TEST Flashcards
What should you take into account if you’re using tiles with deflectors or louvers?
A) Tiles with air deflectors and louvers can be heavy
B) These kinds of tiles will not allow for a flexible cooling solution
C) These kinds of tiles can only be used to cool storage equipment
D) Tiles with air deflectors or louvers will reduce the cooling capacity of the tile
D) Tiles with air deflectors or louvers will reduce the cooling capacity of the tile
A new network storage device in a non-standard sized rack of approximately 600 KG is going to be installed in the data center.
Are new floor loading calculations required?
A) Yes, additional floor loading needs to be done by the floor manager
B) No, as long as the equipment is less than 700 KG
C) Yes, a structural engineer approved and endorsed by the building owner should carry out new floor loading calculations
D) No specifications of equipment is required, the size will already be know
C) Yes, a structural engineer approved and endorsed by the building owner should carry out new floor loading calculations
Smoke sensors need to be tested in order to ensure that they pick up potential fires in the data center.
What would you recommend?
A) Test the sensors according to the vendor’s specification
B) Test the sensor by injecting smoke or simulated smoke directly into the sensor
C) Press the self-test button
D) Inject smoke at the floor level
D) Inject smoke at the floor level
How is PUE calculated?
A) Total Facility Power / Total IT Power
B) Total IT Power / Total Facility Power
C) The UPS Input / The UPS Output
D) Air Conditioning Power / Air Conditioning Output
A) Total Facility Power / Total IT Power
A battery bank is rated with a total capacity of 400 Amp hours.
How much charging current should the rectifier deliver to ensure charging?
A) 8 Amps
B) 40 Amps
C) 60 Amps
D) 80 Amps
B) 40 Amps
The pipes of a VESDA smoke detection system are installed at the air intake of an air conditioning unit inside the computer room. Is this a good practice?
A) Yes, as this reduces the amount of piping needed
B) No, the piping should be installed at the air exhaust of the air conditioner
C) No, it will cause a longer reaction time for smoke detection and there might also be an air bypass for airflow
D) It depends on the type of gas being used
C) No, it will cause a longer reaction time for smoke detection and there might also be an air bypass for airflow
A computer room is very smelly due to paint that was used during construction. In order to reduce the smell in the computer room management has requested you to install an automated aerosol release unit which releases a fresh smell every 15 minutes. Is this ok?
A) Yes
B) No
B) No
Do you need to consider blast protection when designing a data center?
A) No, Blast protection is not a requirement of TIA 9422
B) Yes, Blast protection is a requirement of TIA 9422
C) No there is no sense of implementing it because you can’t predict the impact of a bomb
D) Yes, if your data center is a potential target or your data center is in the vicinity of a potential target.
D) Yes, if your data center is a potential target or your data center is in the vicinity of a potential target.
The humidity in the data center has gone down from 50% to 35% of relative humidity.
What influence would this have on electric static discharge?
A) It has no influence
B) ESD levels would go up
C) ESD levels would go down
D) No influence as long as the temperature stays around 20 degrees Celsius
B) ESD levels would go up
The requirement of a new building code is that only batteries with the highest flame retardant material should be used.
What specifications should you give the battery supplier?
A) Castings compliant to V0
B) Castings compliant to V1
C) Castings compliant to V2
D) Castings compliant to ABS
A) Castings compliant to V0
What is the definition of concurrent maintainability?
Concurrent maintainability requires that each and every capacity component (including elements which are part of the distribution path) can be removed, replaced, or serviced on a planned basis without disrupting the ICT capabilities of the end user.
The air-intake on a mission critical server on the top of a rack measures 25 degrees Celsius.
Is this acceptable?
A) No - the temperature needs to be 20 degrees Celsius
B) As long as it does not exceed the average server room temperature of 38 degrees Celsius it’s ok
C) Yes – this is allowable according to the standards
D) It depends on the TIA 9422 rating level
C) Yes – this is allowable according to the standards
The computer room needs to be fitted with a gas-fire suppression system. The computer room will be a high-density data center with about 30% of the racks being closed-circuit cooling blade servers.
Should the supplier of the fire suppression system be informed of the chosen rack design?
A) No – the cooling and design of racks have no influence on fire suppression
B) Yes – the cooling and design of racks have an influence on fire suppression
C) Only when the rack height obstructs potential fire suppression release points
D) Only when the racks might block access to the fire pattern
B) Yes – the cooling and design of racks have an influence on fire suppression
A data center is located in an area where the demands for power is higher than the power company can supply. This means that there are a lot of power outages and power shedding. The main power is unavailable more than 800 hours a year.
What type of generator would you recommend installing?
A) A stand-by generator in a N+1 configuration
B) A continuous generator installed and no N+1 configuration is needed as the generator will be running all the time
C) A continuous generator installed in a N+1 configuration
D) A combination of stand-by prime and continuous generators
C) A continuous generator installed in a N+1 configuration
What should be taken into account when installing data cabling overhead?
A) Maintain minimum separation between the power and the power cable to ensure that the fire detection and suppression systems are not hindered
B) The copper data cable should not be placed in metal cables
C) The optical fiber cabling should always be positioned on the top of copper cabling in the same cabinet tray
D) All cabling should make sharp bends directly into the rack
A) Maintain minimum separation between the power and the power cable to ensure that the fire detection and suppression systems are not hindered
You are working with a customer that requires a guarantee that there are low THDi levels coming from your UPS, with a maximum of 3% THDi. You have a UPS with a six pulse base rectifier. The current load on the UPS is 10% of its capacity. The customer indicates that they are going to expand within 3 years and they expect to grow and put a load of up to 80% on the UPS. What would you recommend?
A) Nothing – the UPS will be just fine
B) Install an isolation transformer rated at K-13 or K-20
C) Install a passive harmonic filter
D) Install an active harmonic filter
D) Install an active harmonic filter
A data center is in operation for about 1 year and 2 months, the dust levels are relatively high.
What is the most likely root cause of this problem?
A) Low pressure in the data center
B) The cleaning crew is not doing their work
C) Every data center has dust levels which are high
D) The floor tiles are probably not fitted correctly
A) Low pressure in the data center
When designing a data center network, you notice that there’s not a lot of space for cabling in the computer room.
Which possible layout would be your best choice?
A) POP with rack
B) End of row
C) A Star network
D) It doesn’t matter, the cabling outside the rack is not influenced by the network design
A) POP with rack
What is the potential disadvantage of using water misting systems as a fire extinguishing system?
A) It only uses 10% of the water normally used, which might not be enough
B) It extracts oxygen from the air creating a potential risk to humans
C) It will rapidly increase the humidity levels in the data center
D) It has droplets which are too small and can only be used for small fires
C) It will rapidly increase the humidity levels in the data center
The temperature in the computer room is being increased from 18 degrees Celsius to 27 degrees Celsius.
What would be the impact, if any, on the amount of gas required to suppress a fire?
A) The amount of gas would be less
B) The amount of gas would be more
C) The amount of gas would not change
D) The amount of gas cannot be determined without knowing the humidity
A) The amount of gas would be less
What is the requirement for power feeds to a building for a Rated-4 data center based on TIA-942?
A) 2 feeds coming from 2 different substations - 1 power company is NOT acceptable
B) 2 feeds coming from 2 different substations - 1 power company is acceptable
C) 2 feeds coming from 1 substation split over 2 different transformers
D) 1 feed from 1 substation split over 2 separate distribution boards
B) 2 feeds coming from 2 different substations - 1 power company is acceptable
Your data center is 15 years old and you’re asked to improve energy efficiency.
In what sequence would you start to improve the data center?
A) UPS, Generator, CRAC HVAC Units, The raised floor network cabling routing
B) CRAC HVAC Units, The raised floor network cabling routing, UPS, Generator
C) Generator, UPS, The raised floor network cabling routing, CRAC HVAC Units
D) The raised floor network cabling routing, Generator, CRAC HVAC Units, UPS
B) CRAC HVAC Units, The raised floor network cabling routing, UPS, Generator