Low pressure systems operate in _______.
Vacuum below atmosphere pressure
Leaks and gaskets or fittings will cause what to enter into the system?
Air and moisture
Low pressure chiller Purge Units
Purge units removed, noncondensibles that leak into low pressure chiller systems
Excessive running of the purge system generally indicates what?
Leaking system
What is the maximum test pressure or a low pressure centrifugal chiller with nitrogen?
10 psig. Exceeding could cause the rupture just to fail.
What is the high-pressure cut out control typically set for on a recovery unit used for evacuating/recovering the refrigerant from a low pressure chiller?
10 psig
After all the liquid has been removed, an average 350 ton R123 chiller at 0 psig would still have approximately _______ pounds of refrigerant in the vapor state?
100 pounds
When removing refrigerant oil, it should be heated to _______ degrees as less refrigerant will be contained in the oil at higher temperature 
130 degrees F
What will help make refrigerant recovery go faster in chiller type equipment?
Systems, water pumps, recovery, compressor and recovery condenser water should all be on during vapor or liquid removal from a low pressure refrigeration system. Raising room temperature will also result in faster recovery 
Before disposing of a low pressure appliance, the refrigerant must be recovered or evacuated to ______mm of Hg absolute?
25 mm of HG