study guide, notes Flashcards
why is a closed Y closed delta bank primary neutral floated?
to prevent balance or bank action - to prevent burning out the two remaining transformers when on fuse blows and creates an open, the bank continues to provide 3 phase power using two transformers instead of 3. Also to prevent back-feeding the line when a line becomes de-energized, or to prevent backfeeding the hi side of the transformer if the fuse becomes blown.
why is a forth cutout installed on the primary neutral of a closed wye closed delta bank?
to prevent ferroresonance - when you lose your 3rd potential, your reactance and capacitance in the bank can build up to 10X the normal voltage, closing the 4th cutout (connecting the primary neutral bus to the system neutral or ground) will balance the voltage on the neutral bus preventing ferroresonance.
on an open bank what KVA capacity do you have of the two transformers being used?
86.6%
what must be done before climbing above a de-energized transformer?
isolate the secondary leads or ground with approved equipment.
what do you need to do on a closed wye closd wye transformer bank?
tie the primary and secondary neutral bus to prevent high secondary voltages.
what purpose does the case ground serve on a transformer?
to ground the case of the transformer and acts as your neutral on a single bushing transformer
how do you find full load current?
KVA divided by primary or secondary voltage used. On primary use the voltage the transformer is using. On secondary use larger voltage supplied, if paralleled use paralleled voltage.
how do you size two transformers to carry 3 phase balanced load?
multiply the 3 phase load by 57%. This would be the load on each transformer. The single phase load is added only to the “lighter transformer”
how to fuse wye connected primary
KVA divided by primary voltage used, multiplied by design factor of 2 (utility spec will vary) round to nearest fuse size
how to fuse closed delta connected primary
KVA divided by primary voltage used multiplied by 1.73, multiplied by design factor of 2 (utility spec will vary) round to nearest fuse size.
how to fuse open delta primary
cutout with 2 bushings attached: KVA divided by primary voltage used multiplied by 1.73, multiplied by designed factor of 2 (utility spec will vary) round to nearest fuse size.
cutout with 1 bushing attached: KVA divided by primary voltage used, multiplied by designed factor of 2 (utility spec will vary) round to nearest fuse size
transformer core; how does it work, what is made of
the core is the part of the transformer in which the magnetic field oscillates. it consists of laminated steel, insulated, and wound to a desired shape for the coils. the purpose of this thin sheet is to reduce the core loss and the heating produced in the core by insulating each sheet from the other.
coils; what do they consist of, size
the coils consist of an insulated wire or bus bar wound around a wooden block to fit the core; the fewer the turns, the larger the wire. the insulation on the wire depends upon the voltage to be supplied to the coils. the two coils are referred to as an input and output coil. There is no electrical connection between the primary and secondary coil in a distribution transformer.
how to get turns ratio of a transformer
primary voltage used divided by highest secondary voltage used. if paralleled use paralleled voltage
describe transformer tank
the tank is used as a means for enclosing the assembled core and coils. it acts as a protective barrier for the high voltage and current carrying parts, and holds the coolant or transformer oil.
transformer bushings; what are they used for, what are they made of?
used to bring the high and low voltage leads from the coils to the outer edge of the tank. the bushings are made of a strong wet-process porcelain which insulates the line leads form the tank.
what are the 3 main parts of a CSP transformer?
circuit breaker on secondary side; external tank mounted lightning arrestor; internal high voltage fuse mounted in the primary bushing
what are the two basic types of lightning arresters?
expulsion and valve
what are the two main enemies of transformers?
high voltage surges and heating caused by overloading
on a CSP transformer what coil is the circuit breaker on?
secondary
transformer taps are used for what two purposes
to correct low primary voltage and to control voltage to a customer ( raise and lower voltage)
standard taps for transformers are what?
5 taps total, middle tap 100%, then 4 - 2.5% taps, 2 - above 100%, 2 - below 100%
when changing taps on a transformer, which coil are you affecting? primary or secondary?
primary
what happens to the primary coil when changing the taps?
increasing the tap adds to the number of turns of the primary coil; therefore, lowering the secondary voltage and lowering the taps reduces the number of turns of the primary coil raising the secondary voltage.
when determining what tap to select on a transformer tap changer, what formula can be used?
actual voltage divided by desired voltage
what determines the amount of voltage drop when a transformer is fully loaded?
impedance
impedance must be how close when paralleling or banking transformers?
plus or minus 10%
how much capacity would you gain from using a closed delta bank instead of an open delta bank?
