Section 2 General Work Practices Flashcards
1
Q
What are the transmission voltages
A
69,138, 345
2
Q
201
A
safe working distance from energized apparatus
3
Q
MAD 5.1 -15kv
A
Phase to ground 26inches
Phase to phase 27 inches
4
Q
MAD 15.1 to 36 kv
A
Phase to ground 31inches
Phase to phase 35 inches
5
Q
MAD 69 kv
A
Phase to ground 3ft 4in
Phase to phase 4ft
6
Q
MAD 138kv
A
Phase to ground 4ft 4in
Phase to phase 5ft 5 in
7
Q
MAD 345 kv
A
Phase to ground 11ft 3 in
Phase to phase 18ft 2 in
8
Q
202
A
Work around energized lines
9
Q
203
A
Ground wire ground neutrals
10
Q
204
A
Connections in common neutrals
11
Q
205
A
Ground testing
12
Q
206
A
Phasing or tying circuits together
13
Q
207
A
Installing and revoking jumpers
14
Q
Arc level 1
A
9.8 cap
15
Q
Arc level 2
A
9.8 - 29 cal