Does generator spec require ASME stamp for anything?
Yes. H2 coolers
Where did I get the detailed vibration criteria?
USEPR spec.
Why did I accept some deviations to the spec requirements for core vibration and end-winding vibration?
A. Because they meet the overall criteria
B. The specified values are not governed by standards
C. We don’t normally have any stated limit
Arabelle proposed gen voltage
24 kV
Arabelle proposed exciter type
Brushless
Arabelle excitation system ceiling voltage
150%
Arabelle piping design and fabrication code
ASME B31.1 or EN equivalent
for European regulations
WEC DID requirement for STG load rejection.
Load rejection from 100 percent power with the turbine generator
continuing stable operation while supplying the plant auxiliary loads
Is the Gigatop core spring-mounted.
No. Keybars only.
Is the Doosan core spring-mounted?
Yes, Spring-bars. Looks like a TFLQQ machine.
Doosan exciter type
Static
Did I specify any transient stability studies or similar?
No. Just the PSS setting.
Ara include field flashing?
Yes
What pf did we specify?
0.85