TMA01 Flashcards

1
Q

Specific regulations regarding electrical installations are covered by?

A

BS 7671 - covers domestic electrical installs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What part of the Building Regulations makes specific reference to a person’s competence to carry out electrical installation work?

A

Part P

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When bonding to pipework, what does the label state?

A

“Safety Electrical Connection, Do Not Remove” - all bonding must be identified with green/yellow insulation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

At the court of a gas meter, the bonding clamp for the main bonding conductor should be installed within?

A

600mm - earth clamps must be fitted on the consumers side of the pipework, preferably within 600mm of gas meter if practical but within the Building if external

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Information regarding the minimum conductor size for electrical circuits can be obtained from?

A

BS 7671 - this also requires that a cable termination of any kind should securely anchor all of the strands of the conductor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A branch from a ring final circuit is usually described as a?

A

Spur - when the extension of the RFC is necessary (such as extra socket or lighting circuit) it may be done using a spur

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What current rating is required for a protective device of a 9kW shower?

A

45 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A 3kW immersion heater should be supplied from a protective device in the consumer unit rated at?

A

15 A fuse or 16A circuit breaker in the consumer unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The supply of a 3kW immersion heater should originate from?

A

Consumer unit - immersion heaters must be wired on their own individual circuit consisting of 20 A double-pole switch from fixed wiring which is protected by 15 A fuse or 16 A circuit breaker in the consumer unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which piece of equipment is used to test if an electrical circuit is live?

A

Voltage Tester to GS38

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Main equipotential bonding is a method of connecting what to the consumer’s main Earthing terminal?

A

Extraneous conductive parts - requirement of BS 7671 that all ECPs are bonded together and are connected to the main Earthing terminal that is enclosed within or close to the consumer unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The correct size for main bonding conductor for a TN-S system having 25mm^2 phase and neutral supply conductors is?

A

10mm^2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the correct size of fuse to be fitted in the consumer unit of a fused spur supplying a 1kW lighting circuit?

A

5 A - all fuses should be replaced with one rated at 5 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The colour coding of wiring in a modern 3-core flex is made up of?

A

Brown, blue and yellow/green - sheath is also grey

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A ring final circuit should be supplied from a protective device rated at?

A

30 A or 32 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When installing a surface-mounted cable in a domestic premises, the best installation method is?

A

PVC mini-trunking

17
Q

A 3kW immersion heater must be provided with a?

A

20 A double-pole switch

18
Q

When working on any existing electrical system, the first test to be carried out should be?

A

Voltage test - this must be carried out before starting any work on a circuit to reduce risk of electric shock

19
Q

What test identifies short circuits?

A

Insulation resistance - IR provides indication of wrong connection, Short-circuits and earth faults

20
Q

The reason a 7kW instantaneous shower is protected by a 32 A mini circuit breaker is the unit’s?

A

Current rating - high current rating requires a 32 A MCB