42.3%; 100% minus 57.7%
open wye - open delta or open delta - open delta bank KVA ratings Rules of thumb.
- 6% of the two transformers
57. 7% of the initial three (if going form closed to open)
how to size the transformers on a open wye - open delta or open delta - open delta bank
multiply the 3 phase load by 57%, this is the load on each transformer. the single phase load is added only to the lighter transformer.
in closed wye - closed delta or closed delta - closed delta banks how is the load split between the transformers
the lighter pot carries two-thirds of the single phase load and each power pot carries one-third of the single phase load the 3 phase load splits one-third on each transformer
conditions exist on a wye-delta closed bank if the primary neutral bus is tie to the system neutral and one or two primary fuses are blown?
if a primary fuse is blown:
- the bank capacity is reduced to 57% of bank rating, possibly causing overloaded and transformer failure.
- also, the voltage measured on the neutral bus is on half the phase to ground voltage or when two primary fuses are blown, voltage on the neutral bus is at full phase to ground voltage (these two conditions also exits every time a closed wye-delta bank is energized or de-energized)
in open banks can CSP transformers be used
yes if future plans do not call for the closing of the delta
in wye-delta and delta-delta closed banks can CSP transformers be used
yes; only on 240 volt and 480 volt 3 phase 3 wire only. if used on for wire systems and the secondary breaker of the CSP opens it would act as an open neutral causing high secondary voltages.
in wye-wye closed banks can CSP and single bushing transformers be used?
yes
in delta-wye closed banks can CSP and single bushing transformers be used?
only two bushing transformers can be used, 2 bushing CSP transformers can be used
what are the five types of stranded conductor shapes?
concentric round, round, compact round, compact sector, annular, segmental
how are rubber gloves rated; phase to phase or phase to ground?
phase to phase
what type of hard hat is worn by electrical workers? how many volts are they tested to?
class E, 20,000 volts
what is the minimum size of protective grounds?
equipment must be capable of conducting the maximum fault current that could flow, for the time necessary to clear the fault, grounds must have ampacity greater than or equal to that of no. 2 awg
what 5 steps are taken for proper grounding?
need a low-resistance path to earth, clean connections, tight connections, connections made at proper points, adequate current carrying capacity or grounding equipment
what sizes do capacitors come in?
15, 25, 50, 150 and 200 KVA with the 100, 150 and 200 sizes most common
what is the proper procedure for pole top rescue?
call loudly to the injured employee call for help evaluate the situation plan the rescue climb to the proper rescue position asses the casualties condition rig the rescue rope or handline lower victim to the ground administer first aid/cpr
formula for peak value
1.414 x RMS
formula for RMS value
.707 x peak
RMS is also known as what?
effective voltage
what are the six types of substations?
step-up transmission step-down transmission distribution industrial customer owned converter
what is a permanent fault?
where the circuit cannot be automatically reclosed, a line crew is needed to repair and re-energize the circuit
what is line loss? and formula
the amount of voltage lost by pushing current through resistance. I2XR
what are harmonics?
AC and voltage disturbances that can be represented by sine waves, but are at different frequencies of the fundamental 60 hertz sine wave: 30, 120 - 2nd harmonic, 180 - 3rd harmonics
how much more load can a wye system handle over a delta system?
73% more
a fire extinguisher used in an electrical environment must have what rating?
must be a C rated in combination with another rating
what is the purpose of transpositions?
to cancel out induced voltages and reduce electromagnetic fields that interfere with open wire telephone circuits
what type of transformer is used on series street lighting? why?
a constant current transformer, it is used to raise and lower the voltage automatically, depending on the number or street lights in the circuit. a constant current has to be maintained because if one lamp burns out the total resistance of the circuit becomes smaller and current would tend to increase.
what are the two basic distribution voltage regulators
induction and step
an induction voltage regulator is connected how with the load?
series
induction regulators as a rule have two series coils, by operating the coils in series how will they be rated? when the coils are paralleled?
