Volume 3 - Contingency Power Flashcards
Expeditionary Resources
The Air Force uses which deployable assets for beddown of combat expeditionary forces?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Basic Expeditionary Airfield Resources (BEAR)
M3L1T1 - Basic Expeditionary Airfield Resources (19.5.1)
What dictates how and when BEAR assets deploy under the BEAR Order of Battle concept?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Air & Space Expeditionary Task Force
M3L1T1 - Basic Expeditionary Airfield Resources (19.5.1)
According to BEAR Order of Battle concept, the XFAPH High Power Unit Type code provides two BEAR Power Units and what additional equipment?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Two 10K fuel bladders
M3L1T1 - Basic Expeditionary Airfield Resources (19.5.1)
What factor should be considered to prevent environmental damage during BEAR operations?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Hazardous waste storage and disposal
M3L1T1 - Basic Expeditionary Airfield Resources (19.5.1)
Why must total diversified load be calculated?
Lesson 1 Basic Expeditionary Airfield Resources Systems
To decide the correct number of low and high voltage generators.
M3L1T2 - Contingency Electrical Planning (19.5.2)
If loads are not balanced properly between phases, how will this affect the generator?
Lesson 1 Basic Expeditionary Airfield Resources Systems
The generator will not support full load or regulate voltage.
M3L1T2 - Contingency Electrical Planning (19.5.2)
If the base is located in a high threat location, what must be done to the electrical system?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Utilize a loop system to distribute electrical power.
M3L1T2 - Contingency Electrical Planning (19.5.2)
Why should power plants have the capability of being electrically interconnected?
Lesson 1 Basic Expeditionary Airfield Resources Systems
To ensure some degree of electrical generation after an attack.
M3L1T2 - Contingency Electrical Planning (19.5.2)
Why does the Primary Switching Center allow for a safer working environment when dealing with the primary distribution system?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Because the SF6-insulated take prevents arching.
M3L1T3 - Primary Distribution System (19.7.1)
The contingency environment for installing a Primary Switching Center must be what?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Firm and well drained
M3L1T3 - Primary Distribution System (19.7.1)
3E0X1 personnel will assemble and install _____ onsite prior to making connections to the equipment.
Lesson 1 Basic Expeditionary Airfield Resources Systems
Load brake elbow connectors
M3L1T3 - Primary Distribution System (19.7.1)
Why must the primary distribution cables be as short as possible when installed at a bare base?
Lesson 1 Basic Expeditionary Airfield Resources Systems
To prevent voltage drop at the secondary distribution center.
M3L1T3 - Primary Distribution System (19.7.1)
On an SDC, what prevents power from being supplied to both the primary and the alternate power source?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Positive locking bar
M3L1T4 - Secondary Distribution System (19.7.2)
When using a 60 kW Power Distribution Panel, how many 25kW Power Distribution Panels can be connected to it?
Lesson 1 Basic Expeditionary Airfield Resources Systems
4
M3L1T4 - Secondary Distribution System (19.7.2)
When installing BEAR base 60-amp secondary cable assemblies, the maximum distance of cable runs is _____, if no other alternative exists.
Lesson 1 Basic Expeditionary Airfield Resources Systems
800’
M3L1T4 - Secondary Distribution System (19.7.2)
To supply power from the primary distribution system to the 16 low-voltage outputs of the Secondary Distribution Center, what must occur first?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Get stepped down by the 150kVA transformer.
M3L1T4 - Secondary Distribution System (19.7.2)
Maintenance personnel must exercise extreme caution at all times. What could the consequences of carelessness and accidental contact be?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Severe injury or death
M3L1T5 - Medium Voltage Safety
When grounding power plant units, what should be referenced?
Lesson 1 Basic Expeditionary Airfield Resources Systems
The technical order
M3L1T5 - Medium Voltage Safety
What should personnel wear when performing tasks on medium voltage power distribution components?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Arc thermal protective value rated clothing.
M3L1T5 - Medium Voltage Safety
Who is authorized to disconnect power plant output cables?
Lesson 1 Basic Expeditionary Airfield Resources Systems
Electrical Systems personnel
M3L1T5 - Medium Voltage Safety
Which generator operating mode employs an electronic governor?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
Precise
M3L2T1 - Construction Features & Components of 200 kW or Less Mobile Generators (19.1.1.1)
What characteristic describes an 800 series MEP unit?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
Employs sound absorbant technology.
M3L2T1 - Construction Features & Components of 200 kW or Less Mobile Generators (19.1.1.1)
Which MEP unit utilizes full control authority for fuel governing?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
AMMPS
M3L2T1 - Construction Features & Components of 200 kW or Less Mobile Generators (19.1.1.1)
What characteristic describes the legacy MEP units?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
Primarily mechanical and electromechanical parts.
M3L2T1 - Construction Features & Components of 200 kW or Less Mobile Generators (19.1.1.1)
When using the American Wire Gauge system for cable selection the higher the gauge number indicates what?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
Smaller cross-sectional area
M3L2T2 - Fundamentals of Cables (19.1.1.3.1)
Aluminum cables are generally selected for use in what?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
High voltage applications
M3L2T2 - Fundamentals of Cables (19.1.1.3.1)
If using a multi-conductor cable assembly then you must ensure?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
The cables have the proper number of conductors for the application
M3L2T2 - Fundamentals of Cables (19.1.1.3.1)
The #1 criteria for selecting cables is?
Lesson 2 Basic Expeditionary Airfield Resources 200kW and Below
Can the cable safely conduct the current of the load.
M3L2T2 - Fundamentals of Cables (19.1.1.3.1)