Service water Flashcards
Which system's principle purpose is the dissipation of decay heat? A. Service Water System B. Component Cooling Water System C. Ultimate Heat Sink D. Shutdown Cooling System
C’f Ultimate Heat Sink
Which of the following describes the rated design for the Service Water Pumps?
A. 8000 gpm and 120 feet TDH (Total Developed Head).
B. 8000 gpm and 140 feet TDH (Total Developed Head).
C. 7800 gpm and 120 feet TDH (Total Developed Head).
D. 7800 gpm and 140 feet TDH (Total Developed Head).
B. 8000 gpm and 140 feet TDH (Total Developed Head)
Which of the following service water controls does the operator have the capability of
manipulating from remote panel, C-33?
A. P-7A/B/C, Service Water Pump start/stop handswitches.
B. CV-1359, Non-critical service water header isolation valve.
C. CV-0847, Containment Air Cooler service water supply.
D. CV-0857, Critical headers cross connection.
C~ CV-0847, Containment Air Cooler service water supply
Service water pumps P-7A & 78 are running with service water header pressures at 76
psig. Due to an electrical fault, the closing coil fuses for Service Water Pump P-7C
have deenergized.
Assuming all bulbs are good, what Control Room indication could be used to confirm
the above condition?
A. The AMBER light will NOT illuminate when placing P-7C in standby.
B. P-7C would trip if it was in service.
C. The GREEN light above the handswitch is ON.
D. The AMBER light remains ON if P-7C is taken out of standby.
A. The AMBER light will NOT illuminate when placing P-7C in standby
Service Water Pumps, P-7B and P-7C are in service with P-7A in Standby. Service
Water pump discharge pressure is 75 psig.
Which of the following would cause P-7A to automatically start?
A. The air line to CV-1359, Non-Critical Service Water Header Isolation Valve is
severed.
B. The Secondary Side Auxiliary Operator commences chlorinating the Service Water
Bay, causing Service Water pump discharge pressure to fall to 56 psig.
C. CV-1319, SW Pump Cross-Tie, is inadvertently CLOSED.
D.The Control Operator stops the P-7B Service Water Pump; Critical SW Header
pressures lower to 36 psig.
D.The Control Operator stops the P-7B Service Water Pump; Critical SW Header
pressures lower to 36 psig.
Non-critical Service Water has been isolated for maintenance and the containment air
cooler high capacity valves are closed to help raise containment temperature.
• It is day 40 of an extended plant outage.
• Service Water Pumps P-7A and P-7B are in-service.
• Service Water Pump P-7C is in standby.
• Service water header pressure is 80 psig.
To prevent P-7B from being run at significantly reduced flows, the CRS directs the
NCO to secure P-7B. When Service Water Pump P-7B is secured header pressure
lowers to 45 psig, Service Water P-7C starts, and header pressure returns to 80 psig.
Should Service Water Pump P-7C have started and why?
A. Yes, a standby pump starts at 40 psig discharge pressure on either of the other
pumps
B. Yes, a standby pump starts at 45 psig header pressure
C. No, the standby pump should not start when a pump is manually secured
D. No, the standby pump should not start until header pressure reaches 40 psig
A. Yes, a standby pump starts at 40 psig discharge pressure on either of the other
pumps
The Plant is in mode 1 with Service Water Pumps P-7A and P-7C in service. Service
Water Pump P-7B is in Standby. Service Water pump discharge pressure is 75 psig.
Which of the following would cause P-7B to automatically start?
A. CV-1318 SW Pump Cross-Tie is inadvertently CLOSED.
B. The air line to CV-1359, Non-Critical Service Water Header Isolation Valve, is
severed.
C. P-7C discharge pressure switch PS-1320 is inadvertently isolated.
D. P-7A Service Water Basket Strainer F-2 dIP is >5 psid and increasing.
C. P-7C discharge pressure switch PS-1320 is inadvertently isolated.
The plant is on day 30 of a refueling outage. Due to main generator maintenance the
Non-critical Service Water header has been isolated.
• Service Water Pumps P-7A and P-7C are in-service.
• Service Water Pump P-7B is in standby.
• Service water header pressure is above 80 psig.
Due to the low flow conditions the CRS directs the operator to secure P-7C. When
Service Water Pump P-7C is secured critical service water header pressure lowers to
45 psig. Service Water Pump P-7B did not start.
Is this the correct service water pump response and why?
A. No, P-7B should have started at 40 psig discharge pressure on either of the other
pumps.
B. No, P-7B should have started at 45 psig header pressure.
C. Yes, P-7B should not start since P-7C was manually secured.
D. Yes, P-7B should not start until header pressure reaches 40 psig.
A. No, P-7B should have started at 40 psig discharge pressure on either of the other
pumps
The air line to CV-0870, Service Water inlet valve to Containment Air Cooler #3, has
completely broken off resulting in a total loss of operating air to the valve. CV-0870
will:
A. open or remain open.
B. close or remain closed.
C. stay as is due to nitrogen backup.
D. stay as is due to internal valve design.
A. open or remain open.
The air line to CV-0869, Service Water Inlet to Containment Air Cooler #4 Valve has
completely broken off. As a result of this, the valve will:
A. Open or remain open.
B. Close or remain closed.
C. Stay as is, due to nitrogen backup.
D. Stay as is, due to internal valve design.
B. Close or remain closed.
The plant is at normal full power operations with all four Containment Air Cooler (CAC)
High Capacity Outlet valves open. Service Water Pump discharge pressure is 82 psig.