+-10%, when in series, +- 5% when in parallel but carry twice the amperage
the step voltage regulator is basically what?
an auto transformer
the step voltage regulator is connected how with the line?
series
can the step voltage regulator coils be paralleled?
no
what do the load bonus settings do on a voltage regulator?
they are mechanical stops on the position indicator dial. allows the regulator to handle larger amounts of current, used when the voltage regulator becomes overloaded.
is external fuse protection required for voltage regulation
no, a regulator can be connected and disconnected form the power lines using a regulator by-pass switch
what must be done before the by-pass switch is operated on a regulator?
the voltage regulator indicator must be in the neutral position
should surge arrestors be installed on voltage regulators?
yes on the source and load side
T/F, two cutouts and arresters are needed on a wye connected transformer
false
T/F, series can happen when you contact two current carrying sources at the same time
false - second point of contact
T/F, if you have high primary voltage on a transformer your secondary voltage will be low
false
T/F, name plates are only needed if you don’t know your phase to phase voltage
false
T/F, low voltage rubber gloves are needed if you are checking voltage on a new transformer
false
T/F, a 250 KVA transformer would have a additive polarity
false, below 200 KVA or 8660 volts is additive all others are subtractive
T/F you can connect the H2 bushing on a single bushing transformer only to the neutral
false, case ground and secondary neutral tie strap is considered the neutral and should be tied down.
T/F, a transformer can usually only be connected to one circuit voltage on the primary side
true
T/F, a delta connection will allow you to balance the system voltage better than a wye connection
false
T/F, the unlike bushings are connected together to make a wye connection
false
T/F, you must always use the same phase and bushing when paralleling transformers
false, same phase not same bushing
T/F, a transformer whose primary voltage rating is 4160/7200 volts can be used on a 7200/12470 system
false
T/F, a transformer whose secondary voltage rating is 277/480 has two secondary bushings
true
T/F, a 250 KVA transformer whose secondary voltage rating is 120/240 volt has three secondary bushings
false, transformers 100KVA and over have 4 secondary bushings
what are the two basic function of oil in a transformer?
cooling and insulation
underground loop fed transformers are connected through
a buss bar
how many phases of a feeder must be present to connect the open delta-delta bank?
must have 3 phases
what are the three most important things that should be considered from the nameplate of a transformer before installing it in a transformer bank
impedance, polarity, voltage
how are the internal secondary leads connected in parallel on a conventional transformer?
AC-BD, alley cat-bad dog, head to head-tail to tail
in common distribution transformers the tap changer is located in which coil?
primary coil
what is the main advantage of a wye secondary over a delta secondary?
efficiency - because the load is balanced
two 50 KVA transformers are connected open-delta/open-delta. what is the capacity of the bank?
50 KVA x 2= 100 KVA, X 86.6%, 100 x .866=
86.6 KVA
what types of transformers are used for primary metering?
current and potential
transformers are additive polarity if their KVA rating is less than?
200 KVA
transformer tap changers are located where?
located in the oil on the primary coil and the control handle is located above the oil
how are lightning arrestors connected?
in series with a resistor
what 3 advantages does bundling conductors have?
cuts down on corona loss, lower line loss, 50% of the reactance of a single conductor
define corona
an electrical discharge at the surface of a conductor accompanied by the ionization of the surrounding atmosphere. it can be accompanied by light and audible noise.
when banking transformers, what’s a rule of thumb for the max safe rating for the bank?
three times the KVA of the smallest can
what is the element in apparant power that does not do any work?
KVAR
1 watt equals?
one amp flowing under pressure of 1 volt
how many watts equal on horsepower?
746 watts
define impedance
total opposition to flow of current in AC circuit, measured on ohms
define inductance
ability to induce a magnetic field on a conductor measured in Henery’s
what type of transformer is used for series street lighting?
constant current transformer
3 types of faults?
open circuit, short circuit, grounded fault
what’s the most common reason transmission line failure?
insulation flashover
vector is what?
line having definite length and direction
how is a current transformer connected?
series
how is a potential transformer connected?
parallel
define circular mil
a circle with a diameter of one one-thousandth of an inch
volts and amps are ________ proportional
inversly
what percent of electrical contractors worked in the electrical field beforehand?
83%
3 main causes of accidents
human element, acts of nature, mechanical failure
natural enemy of rubber gloves
oil and grease
how often are hot sticks tested?
every 2 years
what would you use to cover a primary insulator?
rubber hood
max exposure for rubber goods is?
36KV
an enclosed space at 5 feet requires what?
mechanical retrieval device, (tripod)
oxygen level in an enclosed space: max, normal, minimum
- 5 max
- 8 normal
- 5 minimum
what’s the greatest risk of bloodbourne pathogen?
hepatitis B
minimum overlap distance of an extension ladder is
3 feet
what’s the safe distance from machinery for swing radius
6 feet
what is found in PVC that can cause cancer
carcinogens
how many IBEW vice presidential districts
11