Traing Bulletins Flashcards
Portable Extinguishers
Purple K
Agent
Use
Capacity/Total Weight
Range
Discharge Time
Examine
Temp Range
Maintenance
Agent: Potassium Bicarb base dry chem
Use: Class B, particularly methanol
Capacity/Total Weight: 27lbs of agent, 52 total
Range: 19-20’
Discharge Time: 11 seconds
Examine: Each tour
Temp Range: -40 to 120
Maintenance: Thoroughly examine monthly, RT2 to tech services if needed
Portable Extinguishers
Dry Chem
Agent
Use
Capacity/Total Weight
Range
Discharge Time
Examine
Temp Range
Maintenance
Agent: Bicarb of soda with drying additive to absorb moisture
Use: Class B, C, A-Small surface
Capacity/Total Weight: According to wight in lbs of dry chem @ 150 psi
Range: 5&10lbs ~ 4 to 12’
Discharge Time: 5&10lbs ~ 10 to 16 secs
Examine: Each tour
Temp Range: -40
Maintenance: Thorough exam every 6 months
Portable Extinguishers
Pressurized Water
Agent
Use
Capacity/Total Weight
Range
Discharge Time
Examine
Temp Range
Maintenance
Agent: Water
Use: Class A
Capacity/Total Weight: 2.5 gallons @ 100 psi
Range: 35 to 40’
Discharge Time: 55 secs
Examine: Each Tour
Temp Range: Above freezing
Maintenance: Check every part!
Portable Extinguishers
Pump Tank
Agent
Use
Capacity/Total Weight
Range
Discharge Time
Examine
Temp Range
Maintenance
Agent: Water
Use: Class A
Capacity/Total Weight: 5 gallons ~ 50 lbs
Range: 30 to 40’ max
Discharge Time: As fast as pumped
Examine: Each tour
Temp Range: Above freezing
Maintenance: Oil on piston rod packing, air vent open, check all parts