All Service Water Pumps are inservice. Which one of the following actions will lower
Service Water Pump discharge pressure?
A. Secure the “B” CAC fans
B. Close one CAC High Capacity Outlet valve.
C. Secure the “A” CAC fans.
D.Secure one Service Water pump.
D.Secure one Service Water pump
Which one of the following describes the position of the Containment Air Cooler
Service Water inlet and outlet valves for a complete loss of Instrument Air and why?
A. VHX-4 inlet and outlet are closed; VHX-1, 2, 3 inlet and outlet are open. This
provides maximum cooling on a loss of instrument air.
B. VHX-4 inlet and outlet are closed; VHX-1, 2, 3 inlet and outlet are open. VHX-4
isolates because it is not safety-related. VHX-1, 2, 3 valves have nitrogen backup.
C. VHX-4 inlet is closed; VHX-1, 2, 3 inlet and outlet and VHX-4 outlet are open.
VHX-4 inlet closes because it is not safety-related. VHX-1, 2, 3 and VHX-4 outlet
have nitrogen backup.
D. VHX-4 inlet is closed; VHX-1, 2, 3 inlet and outlet and VHX-4 outlet are open. This
provides maximum cooling on a loss of instrument air
D. VHX-4 inlet is closed; VHX-1, 2, 3 inlet and outlet and VHX-4 outlet are open. This
provides maximum cooling on a loss of instrument air
Annunciator EK-1129, “SERVICE WATER PUMP BAY LO-LEVEL” alarm initiates and
bay level is lowering.
Which of the following describes the effect on the Service Water System?
A. Temperatures on components cooled by service water will start to lower.
B. The dp on the service water pump basket strainers will start to rise.
C. The critical service water header pressures will start to lower.
D. The service water booster pump P-25, will automatically start.
C. The critical service water header pressures will start to lower
Annunciator EK-1129, “SERVICE WATER PUMP BAY LO-LEVEL” alarm initiates and
bay level is lowering.
Which of the following describes the effect on the Service Water System?
A. Temperatures on components cooled by service water will start to lower.
B. The dp on the service water pump basket strainers will start to rise.
C. The critical service water header pressures will start to lower.
D. The screenwash system will automatically start.
C. The critical service water header pressures will start to lower.
The Service Water System Break Detector alerts the operators to the potential of:
A. Flooding in the Turbine Building.
B. Flooding in the Containment Building.
C. Exceeding the service water pumps motor amps.
D. Exceeding the service water design flow rates
B~ Flooding in the Containment Building.
If the Turbine Bldg. were to experience a loss of Non-Critical Service water due to a
piping system malfunction, which annunciators would alert the control room operators
that a reactor trip was required?
A. EK-0260 H2 Cooler Hi Temp, and EK-1165 Non-Critical Serv Water Lo Press.
B. EK-0259 Exciter Cooler Hi Temp, and EK-1165 Non-Critical Serv Water Lo Press.
C. EK-0156/62 Condensate Pump Hi Temp, and EK-0259 Exciter Cooler Hi Temp.
D. EK-0259 Exciter Cooler Hi Temp, and EK-0260 H2 Cooler Hi Temp.
Not Sure, to be added
Given the following conditions:
• The plant is operating at 100% power.
• Service Water Pump P-7B is tagged out for maintenance.
• P-7A is in service with running amps = 80 amps.
• P-7C is in service with running amps = 83 amps.
• All systems are functioning normally for plant conditions.
A problem develops with the Service Water System. The NCO then notes the following
indications:
• CRITICAL SERV WATER HEADER “A” LO PRESSURE
• P-7A Service Water Pump amps indicates 94 amps.
• P-7C Service Water Pump amps indicates 83 amps.
NO operator actions have been taken. Which one of the following accounts for the
above conditions?
A. A break between P-7A and CV-0845.
B. A loss of instrument air to CV-0844.
C. A loss of instrument air to CV-1359.
D. A partially plugged discharge basket strainerfor P-7A.
A. A break between P-7A and CV-0845.
The Non-critical service water header isolation valve, CV-1359, has experienced a
malfunction causing the valve to close. Which annunciators would alert the control
room operators that a reactor trip was required?
A. EK-0259 Exciter Cooler Hi Temp and EK-0156/62 Condensate Pump Hi Temp
B. EK-1124 Traveling Screen Hi dP and EK-1 129 Service Water Pump Bay Lo Level
C. EK-1165 Non-Critical Serv Water Lo Press and EK-0260 H2 Cooler Hi Temp
D. EK-1165 Non-Critical Serv Water Lo Press and 0259 Exciter Cooler Hi Temp
D. EK-1165 Non-Critical Serv Water Lo Press and 0259 Exciter Cooler Hi Temp