Unit 3 Boiler Safety Devices Flashcards
When the energy output and the energy demand are equal, the boiler pressure
Select one:
a. becomes unstable
b. rises
c. falls
d. remains constant
d. remains constant
An important fitting, which is installed between a steam boiler pressure gauge and the boiler itself and is designed to prevent damage to the gauge, is a: Select one: a. Tee with a plug b. Syphon c. Blowdown valve d. Test connection for an inspector
b. Syphon
Primary controls, as used in a burner management system:
Select one:
a. Should be cleaned of carbon deposits monthly.
b. Generate a voltage, which is then used to monitor flames.
c. must shut off the fuel within four seconds of flame failure.
d. Are unreliable and unsafe.
c. must shut off the fuel within four seconds of flame failure.
All boiler fittings not properly or clearly identified:
Select one:
a. Must not be used
b. May be used for low pressure services
c. Are acceptable for some powerhouse piping applications.
d. Must be sent back to the manufacturer for proper identification.
a. Must not be used
Testing a safety valve on a boiler by pulling the try-lever
Select one:
a. Ensures the popping pressure is correct
b. Ensures the closing pressure is correct
c. Takes approximately two seconds
d. Ensures the valve is free to operate
d. Ensures the valve is free to operate
In hot water boiler firing rate control systems, the measured variable is
Select one:
a. the inlet water temperature
b. the outlet water pressure
c. the combustion air pressure
d. the outlet water temperature
d. the outlet water temperature
Tubular gauge glasses:
Select one:
a. Are suitable for pressures up to about 3000 kPa
b. Are made of glass, in order to resistant boiler alkalinity
c. Indicate the level more accurately than other forms of water level indication
d. Can only be installed on low-pressure boilers
a. Are suitable for pressures up to about 3000 kPa
Every steam boiler must have a safety valve that is:
Select one:
a. Placed in the piping system leading from the steam stop valve.
b. Fitted securely to a shut-off valve, which is directly connected to the top of the boiler.
c. Fitted in a vertical position, directly connected to the top of the boiler.
d. Connected to the steam or water space of the boiler, without any intervening fitting.
c. Fitted in a vertical position, directly connected to the top of the boiler.
An outside screw and yoke valve: Select one: a. Must be a gate valve b. Shows its operating position c. Is difficult to lubricate d. Requires no packing
b. Shows its operating position
The popping pressure of a safety valve \_\_\_\_\_\_\_\_\_\_\_\_\_\_\_\_ without replacing its spring: Select one: a. Cannot be changed b. Can only be increased by 5% c. Can only be decreased by 5% d. Can be changed by plus or minus 5%
d. Can be changed by plus or minus 5%
A safety relief valve is similar to a safety valve except that it:
Select one:
a. Does not have a blowdown ring or bottom guides
b. Must have greater blowdown
c. May have an isolation valve placed between it and the pressure vessel
d. Must discharge directly to the atmosphere
a. Does not have a blowdown ring or bottom guides
When an automatic unattended boiler starts up, the programming control will first:
Select one:
a. Energize the ignition transformer and pilot gas solenoid valve
b. Start the post purge period
c. Start the forced draft fan
d. Energize the main gas valve
c. Start the forced draft fan
What is responsible for the “popping action” of a safety valve? Select one: a. Amount of spring compression b. Blow down ring adjustment c. A lip on the valve disc d. Temperature of the steam
c. A lip on the valve disc
A low water fuel cutoff on an unattended steam boiler shall be installed so that
Select one:
a. It cannot be rendered inoperative
b. It starts the feed water pump
c. It can be isolated if it is not required
d. It shuts down the burner when the water level falls below the lowest visible part of the gauge glass.
a. It cannot be rendered inoperative
How many blow-off valves are required by most power boilers? Select one: a. Zero b. One c. Two d. Three
c. Two
What is the purpose of the high limit control on a hot water boiler?
Select one:
a. To stop the boiler if the water level control fails.
b. To act as a emergency stop for the operator
c. To shut down the burner if the water temperature exceeds 121 degrees Celsius.
d. To prevent the boiler pressure from rising above 1100 kPa gauge.
c. To shut down the burner if the water temperature exceeds 121 degrees Celsius.
After extinguishing the main flame, the next step in a programmed burner shutdown is
Select one:
a. The timer motor stops
b. A post-purge begins.
c. Operation control switch contacts close
d. Flame failure switch contacts open
b. A post-purge begins.
The type of firing rate control frequently used on small capacity packaged boilers is: Select one: a. a modulating control b. a high fuel pressure cut-off c. a constant pressure control d. an on/off control
d. an on/off control
When is a stop valve allowed between a heating boiler’s safety valve and the boiler drum?
Select one:
a. Only if the stop valve is locked open
b. If there is more than one safety valve
c. Never
d. If the stop valve is the quick opening design
c. Never
If a boiler produces steam at a higher rate than the rate of steam consumption, and this condition goes unchecked
Select one:
a. soot will develop on the fireside
b. the boiler efficiency will drop
c. the boiler will over-pressurize
d. the boiler will overheat
c. the boiler will over-pressurize
A boiler with a single safety valve has a maximum allowable working pressure of 1000 kPa. What is the maximum boiler pressure permissible when the safety valve is blowing? Select one: a. 1060 kPa b. 1000 kPa c. 1030 kPa d. 1100 kPa
a. 1060 kPa
What does the boiler inspector do to prevent tampering with the settings of a safety valve? Select one: a. Installs a gag b. Installs a seal c. Plugs the adjusting hole d. Covers the valve
b. Installs a seal
Flat glass water gauges are often used because:
Select one:
a. It is easier to see the level
b. A light can be installed behind them
c. They are more compact
d. They can withstand higher pressures than tubular gauge glasses
d. They can withstand higher pressures than tubular gauge glasses
An automatic boiler on-off firing rate control has one adjustment for pressure set-point and another for:
Select one:
a. Differential adjustment
b. Manual or automatic control
c. Water level adjustment
d. High steam pressure limit set point adjustment.
a. Differential adjustment
A feedwater pipe, where connected to a power boiler, must have:
Select one:
a. A check valve, with a stop valve between the check valve and the boiler
b. A check valve between the stop valve and the boiler
c. A stop valve only
d. A quick and slow opening stop valve
a. A check valve, with a stop valve between the check valve and the boiler
When used on a boiler, modulating combustion control will:
Select one:
a. Change air and fuel flow proportionally to changes in steam pressure
b. Always be at set point when demand is at 50%
c. Alter only the air flow if a selector station is on manual
d. Respond to changes in atmospheric pressure
a. Change air and fuel flow proportionally to changes in steam pressure
A packaged steam boiler modulating combustion control system will routinely:
Select one:
a. Maintain drum level within a desired range
b. Maintain flue gas temperature at some set point
c. Maintain boiler steam pressure within a desired range
d. Alter flue flow without changing the air flow
c. Maintain boiler steam pressure within a desired range
If a high pressure boiler is on high fire with the main steam stop valve closed, the safety valves must ensure that the:
Select one:
a. Boiler pressure does not exceed the maximum allowable working pressure of the boiler by more than 6%.
b. Boiler pressure does not exceed the set point of the safety valve.
c. Steam pressure does not exceed the maximum allowable working pressure of the boiler.
d. Boiler pressure does not exceed the hydrostatic test pressure.
a. Boiler pressure does not exceed the maximum allowable working pressure of the boiler by more than 6%.
The lowest visible point of the gauge glass for a horizontal firetube power boiler with diameter greater than 400 mm must be:
Select one:
a. Level with the highest fire tube
b. Level with the normal water level
c. 25 mm below the highest fire tube
d. 75 mm above the lowest permissible water level
d. 75 mm above the lowest permissible water level
When starting up a cold boiler with a fully modulating firing rate control, it must be
Select one:
a. limited to low-fire until the boiler is sufficiently warm.
b. kept on manual high-fire, to reduce flue gas condensation losses.
c. placed on manual high-fire to raise the boiler temperature or pressure as fast as possible.
d. kept on automatic, to prevent thermal shock.
a. limited to low-fire until the boiler is sufficiently warm.
The prime importance of boiler fittings is: Select one: a. Economics b. To satisfy regulations c. Safety & efficiency d. Convenience
c. Safety & efficiency