Week 4 Flashcards

1
Q

What is the power leg voltage in a 120/240 3ph service?

A

208 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

WYE or DELTA? 120/208

3 ph service

A

WYE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

In a WYE-WYE bank, what must be done to the H2s on each transformer?

A

Tie them together and connect to neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In a WYE-WYE bank, why is it important to parallel the secondary windings?

A

To get the full kVA rating from the transformer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the hot-leg-to-hot-leg voltage (p-p) in a standard 120/208 3ph service?

A

208 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many “power” transformers are there in a closed-DELTA bank?

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What must be done to the secondary coils in a DELTA-WYE bank?

A

They must be paralleled; AC-BD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In a 240 3ph-3wire service, what happens if one phase gets grounded?

A

Nothing. It becomes a corner ground, and the 3-phase service is still delivered. You can ground one time at any point in the service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

WYE or DELTA? 240/480

3 ph service

A

DELTA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the power-leg-to-hot-leg voltage in a 120/240 3ph service?

A

240 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does “Alley-Cat, Bad-Dog” mean?

A

When paralleling the windings for a WYE secondary, open the lid and connect A and C together to X1, and then B and D together to X2.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

WYE or DELTA? 277/480 3 ph service

A

WYE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

In a WYE-WYE bank, what must be done to the X2s on each transformer?

A

Tie them together and connect to neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

In a WYE-DELTA bank, what must be done to the H2s on each transformer?

A

They must be tied together, but not grounded or connected to neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly