Temperatures Flashcards
Reconstruction - Base metal temp where welding is not allowed
< 0 degrees F 653: 10.4.2.3
Reconstruction - Base metal temp when hand-warm pre-heat is
required
0 - 32 degrees F 653: 10.4.2.3
Linings - Minimum temp when installing tank bottom linings
5 degrees F above
dew point 652: 8.3
Corrosion – The corrosion rate of steel tank bottoms may
double with this rise in temperature
18 degrees F 651: 5.4.1 Note
UT Calibration - Calibration Block must be within what
temperature of the part to be examined
25 degrees F 577: 9.9.3.1
Vacuum Box - Standard temperature range for VB exam
40 - 125 degrees F 650: 8.6.6
PT - Standard temperature range for a PT exam
40 - 125 degrees F V: T-652/653
Impact Test - Design metal temperature that requires weld
procedure used for vertical welds to be impacted tested
< 50 degrees F 650: 9.2.2.3
Brittle - Tank metal temperature where brittle fracture is
NOT a concern
> 60 degrees F 653: Fig 5.1
Bottom Lap Patches - Metal temp where lap-patches are NOT
allowed in critical zone on SS tank
> 100 degrees F 653: 9.10.1.2.3
Intervals - If tank product solidify below this temperature,
the code maximum interval rules do not apply
< 110 degrees F 653: 6.4.2.1.2.1
Preheat - Approximate temp of a required hand-warm pre-heat
140 degrees F 653: 10.4.2.3
Corrosion - Temperature when high strength caustic causes
serious corrosion in CS and 300 SS
> 150 degrees F 571: 4.3.10.6c
575: 8.4.3
Preheat - Required pre-heat temperature for shell welds over
1.5” thick during Reconstruction
200 degrees F 653: 10.4.4.3
Bottom Lap Patches - Metal temperature where lap-patches
are NOT allowed in the critical zone on CS tanks
> 200 degrees F 653: 9.10.1.2.3