Steam Boilers Tech Check 5 Flashcards

1
Q

Burning a fuel releases

A. solar energy
B. hydrogen gas
C. heat energy
D. none of the above

A

C. heat energy

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A clogged vent line on a fuel oil tank being filled with fuel oil could result in a

A. loss of suction
B. pressure buildup, which would cause an oil spill
C. loss of pressure
D. no vents are allowed on fuel oil tanks

A

B. pressure buildup, which would cause an oil spill

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A high suction line on a fuel oil tank is used when

A, the tank is full
B. the tank is low on fuel
C. signs of sludge and water are evident in the tank
D. changing over tanks

A

C. signs of sludge and water are evident in the tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The purpose of the fuel oil return line is to

A. circulate fuel oil during warm-up
B. return fuel oil that bypasses the burner
C. return fuel oil from the relief valve
D. all of the above

A

D. all of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

In both steam and air atomizing burners, atomization is accomplished

A. live steam and air
B. high fuel oil pressure
C. the sprayer plate
D low temperature, high pressure fuel oil

A

A. live steam and air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

In a low pressure gas burner, a shuts off the gas supply if a low water condition exists.

A. pressure control
B. zero-reducing governor
C. manual reset valve
D. vaporstat

A

C. manual reset valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The pneumercator is used to

A. indicate gallons of fuel oil in the tank
B, supply primary air to the burner
C, indicate fuel burned in a 24-hour shif
D. indicate gallons of makeup used

A

A. indicate gallons of fuel oil in the tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An indication of a dirty fuel oil strainer would be
across the strainer.

A, a large pressure drop
B. an equalizing of pressure
C, a slight pressure drop
D no change in pressure

A

A, a large pressure drop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Duplex strainers are found on of the fuel oil pump.

A, the suction side
B, the discharge side
C. both the suction and discharge sides
D. none of the above

A

C. both the suction and discharge sides

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  1. Fuel oil heaters must be used when burning No. fuel oil

A.1
B.2
C.4
D. 6

A

D. 6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fuel oil heaters must be protected from excessive fuel oil pressure because they are located the fuel pumps.

A. above
B. on the suction side of
C, on the discharge side of
D. they need no protection due to internal bypass

A

C, on the discharge side of

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The rotary cup burner atomizes fuel oil using

A. pressure
B. a spinning cup
C. a spinning cup and high velocity air
D. an air nozzle

A

C. a spinning cup and high velocity air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

In a pressure atomizing burner, atomization is accomplished by

A. high pressure gas in the burner blower
B, rotating, high pressure oil coming out of the plug or sprayer plate
C. air or steam mixing with the oil the burner
D. the low temperature, high pressure oil supplied to

A

B, rotating, high pressure oil coming out of the plug or sprayer plate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A gas pressure regulator is used to control the

A. flow of gases of combustion
B. desired pressure at the burner
C. air flow going to the burner
D. mixture of air and gas

A

B. desired pressure at the burner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A solenoid valve is a direct acting valve in the gas system and is used

A. to regulate the flow of gas to the burner
B. to regulate the flow of air to the burner
C, as an automatic gas shutoff valve
D. as a gas return valve

A

C, as an automatic gas shutoff valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

To prevent caking and to dry the coal entering the pulverizer,

A. heating coils are used
B, electric pipe heaters are used
C. warm air is used
D dryers are used

A

C. warm air is used

17
Q

Blowers are used in a high pressure gas system to

A, supply air for combustion
B. remove gases of combustion
C. regulate the flow of gas
D, cool the combustion chamber

A

A, supply air for combustion

18
Q

The air-to-gas ratio is maintained by a(n)

A. air damper
B. butterfly valve
C. modulating motor and linkage
D. all of the above

A

D. all of the above

19
Q

The gas pressure reducing valve in the low pressure gas system reduces the gas pressure to psi.

A.0
B.5
C. 10
D. 15

A

A.0

20
Q

The amount of gas drawn into the air stream in a low pressure gas system is controlled by the

A. manual reset valve
B. check valve
C. venturi effect
D. flow control valve

A

C. venturi effect

21
Q

Boilers are equipped with a combination gasfuel oil burner for

A greater efficiency
B. more flexible operation
C. safer operation
D higher rates of combustion

A

B. more flexible operation

22
Q

The underfeed stoker ean burn

A. only anthracite coal
B. only bituminous coal
C. anthracite or bituminous coal
D. only coal with a highly volatile content

A

C. anthracite or bituminous coal

23
Q

spreader stokers burn coal

A. only in suspension
B. only on grates
C. in suspension and on grates
D., in retorts

A

C. in suspension and on grates

24
Q

To achieve complete combustion in a spreader stoker, air is introduced

A. under and over the fuel
B. only under the fuel bed
C. only over the fuel bed
D. using an induced draft fan

A

A. under and over the fuel

25
Q

The thickness of the fuel bed on a chain grate stoker is regulated by a coal

A. conveyor
B. scale
C. hopper
D. gate

A

D. gate

26
Q

Pulverized coal burns

A. on inclined grates
B, in suspension
C. in suspension and on grates
D in the pulverizer

A

B, in suspension

27
Q

The volume of gas to the burner in a high pressure gas system is controlled by a valve.

A. solenoid
B. manual reset
C. check
D. butterfly

A

D. butterfly