Stairshafts in high rise buildings constructed after ___ are required to employ a stairshaft ventilation system.
1974
Fan must provide not less than ____ while maintaining a positive pressure of not over ___ on interior doors
50 cubic feet per minute / 25 lbs
Pre-60 has _____ windows
openable
Post-60 has ___
tempered glass on at least two sides of the building
Post-60 Tempered glass location
at corners, and at 50 foot intervals or less
Post-74 has ____
tempered glass on four sides of the building
Post 74 Tempered glass location
at corners and at 50 foot intervals or less
Tempered glass windows are identified by ___
3 inch luminous or reflective decals in a lower corner which indicated for For FD use
Post 1996 “Uniform building code”
Requirement of smoke control systems in high rise buildings eliminated the requirement of installation of tempered glass
Prior to breaking windows….
radio notification shall be made indication the need and intention to break glass and the specific side of the building
Natural air flow within building stairshafts is virtually static in buildings up to ___
25 stories
Buildings over 25 stories will naturally flow
minimal amounts of air in an upward direction
Natural vertical air currents of ____, can be created by simply opening a door at the bottom and roof levels of a stair shaft
3 to 6 mph
High rise buildings constructed after ____ are required to employ an _____
1974 / emergency smoke control system
3 components of an emergency smoke control system
Pressurized stairshaft, mechanical smoke removal system, tempered glass or openable windows