What is the LCO and Applicability of Technical Specification 3.4.4, Safety/Relief Valves (S/RVs)?
LCO 3.4.4: The safety function of seven S/RVs shall be OPERABLE,
AND
The relief function of six additional S/RVs shall be OPERABLE.
APPLICABILITY: MODES 1, 2, and 3.
What are the one hour or less actions associated with Technical Specification 3.4.4, Safety/Relief Valves (S/RVs)?
NONE
What is the LCO and APPLICABILITY of Tech Spec 3.6.1.3, Primary Containment Isolation Valves (PCIVs)?
LCO 3.6.1.3: Each PCIV, except containment vacuum breakers, shall be OPERABLE.
APPLICABILITY: MODES 1, 2, and 3,
When associated instrumentation is required to be OPERABLE
Per LCO 3.3.6.1, “Primary Containment and Drywell Isolation Instrumentation.”