Relay Officer drives his vehicle from the water source to the incident using his odometer to measure the distance in ____.
tenths of a mile.
He requests ___ apparatus with 3½” hose per tenth of a mile or Portion thereof plus one company for the hydrant
one triple
A standard ___ hose bed will cover 528’ (1/10 mile) with sufficient slack hose to make connections at each end.
600’
Triple engines with ____ only should not be used except at the hydrant.
2½” hose
If the necessity arises to use them in the relay, they should lay 600’ of ___. The total capacity of the relay will be limited to ___ gpm.
two 2½” lines / 700
All pump operators will build pressure as their suction gauge pressure increases. On flat terrain, all pumps will maintain ____ engine pressure using their gate pressure gauge.
180 psi
The delivery to each succeeding pump in the line will be ____ positive pressure.
900 gpm at 10 psi
Remember, in a relay situation, shutdowns are always initiated at the ____.
source of supply
Older reserve apparatus with 2½” discharge gates, depending on the design of the gate, will experience as much as ____ friction loss in the gate when 900 gpm is flowing.
50 psi
Do not use shutoff butts. They will restrict the flow of water to approximately ____.
450 gpm
When 3½” hose is used and large quantities of water are desired, four-way valves should not be used in the line due to the ____.
added restriction
Do not use ___ bypasses in conjunction with 3½” hose lays.
2½”