Transformer Operation 1 Φ Flashcards

1
Q

What is transformer action?

A

Electromagnetic (mutual) Induction.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Why is an equivalent circuit of a transformer useful?

A

It allows us to see clearly, the volt drops which affect a fully loaded transformer’s output.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Is current flowing in an open secondary transformer, with it’s primary connected to source?

A

Yes, there will be a small exciting current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Does secondary current flux enhance the exciting flux?

A

No, it opposes exciting flux.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What property is the net flux of a loaded transformer most closely related to?

A

The exciting flux.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is Voltage regulation?

A

The change in a transformer’s output voltage from no load to full load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Who is under the table?

A

The fully loaded guy.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How are core losses of a transformer determined?

A

An open circuit test, using a wattmeter in the primary.

I2R losses can be ignored since exciting current is so low.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Do core losses increase as load is added to a transformer?

A

No, they are (roughly) constant with a consistent applied voltage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Do copper losses vary with load?

A

Yes, they are proportional to the square of the current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How can Full load copper losses be determined?

A

With a short circuit test, and a wattmeter in the primary.

Applied V is low so core losses are minimal and may be ignored.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the copper losses at one half load?

A

They are one quarter of full load losses.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How is efficiency in a transformer calculated?

A

It is the ratio of useful power output to power input.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which factors affect a transformer’s efficiency?

A
  • Load capacity. As load is decreased, efficiency is as well
  • Power factor. As pf increases, efficiency does as well.
  • Losses. As losses increase, efficiency decreases.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is impedance voltage?

A

The primary voltage required to circulate rated secondary current in a short circuited winding.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How is available fault current calculated?

A

It will be the full load secondary current divided by the percent imdedance.

17
Q

Why would transformers be paralleled?

A

To increase the capacity and reliability of a system.

18
Q

Which precaustions should be observed when paralleling transformers?

Why?

A

VS must be equal. (Unnecessary heating);

Same tap settings. (Different VS);

%IZ within 5% of eachother. (Disproportionate loading);

Must be connected in phase [observe polarity]. (Fault condition).

19
Q

What is a backfeed?

A

When one transformer coil induces voltage onto a paralleled, presumably “disconnected” coil.

To avoid this, always ensure the transformer is disconnected from all circuitry.

20
Q

If a transformer has 1 coil on the primary and 2 coils on the secondary and it is feeding a 120/240 V load, how is it connected?

A

The secondary coils are in series, with a tapped neutral at the mid point.

The max load allowable is a series load.