Test 3 Flashcards
While the driver of a tandem-axle truck is backing up at a construction site, he or she should:
A. shout while backing up B. wave his or her hands and shout while backing up C. sound the backup warning device while backing up D. sound the horn while backing up
C. sound the backup warning device while backing up
All vehicles with a cargo capacity of 2.5 cubic yards or more are required to have a working automatic backup warning device. A “tandem-axle” truck would most likely be at least that large.
Exterior connectors used on conduit must be:
A. waterproof B. water-resistant C. either water-resistant or waterproof D. galvanized
C. either water-resistant or waterproof
Connectors suitable for outside installations are not all waterproof, and if well sheltered they might not even need to be water-resistant. Connectors are selected based on their UL listing for a specific purpose. Usually, outside connectors should be raintight, but if the installation is below grade or subject to immersion, this is not enough. The water resistance of a connector also depends on proper installation. Plastic or aluminum connectors are not galvanized.
Which of the following substances is now regulated by Title 8?
A. concrete B. asbestos C. plaster board D. electric wire
B. asbestos
The California Code of Regulations is broken up into 28 different Titles. Title 8 covers Industrial Relations and includes the Construction Safety Orders and General Industry Safety Orders, both of which have big sections detailing the many regulations on asbestos in the workplace.
What is the minimum clearance above grade, as specified in the Electrical Code, for a service drop up to 600 volts?
A. 8' B. 10' C. 12' D. 15'
D. 15’
At least 15’ clearance is required for service drops from 300 V to 600 V.
Who schedules the next phase of work after the rough wiring is done?
A. city inspector B. architect C. owner D. prime contractor
D. prime contractor
When installing multiple fire detectors, it is a good practice to wire the detectors:
A. in series B. in parallel C. individually, with batteries D. in series and parallel
B. in parallel
Both series and parallel circuits are used, but the series fire alarm circuits are approved only for coded systems. In residential fire warning equipment, detectors must be wired in parallel as normally open elements that close (short) when activated. This prevents activating the alarm signal if there is a breach (open circuit) in the system wiring. A system integrity monitoring circuit is wired in series with the system wires to provide a trouble signal. Battery detectors are used only in existing construction.
Type MC cable may have what type of conductors?
A. copper B. aluminum C. copper-clad aluminum D. any of the above
D. any of the above
If you are installing several smoke detectors, you would:
A. wire them in series B. wire them in parallel C. use batteries D. use detectors listed for use with the control panel
D. use detectors listed for use with the control panel
All detectors must be listed for use with the panel. Both series and parallel circuits are used, with restrictions on the use of series circuits.
If a fire detection sensor is to be wired to a control panel, it must be approved by:
A. the fire department B. the manufacturer's specifications C. the authority having jurisdiction D. the NEC
C. the authority having jurisdiction
According to NFPA standards, when installing a fire-alarm panel and other devices attached to the panel:
A. all components must be purchased at the same time B. all devices being attached must be UL-approved for the panel C. all devices must be approved by the authority having jurisdiction, or listed for use with the panel D. any device that is equivalent to a listed device may be used
C. all devices must be approved by the authority having jurisdiction, or listed for use with the panel
NFPA = National Fire Protection Association
In fire alarm systems, the wire coming from the alarms must be:
A. mechanically supervised B. electronically supervised C. manually supervised D. unsupervised
B. electronically supervised
Where would you place smoke detectors in a family living unit to meet minimum code requirements?
A. crawl spaces B. kitchen C. every sleeping area and common hallway D. all of the above
C. every sleeping area and common hallway
Smoke detectors are required: (1) outside of each separate sleeping area, (2) in the basement, (3) in an attic, if finished, (4) in a common hallway, and (5) on each additional story if not already covered by (1), (2), (3), and (4). A separate sleeping area is defined as one or more bedrooms that are separated from any other bedrooms by a different type of room (such as a living room). Additional detectors in other locations are “recommended.”
A GFCI is intended to:
A. protect people by de-energizing the circuit when the device's rated sense threshold is exceeded B. disconnect the circuit automatically when a pre-determined over-current is detected C. ensure electrical ground continuity D. ensure the integrity of electrical insulation
A. protect people by de-energizing the circuit when the device’s rated sense threshold is exceeded
A GFCI (Ground-Fault Circuit Interrupter) detects outgoing current that fails to return through the circuit neutral, indicating leakage to ground via any of many possible paths. When a leak is detected, the circuit is interrupted.
If you use an extension ladder to reach a landing on the 2nd floor, how far must the ladder extend above the landing?
A. 12" B. 24" C. 32" D. 36"
D. 36”
The 36” is intended to provide a hand-hold for someone climbing the ladder. This applies to all similar situations, such as using a ladder to access a roof.
