the two main to control in Refrigration? Flashcards

temprature and pressure

1
Q

condensing unit on R-22

A

30 delta T

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

condensing unit on R-410

A

10 to 15 delta T

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

low super heat

A

overcharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

high super heat

A

undercharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

normal subcooling

A

10-15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Relative himudity measured with

A

dry valve and wet valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

75va and 24 volts

A

75va divided to 24volts 3.125 amp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

3 ton of cooling 1200

A

1200 divid to 13.33=90.02lb/mn times60minunit/hr =5400lb/hr times24 hr/day=129,600 lbs/day

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

what are the three traders

A

mechanical, electrical, sheet metal dutc work

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

the design charging refrigeration is

A

95 ambient temprature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

for medium temp-refrigerator what is first to check for low charge.

A

we have to check subcooling before super heat.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Normal super heat is?

A

8-12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

if your sub cooling is normal but high super heat what is the reason?

A

bad TXV or plug line happening.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

for high amp draw voltage what you have to check?

A

plugged up condenser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

sub cooling temp meter clamp on?

A

liquid line

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

super heat temp meter clamp on?

A

suction line

17
Q

for confort what is the delta T

A

75f 40 poling point. 55f exite 75-55=20 DT

18
Q

two load condensing unit connected in

A

parallel

19
Q

what is the reason insulateing suction line?

A

to prevent from heat gaining and condensing from surrounding ambient temprature.

20
Q

defrost is always happen by

A

temperature and time

21
Q

for comercial service valve back seated? mid seated? front seated?

A

open, vacuum, close

22
Q

temperature of 95f and an inside temperature 80f with 50 humidity is ?

A

the rating establish by air conditioning

23
Q

the AHRI directory is rated under the same conditions?

A

80f db 50% humidity indoor and 95f db out door.

24
Q

what are two fixed bore metering device?

A

capillary tube and orifice (piston)

25
Q

Pumping down a refrigeration system to 5-10 pressures on the liquid line is done primarily

A

to prevent liquid refrigerant from entering the compressor during off-cycles

26
Q

restricted airflow

A

Amperage goes down

27
Q

too much air flow

A

amperage go up

28
Q

three pressures are present in the duct system are

A

total= static plus velocity

29
Q

the weakness of every force-air system.

A

Hot air rises and cold air falls