCE REQUIREMENTS, records of all testing and
maintenance shall be
retained on the premises by the building or system owner for a period of
how many years after
the next required test or maintenance?
5 years