If the FSII level in bulk storage drops below _____% by volume, the air station commanding officer must be notified.
0.07
________ and _______ are responsible for ascertaining the correct fuel required for individual aircraft and for assuring that the aircraft is serviced with the correct fuel.
Pilots, aircrew
CGTO PG-85-00-170-A
AVIATION FUEL HANDLING PROCEDURES PROCESS GUIDE
Fire or explosion hazards are always present in locations where fuels are handled. Safe fuel service depends on keeping fuels in controlled areas, avoiding spills, and keeping all ignition sources ___ ft away from designated servicing areas and tank farms
50
The primary difference between the grades of turbine fuels is the _________.
volatility
No other grades of fuel can be routinely used by Coast Guard aircraft without prior approval from __________.
Commandant (CG-41)
All three military fuels contain the following additives not normally contained in commercial fuel:
a. Fuel System Icing Inhibitor (FSII)
b. Lubricity Additive (corrosion inhibitor)
c. Antioxidants (storage stability additives)
d. Static Dissipater Additive (SDA) (JP-4 and JP-8 only)
TYPES OF CONTAMINATION
- Particulates
- Water
- Microbes
- Surfactants
- Miscellaneous Contaminants
__________ materials must not be used in aircraft fuel service.
Galvanized
WARNING:
DO NOT START FILLING OPERATIONS WHEN A LIGHTNING ADVISORY HAS BEEN ISSUED, INDICATING AN ELECTRICAL STORM IS WITHIN __ NAUTICAL MILES OF THE TRUCK FILL POINT.
5
Fueling pressure at the fuel nozzle shall not exceed the maximum allowable pressure listed in the applicable aircraft flight manual. Listed for reference:
- MH-65 55 PSIG
- MH-60 55 PSIG
- HU-25 50 PSIG
- HC-130 60 PSIG
- HC-144 50 PSIG
Fuel flow should be stopped within a maximum __% overrun.
5
There are three types of fuel samples taken at a Coast Guard air station
a. Clear and bright samples
b. FWD, CFD, and FSII test samples
c. Lab samples
The particulate contamination level for fuel being dispensed to aircraft is ___ mg/l at the fuel dispensing nozzle as determined by the AEL MK III tester.
1.0
The limit of water contamination in turbine fuels is ___ ppm.
10