What is the usual “watts per unit length” rating of standard density baseboard heaters?
820W per meter
Where in a room should baseboard heaters be mounted?
At floor level, centred along a wall and preferably under a window
What type of heater is installed at ceiling height?
A Unit heater
Residential electric furnaces are usually available in both single-phase and three-phase ratings from ______ kw to _____ kw
4kw to 50kw
What type of heater unit can be used with certain oil-fired, force air furnaces?
A Plenum Heater
Residential water heaters are commonly available in ____ kW and ____ kW
3kW and 4.5kW
What are three types of thermostats commonly used is residential space heating applications?
Line Voltage
Low Voltage
Electronic
If a heat lamp using a medium-base lampholder is installed in a residential bathroom, does it have to be on a separate heating branch circuit? Y or N
No
Where are the supply registers of force-air furnace normally located?
Around the perimeter of each room
What is the purpose of the heat exchanger in a gas-fired furnace?
To separate the products of combustion from the air
The typical efficiency of a gas-fired furnace is between ____ % - ___ %
70%-80%
How many conductors are commonly needed between the furnace and the room thermostat? And what is the magnitude of the voltage that they carry?
2 or 3c
24v
Which does the room thermostat control directly, the gas valve or the blower motor?
Gas Valve
After the thermostat opens, which shuts off first, the blower motor or the gas burner?
The gas burner
What is the purpose of the anticipator resistor in the room thermostat?
To limit the set point overshoot to an acceptable value
What is the purpose of the thermocouple? Is it necessary?
It uses thermoelectric generation to create a small voltage when heated.
No.
List three conditions that may cause overheating of the heat exchanger
Room thermostat contacts stuck
Blower does not run
Insufficient air flow
What prevents the heat exchanger from overheating?
The high limit over heat safety thermostat will close the gas valve
What are the Typical settings for the blower control/overheat safety thermostat?
- Blower off 90 degrees
- Blower on 130 degrees
- High limit off 104 degrees