What 2 things are not mentioned in the code book for doing apartment calculations?
- Summer vs. Winter
(A/C vs Heat + Car Stalls)
Choose Larger - ALWAYS use 240V as divisor for Apartments
Regarding Apartment or Single Dwelling calculations; If you have a load at 2000W and a load at 2000VA how do you add them up?
Treat the VA like watts. 2000W + 2000VA = 4000W
*We don’t deal with VA properly until the Masters course.
The service raceway will NEVER have what in it?
A Bonding Conductor
When you add up all items in a Single Dwelling from 8-200 1) a) you get 22500W as a minimum value.
8-200 1) b) works out to be 24,000W based on the floor area.
What is the Calculated load of the service?
24,000W
(You take the higher of 1a and 1b as the Calculated Load)
Where in the CEC do you go for how to treat 2 Ranges in a single dwelling?
App B 8-200