Week 2 Flashcards

1
Q

Provide three advantages that three-phase systems have over single-phase systems.

A

Increase in power capability
Less pulsating on rotating generators and motors
Generators, transformers, and motors are smaller and less expensive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How far apart are the three coils of a generator from one another?

A

120 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How many times does the voltage fall to zero in one cycle?

A

Three times

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If the system voltage is 12,470 volts, what would the coil voltage be in a WYE configuration?

A

7,200 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If the phase current in a WYE system is 40A, what is the coil current?

A

40 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If the coil voltage in a DELTA system is 12,000 volts, what is the system voltage?

A

12,000 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Why could linemen work barehanded on the older DELTA systems back in the day?

A

Because there was no ground or neutral reference. If there was nothing touching the other phases on the circuit, like a tree limb or another lineman, then there was no short circuit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Why is it hard to tell the difference between a DELTA and an ungrounded WYE in the field?

A

Because neither system has a system neutral.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is meant by “phase sequence”?

A

Phase sequence is the direction a motor will spin, based on how it is connected to the system. If the sequence is unchanged, the motor will spin the same direction as the generator.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

You are reading the phase sequence on a 7,200/12,470-volt system with a high-voltage phasing meter. You read across an open cut-out (from top to bottom) and you read 12,470 volts. What does this mean?

A

The phase sequence is changed. DO NOT CLOSE THAT CUTOUT!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly