Trips Flashcards
Low Pressure
1950 psig 2/4
High Pressure
2385 psig
High Lpzr
90% 2/3
S/G Lo-Lo Lvl
15% 2/3 sensors 1/4 loops
Time delay when < 50% power.
Turbine Trip
Auto Stop Oil < 50psig (2/3) OR Stop Valves Closed (4/4)
Manual
1/2
Safety Injection
Any S Signal
Seismic
.3 G on 2/3 sensors in the same direction
SSPS General Warning
Train A & B SSPS simultaneously (2/2)
SR Hi Flux
10^5 cps (1/2)
IR Hi Flux
25% Current equivalent (1/2)
PR Hi Flux Low
25% Power (2/4)
PR Hi Flux Hi
109% (2/4)
PR + Rate
+5% power in 2 seconds (2/4)
OT∆T
120% +/- penalties (2/4)
OP∆T
107.2% - penalties (2/4)
Low Loop Flow
90% 2/3 sensors
2/4 Loops (<P-8)
1/4 Loops (>P-8)
RCP Breaker Open
2/4 Loops
RCP Bus UV
8050V (1/2 sensors on 2/2 buses)
RCP Bus Underfrequency
54 Hz (2/3 Sensors on 1/2 buses)