Why is a conduit bender the best tool for bending EMT?
A. it produces a perfect bend B. it is easier to pull than a hickey C. it keeps the interior volume of the pipe unchanged D. it is most portable
C. it keeps the interior volume of the pipe unchanged
The Electrical Code requires that bends in either Electrical Metallic Tubing (EMT) or Rigid Metallic Conduit (RMC) be made by a means that does not damage the tubing or effectively reduce its internal diameter. EMT is too thin to bend with a hickey, which would kink the tubing, but a conduit bender makes a smooth bend in either EMT or RMC.
A building has a 120/208 V wiring system and requires a 400-amp service. A 480 V power line is available. What size and type of transformer is needed?
A. 480 V, 400-amp in, 1.73:1 delta-wye with 120 V center taps B. 480 V, 100 amp in, 1:4 delta with neutral leg C. 832Y/480 V, 100-amp in, wye-connected 4:1 step-down D. 480/208 V, 400-amp in, 120 T-tap delta step-down
C. 832Y/480 V, 100-amp in, wye-connected 4:1 step-down
The building has a 3-phase 120/208 volt 4-wire wiring system, also called a “208Y/120.” This is obtained by using a 832Y/480 primary to 208Y/120 secondary 4:1 step-down transformer. When you step down the voltage 4:1, you step up the current 1:4, from 100 amps to 400 amps.
What ohmmeter reading might indicate a good capacitor?
A. a high resistance reading, like an open circuit B. initial high reading followed by a low reading C. initial low reading dropping to a high reading D. you can only test a capacitor with a capacitance meter
C. initial low reading dropping to a high reading
An ohmmeter connected across a good capacitor should jump toward a zero reading, then fall back toward an infinity reading (open circuit) as it charges.
At least two 20-amp circuits must be provided in the kitchen for small appliance receptacles, but one of these circuits may be extended to receptacles in a:
A. bedroom B. family room C. bathroom D. dining room
D. dining room
Bathrooms must have a separate 20-amp circuit. The two or more small-appliance circuits for the kitchen may also supply outlets for refrigeration and pantry areas, breakfast rooms, dining rooms, and similar areas.
What is the maximum distance that outlets must be spaced for kitchen countertops?
A. 12" B. 24" C. 36" D. 48"
D. 48”
No point on a wall may be more than 24” from an outlet. This will be satisfied if the outlets are no more than 48” apart.
What is the maximum rating for a garbage disposal on a 20-amp branch circuit?
A. 50% B. 70% C. 80% D. 90%
A. 50%
What is the maximum length of a power cord for a self-contained spa when it is protected by a GFCI?
A. 5' B. 6' C. 10' D. 15'
D. 15’
As defined in the Electrical Code, a self-contained spa has a built-in power panel. A cord of up to 15 feet may be used only if protected by a GFCI. If liquidtight flexible conduit is used, it is limited to 6 feet.
A transformer that provides a 120/240 V service entrance must be grounded:
A. at the low leg of the primary B. at the high leg of the primary C. anywhere on the secondary D. at the center tap of the secondary
D. at the center tap of the secondary
The center tap is the neutral in this system, also called the grounded circuit conductor. Grounding the center tap minimizes the hot-to-ground voltage to 120 volts. In a typical residential installation, grounding electrodes are installed to establish this connection to earth both at the service-pole-mounted transformer and within 5 feet of the service panel. The first is installed by the electric company and the second by the residential electrician.
Where would a 208Y/120 V service most likely be installed?
A. single family residence B. light industrial building C. heavy industrial building D. special purpose only
B. light industrial building
A grounding electrode system is the last step in contact with the earth. According to the current code, a gas line may not be used as a grounding electrode. If one is present, a metal water pipe MUST be connected as a grounding electrode, but it cannot be used as the only electrode in the system. A copper ground rod, a 10’ section of empty steel pipe, or a connection to steel reinforcing bar in a slab foundation may each be used as additional electrodes. Connections 5 & 6 are part of the equipment grounding system, not the grounding electrode system.
The secondary of a transformer provides 240∆/120 V power in an older factory service drop. Where must this transformer be grounded?
A. at the A-phase terminal B. at any phase terminal C. on the winding that provides the two 120 V legs D. it should not be grounded
C. on the winding that provides the two 120 V legs
This older delta system provides power for three-phase motors and a limited number of lighting and general use circuits. If a phase terminal (a corner of the “delta”) were grounded, this would limit the hot-to-ground to 240 V. But grounding the center tap in the one winding that provides 120 V has the effect of limiting the hazard to 208 V.