Standard Basic Relay Operation Flashcards

1
Q

Relay Officer drives his vehicle from the water source to the incident using his odometer to measure the distance in ____.

A

tenths of a mile.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

He requests ___ apparatus with 3½” hose per tenth of a mile or Portion thereof plus one company for the hydrant

A

one triple

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A standard ___ hose bed will cover 528’ (1/10 mile) with sufficient slack hose to make connections at each end.

A

600’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Triple engines with ____ only should not be used except at the hydrant.

A

2½” hose

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If the necessity arises to use them in the relay, they should lay 600’ of ___. The total capacity of the relay will be limited to ___ gpm.

A

two 2½” lines / 700

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

All pump operators will build pressure as their suction gauge pressure increases. On flat terrain, all pumps will maintain ____ engine pressure using their gate pressure gauge.

A

180 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The delivery to each succeeding pump in the line will be ____ positive pressure.

A

900 gpm at 10 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Remember, in a relay situation, shutdowns are always initiated at the ____.

A

source of supply

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Older reserve apparatus with 2½” discharge gates, depending on the design of the gate, will experience as much as ____ friction loss in the gate when 900 gpm is flowing.

A

50 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Do not use shutoff butts. They will restrict the flow of water to approximately ____.

A

450 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When 3½” hose is used and large quantities of water are desired, four-way valves should not be used in the line due to the ____.

A

added restriction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Do not use ___ bypasses in conjunction with 3½” hose lays.

A

2½”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly