Treatment Plant Design Criteria Flashcards

1
Q

What is the detention time for a flash mixer?

A

Not to exceed 30 Seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the detention time for Flocculation?

A

At least 30 mins w/ 45 mins recommended

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum detention time for Sedimentation?

A

4 hours for conventional, 3 hours for iron removal, 1 hour if tube settlers are used.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What types of filters are approved by TDEC?

A

Gravity and pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Can you use pressure filters for surface water treatment?

A

No, or for lime softening plants.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many chlorinators do you have to have?

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How often does the air in a Chlorine room have to change?

A

Once per minute.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where is the air outlet for a chlorine room?

A

Near the floor.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is the air inlet for a chlorine room?

A

Near the ceiling.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the best method to check for small chlorine leaks?

A

A chlorine detector.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What can you use to check chlorine cylinders for leakage?

A

26 baume ammonium hydroxide

How well did you know this?
1
Not at all
2
3
4
5
Perfectly