Topic Quiz: 8-Hour Electrical Flashcards
A panel board requiring access while energized SHALL be provided with a minimum of _____ depth measured int the direction of access.
a. 30’’
b. 36’’
c. 42’’
d. 48’’
b. 36’’
[IRC E3405.2]
Workspace in front of an electrical panel board shall be a minimum of _____width but not less than the width of the panel board.
a. 30’’
b. 36’’
c. 42’’
d. 48’’
a. 30’’
[IRC E3405.2]
The minimum size of conductors for feeders & branch circuit conductors shall be _____ copper.
a. #16 AWG
b. #14 AWG
c. #12 AWG
d. #10 AWG
b. #14 AWG
[IRC E3406.3]
The minimum clearance for a recessed incandescent light from a combustible material is a closet is _____.
a. 2’’
b. 4’’
c. 6’’
d. 8’’
c. 6’’
[IRC E4003.12 (3)]
A minimum of ______ is required for a GFCI outlet or switch from a spa or hot tub.
a. 3’
b. 5’
c. 6’
d. 8’
b. 5’
[IRC E4203.2]
______ is the minimum distance for a GFCI protected outlet from a swimming pool.
a. 4’
b. 6’
c. 8’
d. 10’
b. 6’
[IRC E4203.1.1]
Not connected to ground or to a conductive body that extends the ground connection.
a. Grounded
b. Ungrounded
c. Ground
d. Bonded
b. Ungrounded
[IRC E3501 ELECTRICAL DEFINITIONS]
A point on the wiring system at which current is taken to supply utilization equipment.
a. Breaker
b. Outlet
c. Branch Circuit
d. Lighting Outlet
b. Outlet
[IRC E3501 ELECTRICAL DEFINITIONS]
The overhead service conductors between the utility electric supply system & the service point.
a. Service entrance conductor
b. Service cable
c. Service drop
d. Service equipment
c. Service drop
[IRC E3501 ELECTRICAL DEFINITIONS]
A service conductor’s overhead clearances must be?
a. 10’ minimum above walking surface
b. 12’ above residential property & driveways
c. 18’ above public streets, alleys or parking areas.
d. ALL OF THE ABOVE
d. ALL OF THE ABOVE
[IRC E3604.2.2 (1)(2)(3)]
An open service conductor without an overall outer jack SHALL have a minimum clearance of _____ from the sides of doors, porches & operable windows.
a. 3’
b. 4’
c. 6’
d. 8’
a. 3’
[IRC E3604.1 (Fig. E3604.1)]
A temporary service pole is installed in the earth usually to a depth of a least_____.
a. 2’
b. 3’
c. 4’
d. 5’
b. 3’
[or more as required by Authority Having Jurisdiction (AHJ)]
A minimum of 2 ______ amp rated branch circuits shall be provided to serve receptacles located in the kitchen, pantry, breakfast area & dining room.
a. 15 amp
b. 20 amp
c. 30 amp
d. 40 amp
b. 20 amp
[IRC E3703.2]
All branch circuits that supply 125V, single-phase, 15 & 20 amp outlets installed in the dwelling unit ______ SHALL be protected by an ARC-fault circuit interrupter.
a. Bathrooms
b. Bedrooms
c. Kitchens
d. Garages
b. Bedrooms
[IRC E3902.12]
Each ______ requires an individual terminal.
a. Ground
b. Neutral
c. Subwire
d. Breaker
b. Neutral
[IRC E3706.4]
Unless installed parallel to framing members NM (non-metallic, sheathed cable/ROMEX) wiring run in an attic accessed by a portable ladder, SHALL be protected from damage where located within _____ of the nearest edge of the attic entrance.
a. 6’
b. 7’
c. 8’
d. 10’
a. 6’
[IRC E3802.2.1]
Type NM (non-metallic, sheathed cable/ROMEX) wiring shall be supported a maximum of _____ on center.
a. 3’
b. 4.5’
c. 6’
d. 12’
b. 4.5’
[IRC Table: E3802.1]
Insulated grounded conductors of sizes #6 AWG & smaller may be identified by all EXCEPT which one of the following methods?
a. Continuous WHITE outer finish
b. Continuous BLACK outer finish
c. 3 continuous WHITE STRIPES (on other than green insulation)
d. Continuous natural GRAY outer finish
b. Continuous BLACK outer finish
[IRC E3407.1]