Section H Ontario Fire Code – Parts 6, 7 &8 Flashcards
H-1.
(OFC Div. B. 6.2.4.3)
Portable extinguishers with a gross weight of 18 kg or less are required to be installed so that the top of the extinguisher is:
a) Not more than 1.1m above the floor
b) Not more than 1.5m above the floor
c) Not more than 1.3m above the floor
d) None of the above
b) Not more than 1.5m above the floor
H-2.
(OFC Div. B. 6.2.5.2)
When determining portable extinguisher requirements, a parking garage or light manufacturing business is to be graded as:
a) Ordinary hazard
b) Extra hazard
c) Light hazard
d) Extinguishers are not required
a) Ordinary hazard
H-3.
(OFC Div. B. 6.2.6.4)
A portable extinguisher with a 2A rating is acceptable for installation in:
a) A light hazard occupancy
b) An ordinary hazard occupancy
c) An extra hazard occupancy
d) Both a) & b)
d) Both a) & b)
H-4.
(OFC Div. B. 6.2.7.2)
The Ontario Fire Code requires portable fire extinguishers to be inspected:
a) Monthly
b) Weekly
c) Yearly
d) Every six months
a) Monthly
H-5.
(OFC Div. B. 6.2.6.6)
Hose stations allow the number of portable extinguishers to be reduced:
a) Only if the building is sprinklered
b) By one quarter
c) By one third
d) By one half
d) By one half
H-6.
(OFC Div. B. 6.5.3.4)
To ensure they are free from damage, corrosion, grease, dust, paint, etc., sprinkler heads are required to be checked:
a) At least once per year
b) As found necessary
c) Once a month
d) Both b) & c)
a) At least once per year
H-7.
(OFC Div. B. 8.1.2.1)
The Ontario Fire Code requires that existing building services that may be affected by demolition so as to cause a fire hazard:
a) If relocated are to be protected
b) Are to have a fire watch provided over
c) Are to be shut off and terminated
d) a) or c)
d) a) or c)
H-8.
(OFC Div. B. 8.1.2.6 (3))
Buildings being demolished which are not equipped with a standpipe system require a temporary standpipe be provided:
a) If the building is over 8 storeys in building height
b) If the building is over 84m in height
c) If the building is over 4 storeys in building height
d) At least to 3 floor levels below the level of the floor being demolished
a) If the building is over 8 storeys in building height
H-9.
(OFC Div. B. 6.7.1.4)
The amount of fuel required to be stored and connected to an emergency power system shall be sufficient to operate the engine for:
a) At least 2 hours
b) At least 4 hours
c) At least 8 hours
d) At least 30 minutes
a) At least 2 hours
H-10.
(OFC Div. B. 6.5.5.4 (4))
Dry-pipe sprinkler systems are required to be trip tested with the control valve fully open:
a) Monthly
b) Every 3 years
c) Monthly unless the system has been subjected to freezing
d) Every 15 years
b) Every 3 years
H-11.
(OFC Div. B. 6.2.6.1 (2))
In an unoccupied warehouse equipped with a fixed fire protection system:
a) Fire extinguishers are not required
b) Fire extinguishers are required in accordance with Division B, Table 6.2.6.A. of the Ontario Fire Code
c) A suitable number of extinguishers shall be provided for responding personnel in locations approved by the Chief Fire Official
d) The number of fire extinguishers can be reduced by one third
c) A suitable number of extinguishers shall be provided for responding personnel in locations approved by the Chief Fire Official
H-12.
OFC Div. B. Table 6.2.6.B)
The maximum travel distance allowable to a portable extinguisher rated for a Class B fire for any grade of hazard (light, ordinary, extra) is:
a) 25m
b) 9m
c) 20m
d) 15m
d) 15m
H-13.
(OFC Div. B. 6.3.1.5)
Once activated, a fire alarm system is not to be manually silenced:
a) Until the area shown on the annunciator panel has been checked for fire by supervisory staff
b) Until the building has been fully evacuated
c) Until the Fire Department arrives
d) Until it is determined by supervisory staff, in accordance with approved procedures as detailed in the building’s Fire Safety Plan that no fire emergency exists
d) Until it is determined by supervisory staff, in accordance with approved procedures as detailed in the building’s Fire Safety Plan that no fire emergency exists
H-14.
(OFC Div. B. 6.3.2.2 (1))
Fire alarm systems are subject to the inspection and test requirements of: a) ULC-S537-1979
b) CAN/ULC-S536, “Inspection and Testing of Fire Alarm Systems”
c) CAN/ULC-701-1977
d) ULC-S536-1979, Section 4, “Periodic Testing of Fire Alarm System”
b) CAN/ULC-S536, “Inspection and Testing of Fire Alarm Systems”
H-15.
(OFC Div. B. 6.4.2.5 (1))
Standpipe hose is required to be tested:
a) Monthly
b) Yearly
c) Before being re-racked after use
d) Never - not required
d) Never - not required