For electromagnetic field testing, additional detailed spot measurements should be taken directly at floor level
and at _______ above the floor at grid point locations directly on the wall surface separating measured area from
suspected magnetic field source
two meters
Which of the following ground fault detection methods involves sensing current in only one conductor?
Direct method
Before performing ground fault test on a 480V main switchboard you measure less than 1 megohm between the
neutral and ground bus. Which of the following statements is true?
The reading is low and should be improved before testing the ground fault protection.
According to ANSI/NETA MTS, how often should ground systems be electrically tested assuming a multiplier of
1.0?
Once every two years
A new 35kV Step Voltage Regulator is being acceptance tested, which test would be optional for an insulating
liquid analysis on fluid sampled from the main tank in accordance with NETA standards?
Power factor
A(n) ____ disconnecting means is required within sight of the storage battery for all ungrounded stationary
battery system conductors operating at over 60VDC
Readily accessible
What is the minimum acceptable dielectric breakdown value for service-aged FR3 insulating liquid tested in
accordance with ASTM D1816 using a 2mm gap?
34kV
What is a newer SCADA system that doesn’t require cables?
PLCC
What is the Restricted Approach Boundary for a 69kV system?
3 ft 6 in
IEEE standards recommend that batteries should undergo additional performance tests periodically. It is
recommended that the performance test interval should not be greater than ____ % of the expected service life.
25
In an RC parallel circuit, the current through the resistor and the current through the capacitor are
less than 90° out of phase with the resistor current lagging
One advantage DC type motors have over AC types is that:
their speed can be easily varied
Which of the following is not considered a fiber optic connector?
8P8C
Aluminum lightning protection materials may be installed on or in contact with copper surfaces only when
corrosion protection and bimetallic listed connectors are used
False
F6 pressure within switchgear will generally vary from ____ psig, due to changes in ambient temperature
3 to 10
A current transformer with a current ratio of 60/1 is used with a current of 150 amperes. If an instrument with a
total impedance of 4 ohms is connected to the secondary of the transformer, the secondary voltage is?
10 volts
New installation of 350 MCM copper 15kV tape shielded 100% EPR insulated power cable requires inline splice.
To properly perform a splice on this cable which is not required:
Some type of conductors are required to cross splice and connect the shield on both sides
What is the expected Maximum Trip Time (in Seconds) for a 600V, 2500A molded-case circuit breaker inverse
time test at 300% of Rated Continuous Current?
850
Which of the following maintenance tests is required for a 13200-480Y/277V 2500kVA dry-type transformer?
excitation-current test on each phase
Which of the following could cause ground faults in standby battery banks
Any of these
A newly installed 3-phase 4160V 200HP emergency generator was insulation resistance tested at 500VDC for one
minute. The calculated DAR value was found to be 1.5, is this value acceptable?
No, this generator should be tested at 1kVDC.
What is the cause of continuous increase in resistance during an insulation resistance test?
Capacitance
Temperature corrected winding-resistance acceptance testing values for large air-cooled transformers should
compare within ____ percent of previously obtained results.
1
What is the approximate expected interfacial tension of new insulating fluid?
40 Dynes/cm