Q

W1

TEMPORARY CONSTRUCTION METER

A

10” GAP FOR METER
BACKFLOW REQUIRED
INSTALL AND REMOVED ONLY BY PCU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

W2

LARGE 3” AND ABOVE METER W/ SINGLE BFP

A

BFP EQUAL TO SIZE OF METER
ABOVE GROUND PIPING TO BE GLANGED DI PIPE
PCU MAY REQUIRE FENCE AROUND ASSEMBLY
ABOVE GROUND PIE = SAME SIZE AS METER INLET
IF PROVIDING FIRE PROTECTION, BYPASS = 6”
PROVIDING WATER ONLY, COMPOUND METER REQUIRED
SLAB 1’ FROM BYPASS, 2’ FROM ALL OTHER PIPING

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

W3

LARGE 3” AND ABOVE METER W/PARALLEL BFP

A

BFP EQUAL TO SIZE OF METER
ABOVE GROUND PIPING TO BE GLANGED DI PIPE
PCU MAY REQUIRE FENCE AROUND ASSEMBLY
ABOVE GROUND PIE = SAME SIZE AS METER INLET
IF PROVIDING FIRE PROTECTION, BYPASS = 6”
PROVIDING WATER ONLY, COMPOUND METER REQUIRED
SLAB 1’ FROM BYPASS, 2’ FROM ALL OTHER PIPING

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

W4

NOTES

A

DISSIMILAR METALS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

W5

BFP 3/4”-2”

A
EXPANSION JOINTS SCH 40 SLEEVING
2' AROUND BFP FOR TESTING
1' MINIMUM BETWEEN SLAB AND BFP
SLAB 1' AROUND ENTIRE ASSEMBLY
PAINTED BLUE
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

W6

PARALLEL BFP

A
EXPANSION JOINTS SCH 40 SLEEVING
2' AROUND BFP FOR TESTING
1' MINIMUM BETWEEN SLAB AND BFP
SLAB 1' AROUND ENTIRE ASSEMBLY
PAINTED BLUE
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

W7

DOUBLE CHECK W / DETECTOR 3”-12”

A
3' AROUND ENTIRE DEVICE FOR TESTING
PAINTED SAFETY RED
ABOVE GROUND PIPING FLANGED
AMR
EXPANSION JOINTS
PIPE SUPPORTS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

W8

RPZ 3/4”-2”

A
1' AROUND ASSEMBLY
1' SLAB TO PIPING, 4" SLAB
1' BETWEEN DUMP AND SLAB
EXPANSION JOINTS
PAINTED BLUE
4 4" BOLLARDS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

W9

PARALLEL RPZ 3/4”-2”

A

4 4” BOLLARDS
2’ MINIMUM DUMP TO SLAB
PAINTED BLUE
SLAB EXTENDS 1’ AROUND ENTIRE ASSEMBLY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

W10

RPZ 3” - 8”

A
4 6" BOLLARDS
2' MINIMUM DUMP TO SLAB
PAINTED RED
SLAB EXTENDS 2' AROUND ENTIRE ASSEMBLY
PCU OPTION TO ENCLOSE IN FENCE
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

W11

WATER CONNECTION WITH FIRE PROTECTION

A
1 TAPPING VALVE
INDIVIDUAL ISOLATION VALVES
15 X 15 UTILITY EASEMENT
TREE CLEAR ZONE 7.5' EACH SIDE
1 DDCVA, 2 BFPD
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

W12

WATER CONNECTION WITHOUT FIRE PROTECTION

A
1 TAPPING VALVE
INDIVIDUAL ISOLATION VALVES
15 X 15 UTILITY EASEMENT
TREE CLEAR ZONE 7.5' EACH SIDE
2 BFPD
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

W13

FIRE HYDRANT PERPENDICULAR TO MAIN

A

3’ CLEAR ALL SIDES
YELLOW W / CAPS AND BONNET PAINTED PER FLOW RATE
18” MINIMUM 24” MAXIMUM MIDDLE FRONT STEAMER
MAXIMUM 20’ HYDRANT TO OPERATING VALVE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

FLOW RATES

A

BELOW 500 GPM = RED
500-1000 GPM = ORANGE
1000-1500 GPM = GREEN
ABOVE 1500 = BLUE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

W14

FIRE HYDRANT

A

3’ CLEAR ALL SIDES
YELLOW W / CAPS AND BONNET PAINTED PER FLOW RATE
24” MINIMUM 24” MAXIMUM MIDDLE SIDE STEAMER
MAXIMUM 10’ HYDRANT TO OPERATING VALVE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

W15

FIRE HYDRANT

A

3’ CLEAR ALL SIDES
YELLOW W / CAPS AND BONNET PAINTED PER FLOW RATE
24” MINIMUM 24” MAXIMUM MIDDLE SIDE STEAMER
MAXIMUM 10’ HYDRANT TO OPERATING VALVE