Steam Generating/SGWLC/Blowdown Flashcards
What do the J tubes help to prevent?
- Maintain ring full to minimize water Hammer when AFW initiates
What is P-14 permissive?
- SG Hi HI Lvl at 67% on 1 SG (2/3)
What will P-14 permissive cause?
- Turbine Trip
- MFP Trip
- FWI
What enables AMSAC?
- > 40% Power (C-20, 2/2 Turbine first stage Impulse #)
What causes an AMSAC signal?
- FW flow < 25% (3/4 Feed flow)
What will AMSAC actuate?
- All 3 AFW Pumps
- Trips Main Turbine (30 Sec)
Control air header pressure is lowering at a fast rate. At 80 psi, the reactor is manually tripped, and header pressure continues to lower. What will happen to the air reg valves in the BD system if pressure continues to lower?
- All air reg valves on BD system will isolate on loss of ctrl air
- DRV-350/352
- BD isolation valves
- BD Flow Ctrl Valves
- BD Sample Valves
What does SGWLC maintain?
- SGWLC maintains SG Narrow Range level at 43.8% for all power levels.
What is the dominant control for SG Level? ***
- Level Dominant (43.8%)
- Steam Generator Level overrides Feed flow/Steam Flow mismatch over time, level is a lag signal*
What causes a Steam Line Isolation (SLI)? ***
- Cnt # High-High at 2.8# (2/4)
- SG # low < 500# (1/1 on 2/4 SG)
- High Stm flow with P-12 (1.42E6/1.6E6) (1/2) on 2 SG
What is the definition of density compensation?
- converts volumetric flow rate of steam to mass flow rate for input into SGWLC circuit. (Left 2 Channels ctrl SG lvl)
Where do we measure SG Level?
- SG Downcomer
What is swell caused by? ***
- an increase in steam flow (which will cause an increased indication of SG lvl in the downcomer due to decreased SG #) (More intense boiling)
What is shrink caused by?
- reduction in steam flow (which will cause an decreased indication of SG lvl in the downcomer due to a rise in SG#) (Less intense boiling)
If the steam flow indication fails high to your flow controller, what will happen the FRV?
- The FRV will go open because Feed Flow will want to match Steam Flow