Transformers: Chapter 6 - Possible Test Questions - WEEK 13 Flashcards
WYE - WYE BANK:
- With a Wye - Wye bank, each transformer is connected to the system between a phase and grounded neutral.
- In addition, each of the three transformers provide one hot leg on the secondary side to deliver three- phase power. For this reason, three-phase power can only be supplied with three transformers.
An open bank would not provide three-phase power if the secondary were connected:
- Open WYE
WYE - WYE BANK (SECONDARY)
- The secondary coils are paralleled, leaving the x3 lug idle. It is strongly recommended that paralleling be done between the xl and x2 rather than the x1 and x3. The x2 bushing is considered the neutral position and should be treated as such.
Wye connected banks have two main advantages:
- All three transformers can share the single-phase load equally.
- They can be built using single or dual primary bushing transformers.
The disadvantage for a WYE-WYE Bank:
- is that if one transformer fails, the customer is down to one phase until the defective transformer is fixed or replaced.
WYE - DELTA BANK:
- With a Wye - Delta bank, each transformer is connected to the system and the Wye point is floated (not grounded). Because the Wye point is floated, transformers with two primary bushings must be used.
WYE - DELTA BANK
- With one unit out of service, a bank of single-phase units can be reconnected as an:
- open Wye - open Delta, which may temporarily supply power to the customer until permanent repairs are made.
WYE - DELTA BANK
- Grounding the Wye point would create a:
- ground source for the primary system. This could subject the transformer to severe overloading during a primary system disturbance or load imbalance. Because the Wye point is floated, this connection can be used on both three- and four-wire systems.
WYE - DELTA BANK
- With one unit out of service, a bank of single-phase units can:
- be reconnected as an open Wye - open Delta, which may temporarily supply power to the customer until permanent repairs are made.
WYE - DELTA BANK
- How are he secondary coils are connected:
- in series.
WYE - DELTA BANK
- The voltage between the neutral and the power leg (designated as ‘p’ above) is:
- 1.73 times greater than the neutral to hot leg voltage.
WYE - DELTA BANK
- The power leg has no use electrically and is simply a by-product of a:
- Delta secondary. Three-phase motors only see the h - h voltage and do not “notice” the power leg. It is very important to avoid confusing the power leg with hot legs when connecting to 120-volt lighting loads.
WYE - DELTA BANK
- The floating Wye point can be a:
- hazard to lineworkers because it is not grounded.
WYE - DELTA BANK
A power leg only exists on:
Delta and open Delta secondaries when a ground is attached to the winding midpoint of one of the transformers.
WYE - DELTA BANK
Delta secondaries do not allow all three transformers to:
share the single- phase load equally; therefore, one transformer of the bank must provide the majority of the lighting load. It will always be the transformer with the x2 grounded serving as a neutral. Because this transformer must provide the majority of the single-phase load, it must be sized larger than the other two transformers in the bank, and is referred to as the lighter transformer because it handles the “lighting” load. The other transformers share somewhat equal portions of single-phase and three-phase load and are referred to as power transformers.