Steam Generating/SGWLC/Blowdown Flashcards

1
Q

What do the J tubes help to prevent?

A
  • Maintain ring full to minimize water Hammer when AFW initiates
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is P-14 permissive?

A
  • SG Hi HI Lvl at 67% on 1 SG (2/3)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will P-14 permissive cause?

A
  • Turbine Trip
  • MFP Trip
  • FWI
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What enables AMSAC?

A
  • > 40% Power (C-20, 2/2 Turbine first stage Impulse #)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What causes an AMSAC signal?

A
  • FW flow < 25% (3/4 Feed flow)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What will AMSAC actuate?

A
  • All 3 AFW Pumps

- Trips Main Turbine (30 Sec)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Control air header pressure is lowering at a fast rate. At 80 psi, the reactor is manually tripped, and header pressure continues to lower. What will happen to the air reg valves in the BD system if pressure continues to lower?

A
  • All air reg valves on BD system will isolate on loss of ctrl air
  • DRV-350/352
  • BD isolation valves
  • BD Flow Ctrl Valves
  • BD Sample Valves
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does SGWLC maintain?

A
  • SGWLC maintains SG Narrow Range level at 43.8% for all power levels.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the dominant control for SG Level? ***

A
  • Level Dominant (43.8%)

- Steam Generator Level overrides Feed flow/Steam Flow mismatch over time, level is a lag signal*

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What causes a Steam Line Isolation (SLI)? ***

A
  • Cnt # High-High at 2.8# (2/4)
  • SG # low < 500# (1/1 on 2/4 SG)
  • High Stm flow with P-12 (1.42E6/1.6E6) (1/2) on 2 SG
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the definition of density compensation?

A
  • converts volumetric flow rate of steam to mass flow rate for input into SGWLC circuit. (Left 2 Channels ctrl SG lvl)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where do we measure SG Level?

A
  • SG Downcomer
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is swell caused by? ***

A
  • an increase in steam flow (which will cause an increased indication of SG lvl in the downcomer due to decreased SG #) (More intense boiling)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is shrink caused by?

A
  • reduction in steam flow (which will cause an decreased indication of SG lvl in the downcomer due to a rise in SG#) (Less intense boiling)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If the steam flow indication fails high to your flow controller, what will happen the FRV?

A
  • The FRV will go open because Feed Flow will want to match Steam Flow
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If the steam flow indication fails low to your flow controller, what will happen the FRV?

A
  • The FRV will go closed because Feed Flow will want to match Steam Flow
17
Q

If the feed flow indication fails low to your flow controller, what will happen the FRV?

A
  • The FRV will go open because Feed Flow will want to match Steam Flow
18
Q

If the feed flow indication fails high to your flow controller, what will happen the FRV?

A
  • The FRV will go closed because Feed Flow will want to match Steam Flow
19
Q

Unit 1 was operating at 100% power when a loss of main feedwater occurs to a single SG due to the failure of the controlling feedwater flow instrument.

A valid indication on the affected SG “Flows / Level / Pressure” recorder for this failure would be a rapidly lowering SG level and a?

A
  • high feedwater flow indication on the feedwater flow pen.
20
Q

What will cause a FWI?

A
  • SG High-High level (P-14) (67% NR 2/3 on 1 SG)
  • SI
  • Rx trip (P-4) with low Tavg (Tavg < 554°F on 2/4 loops)
21
Q

What is the reactor trip associated with SG Lvl Low

A

15% (U1) 26% (U2) 1/2 channels on 1/4 SGs w/ SF/FF Mismatch 0.71M (U1) 1.47M (U2) 1/2 channels on the same SG

22
Q

What happens on a SG Lvl Low-Low

A

5% (U1) 22% (U2) 2/3 channels on 1/4 SGs

  • Rx Trip
  • Auto start of MDAFP (1 SG)
  • Auto start of TDAFP (2 SGs)
23
Q

What are the SG Pressure and Temperature TRM limits

A

Primary and secondary temps in a SG must be greater than 70 deg when the pressure of either primary or secondary is greater than 200# to prevent brittle fracture (restore in 30 mins)