TEST PREP Flashcards
- CAVITATION CAN DESTROY A CENTRIFUGAL PUMP, IS NOISY AND IS CAUSED BY:
INLET PRESSURE THAT IS TOO LOW.
Inlet pressure that falls below the manufacturer’s recommended Net Positive Suction Head (NPSH) will cause water to boil due to the low pressure, causing bubbles and cavitation.
- A VACUUM BREAKER IS INSTALLED BETWEEN EQUIPMENT AND A STEAM TRAP TO:
ALLOW CONDENSATE TO DRAIN AFTER THE STEAM HAS BEEN SHUT OFF.
Once steam supply has been shut off, steam will condense and will be unable to drain because of the vacuum. The vacuum breaker provides a vent and allows the condensate to drain.
- TWO TYPES OF THERMAL OVERLOAD RELAYS IN COMMON USE TODAY ARE:
THE BIMETAL RELAY AND THE MELTING ALLOY RELAY.
- THE EFFICIENCY OF AN ELECTRIC FURNACE IS USUALLY:
100 %
- DEFECTIVE RIGGING COMPONENTS AND HARDWARE SHOULD BE:
DESTROYED
Inspection for damage of sling and all fastenings and attachments should be made PRIOR TO EACH SHIFT.
- IN ORDER TO REDUCE PRESSURE TO AN ACETYLENE PRESSURE REGULATOR, THE ADJUSTING SCREW IS TURNED:
COUNTER-CLOCKWISE UNTIL THE TENSION IS OFF.
Pressure adjusting screw. The regulator adjusting screw controls the flow of gas and delivery pressure to the hose and torch.
Soldering & Brazing
Ch. 6 Pg. 90
- SUCTION GAS TEMPERATURE LEAVING EVAPORATOR MINUS SATURATED SUCTION TEMPERATURE EQUALS:
SUPERHEAT
HVACR Training Manual
Unit 3.11 Page 39
- WHICH OF THE FOLLOWING GASES MUST NEVER BE USED TO PRESSURIZE OR LEAK TEST A REFRIGERATION SYSTEM:
OXYGEN
Precautions:
- Nitrogen must be oil-pumped dry nitrogen.
- Although (CO2) Carbon Dioxide could be used, NEVER use just oxygen or just acetylene.
- When using high-pressure gas such as n nitrogen or carbon-dioxide in cylinders, always use a pressure regulator and a relief valve.
- FOR ELECTRIC HEAT FURNACE WHAT SIZE SHOULD THE FLUE PIPE BE:
NO FLUE IS REQUIRED
- A REFRIGERANT HEAT EXCHANGER MIGHT CAUSE:
THE COMPRESSOR TO BE OVERHEATED
Precautions:
- Must be constructed and installed so as to not trap oil.
- The amount of superheating should be limited, as excessive superheating of suction gas will cause excessive discharge temperature and overheat the compressor.
- THE PURPOSE OF A SUCTION LINE ACCUMULATOR IS TO:
TRAP LIQUID REFRIGERANT
Installed in the suction line between the evaporator and the compressor. Basically a tank; a slug of liquid refrigerant and/or oil leaving the evaporator will be trapped in the accumulator.
- THE PROPER LOCATION FOR AN OIL SEPARATOR IS NEAR THE:
COMPRESSOR
An oil separator is a tank-like device which removes oil from the refrigerant and automatically returns the oil to the compressor.
- THE TWO PLANES OF ALIGNMENT THAT MUST BE CONSIDERED WHEN ALIGNED A FLEXIBLE COUPLING ARE:
PARALLEL AND ANGULAR
Shafts must be aligned so that the centerlines meet each other exactly in the center (parallel to one another, or axially) and they must be aligned so that they have no angular difference between them (also called radical alignment).
- HOW CAN YOU IDENTIFY REVERSE OPERATION WITH A SCROLL COMPRESSOR?
BOTH:
. THE COMPRESSOR WILL NOT COMPRESS
. THE COMPRESSOR WILL STOP ON MOTOR OVERLOAD
- WHAT SHOULD YOU INSTALL AT THE BOTTOM OF A SUCTION LINE RISER?
A P-TRAP
Getting oil to flow upward in certain vertical piping can be a problem, and a trap at the bottom of the riser can assist in getting the oil to begin the upward flow. Also prevents oil in certain lines from draining back to the compressor during the off-cycle.