Test 3 Flashcards
- Any part of the piping system that extends to fixtures on two or less consecutive floors except a riser, main or stack:
A. Branch.
B. Crotens.
C. Riser.
D. Stack.
A. Branch.
- A distance along a soil waste stack corresponding in general to a story height, but not less than 8 feet, within which the horizontal branches from one floor or story of a structure are connected to the stack:
A. Branch bent.
B. Building pipe.
C. Branch interval.
D. Building drain.
C. Branch interval.
- A vent connecting one or more individual vent with a vent stack or stack:
A. Branch interval.
B. Branch vent.
C. Building branch.
D. Building branch drain.
B. Branch vent.
- That part of the lowest piping of the drainage system that receives the discharge from soil, waste and other drainage pipe inside and that extends 5 feet in developed length of pipe beyond the exterior walls of the building and conveys the drainage to the building sewer:
A. Branch drain.
B. Building drain.
C. Branch interval.
D. Building sewer.
B. Building drain.
- A building drain that conveys both sewage and storm water or other drainage:
A. Combined building drain.
B. Combined sanitary drain.
C. Sanitary street sewer.
D. Combined street sewer.
A. Combined building drain.
- An access opening in the drainage system utilized for the removal of obstructions:
A. Plug
B. Trap.
C. Fixture trap.
D. Clean-out.
D. Clean-out.
- A vent connection at the junction of two fixture drains or to a fixture branch and serving as a vent for both fixtures:
A. Common vent.
B. Unit vent.
C. Dual vent.
D. A, B, & C.
D. A, B, & C.
- A pipe inside the building that conveys storm water from the roof to a storm or combined building drain:
A. Leader.
B. Conductor.
C. Water pipe.
D. Drainage pipe.
B. Conductor.
- The smallest size soil branch permitted is:
- 1-1/2 inch
- 2 inch
- 3 inch
- 4 inch.
- 3 inch
- The plumbing code permits slip joints
A. on the outlet side of the fixture trap
B. on the inlet side of the fixture trap
C. only with expansion joints
D. only on roof terminals over 5’.
A. on the outlet side of the fixture trap
B. on the inlet side of the fixture trap
- Of the following traps. the type that is not permitted to be installed is
A. 1/2-S
B. P
C. 3/4-S
D. running.
C. 3/4-S
- The maximum distance between clean-outs in horizontal drainage lines shall be
A. 25 feet
B. 35 feet.
C. 100 feet.
D. 75 feet.
C. 100 feet.
- When referring to a building drainage system, the term “waste pipe” should normally be applied to
A. piping which drains water closets
B. piping which does not receive human waste
C. any pipe which carries water-borne wastes
D. any pi[e which connects to the building drain.
B. piping which does not receive human waste
- A trap should be vented so that the seal at no time is subjected to a pressure differential of more than
A. 1 inch of water
B. 2 inches of water.
C. .1 pounds per square inch
D. .2 pounds per square inch.
A. 1 inch of water
- The minimum required diameter of any soil stack extension which passes through the roof is
A. 3 inches
B. 4 inches
C. 5 inches
D. 6 inches.
B. 4 inches
- A device used to prevent back flow by siphonic action is called a
A. relief valve
B. sewage ejector
C. foot valve
D. vacuum breaker.
D. vacuum breaker.
- The minimum pressure available at the faucet or water outlet with the water outlet wide open shall be
A. 2 psi
B. 4 psi
C. 6 psi
D. 8 psi.
D. 8 psi.
- Air chambers installed at individual fixtures
A. need not be accessible
B. shall be accessible
C. are required for loads of less than 5 fixture units
D. are required for loads of more than5 fixture units.
B. shall be accessible
- Each fixture trap shall have a liquid seal of at least
A. 2”
B. 2-1/2”
C. 3”
D. 4”.
A. 2”
- Each fixture trap shall have a protecting vent so located that the developed length of the fixture drain from the trap weir to the vent fitting is not more than
A. 6 inches
B. 12 inches
C. 18 inches
D. 48 inches.
D. 48 inches.