Wiring Procedures For Fire Alarm Systems Flashcards

1
Q

The disconnecting means for the primary power supply of a F.A.S must be lockable in the ON position. T or F?

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The Emergency power supply of a F.A.S must be provided by a generator that is capable of operating at full load for not less than four hours. T or F?

A

False, not less than 2 hours is correct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A zone cannot cover more than one storey in a building. T or F?

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In a Class B fire alarm circuit, the field devices are connected in series. T or F?

A

False, they’re connected in Parallel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The _____ device is what facilitates the required amount of supervisory current to flow through the circuit.

A

End of line device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

In Conventional Class B circuit, a short circuit in the NAC causes what condition at the control panel?

A

Trouble

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

In a Class A circuit, a single open circuit in the wiring may cause a device, intiating or signalling to become inoperable. T or F?

A

False, they will not become inoperable under a single short circuit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How is a tamper device installed in regards to a sprinkler device?

A

Wired in series with the EOL device after the flow switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does a control valve switch detect?

A

The position of the valve, if it’s been changed and if it has, cause a supervisory condition at the F.A.C.P

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fault Isolator Modules are used in what sort of circuits?

A

DCLC or Class C circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What sort of modules are required for a fire door to close or HVAC units to shut off automatically during a fire?

A

Control Modules

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is another name for an extender panel?

A

Booster Panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What can be done to reduce the number of cables that need to be run all the way back to a F.A.C.P?

A

A transponder can be utilized.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The wiring of Fire Alarm circuits must conform to ULC-S524 and the ____.

A

CEC / Canadian Electrical Code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Conventional (non-addressable) can be Class A only. T or F?

A

False. They can be Class A or B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The three main types of addressable fire alarm circuits are:

A

DCLA
DCLB
DCLC

17
Q

What would be the result of a short circuit in the DCLB wiring of a two-stage addressable F.A.S?

A

The system would initiate a trouble signal.

18
Q

What section of the CEC pertains to Fire Alarm Requirements?

A

Section 32

19
Q

The secondary power supply of a F.A.S will be one or more power sources. T or F?

A

True

20
Q

Whats does IDC and NAC stand for?

A

Initiating Device Circuit
Notification Appliance Circuit