Briefly described the three major components of the unit eight fire protection system 
Fire zones, defines the specific fire protection needed for the area.
Fire area, associated with a building or piece of equipment.
Main fire protection control system, system that controls the CO2, alarms, and deluge
Where are the main and remote auxiliary fire protection panels located at unit unit eight
Main control center and local control centers 
List the equipment and compartments protected by CO2
GT 81,82 and 83 load compartment, turbine compartment, auxiliary compartment 
State the concerns caused by low nitrogen system pressure alarm
Nitrogen is used to activate Deluge system on ST 84, transformers and cable trays and North tank farm control valves. 
Explain how each firewater pond level is controlled
One-manual gates, and float system
Two-canal level
Three- to be pumped from pond one or two 
State the normal operating pressure for firewater system
150 psi 
List the six main AC voltages that will be produced and utilized by unit unit eight
15 KV, 18kv, 5kv, 120V, 240V, 480V
List the 6 main AC voltages that will be produced and utilized by unit unit eight
5kv, 15kv, 18kv, 480v, 240v, 120v
Defined the term step up transformer
Takes 15 KV and steps it up to 138 KV low to high
State the operating units at the oyster Creek site
CRW, LHC9, LHC8, phenol, PDH, vinyl, Power 8, braskem
State what services is provided by B breaker on 15 KV system
It is a service breaker that reduces voltage to supply plant equipment 
List the hazards associated with clearing, electrical switch gears
Arc flash, shock, grounding, pinchpoints 
List the device that is used to measure, bearing and winding temperatures in a high voltage pump motor
RTD resistance temp detectors 
State whom must be contacted before operating or clearing any 15 KV switch gear
Power dispatch extension, 2575 
State the three operating positions that a five KV breaker can indicate while in its housing
Test position, connected, disconnected
State the approved electrical protective equipment required when operating switch gears
Flash hood, flash suit, gloves, hardhat, side shields
State who may issue an ESWP at the Unit eight Plant
Train documented personnel by I&E supervisor 
State the main purpose of a positive nitrogen purge on a transformer
Keeps out air and moisture
List the two main purposes of a transformer
Steps up or down voltages also it’s used to isolate power from source
List, the purpose and location of the pressure relief device used on a transformer
Top of transformer and used to relief, gas pressure 
Who will issue an order to Raise or lower the settings on the load tap chargers used when the 15 KV 138 KV transformers 
Power, dispatch
List the purpose of protective relay
Used to protect personnel from electrical shock during abnormal conditions, and used to protect equipment
List the purpose of an 86 lockout relay
Trips/alarms and locks out more than one breaker. It has to be manually reset when electrically tripped. 
State the building location of the two 125 V DC distribution buses
OC 882 local 
List the major components of the 125V DC system
2 125 VDC buses, two sets of batteries, three battery chargers 
List the primary voltage for the chargers and the location where power originates from
MCC switchgear and 480 VAC 
State the type of cooling medium used to cool the stator windings of each generator
Hydrogen
State the type of gas used for arc suppression in the 15 KV breaker
SF-6 sulfur hexa fluoride
List whom may issue in order to raise or lower the tap chargers on the 15 KV 138KV distribution transformer
Power, dispatch