Splicing And Terminating 030104c Flashcards
What are the four common classes of terminations and connections?
Objective 1 Page 2
Soldered
Fused
Mechanical
Compression
What type of connection is best for electronics?
Objective 1 Page 2
Soldered
What connection normally requires a screwdriver and is considered reusable?
Objective 1 Page 3
Mechanical
What is the proper way to remove the insulation from conductors?
Objective 2 Page 7
Penciling the insulation at approximately 30 degrees.
Ensure to never ring the conductors.
Name four materials that can be used to reinsulate a spliced conductor?
Objective 2 Page 8
Electrical tape
Heat Shrink Tubing & Caps
Splicing Compound
Preformed insulating covers and boots.
What are two insulation properties you must consider when selecting a twist-on wire connector?
Objective 2 Page 8
Maximum voltage
Temperature.
What are the three basic wire or cable connections?
Objective 3 Page 11
Splices
Taps
Terminations.
What is the difference between a splice and a tap?
Objective 3 Page 11 & 12
Splice is the joining of two or more conductors of the same size and ampacity.
Taps are connections when at least one of the conductors is a smaller size that the other conductors.
What is a termination?
Objective 3 Page 13
The connection of a conductor at its final destination.
What is the maximum wire size that can be terminated under a screw?
Objective 4 Page 15
10 AWG
On devices that have a wire binding screw terminal with a raised shoulder what is not required?
Objective 4 Page 15
It is not required to wrap the conductor around the screw.
What are the four problems specific to aluminum conductor connections?
Objective 5 Page 22 & 23
Oxidation
Cold Flow
Thermal Expansion
Galvanic Corrosion.
What markings must be on a receptacle if it is to be used with aluminum conductors?
Objective 5 Page 24
CU/AL or CO/ALR
What must you do after stripping aluminum wire?
Objective 5 Page 22
Must be wire brushed to remove any oxide then coat with anti-oxidant.
What can you do to help with cold flow?
Objective 5 Page 23
A lowering binding pressure can help reduce cold flow. A conical or helical washer must be used when you connect aluminum lugs to bus bars.