S-12 DEFINITIONS Flashcards
A Deluge Sprinkler System Is?
A sprinkler system employing automatic sprinklers that are attached to a piping system that is connected to a water supply through a valve that is opened by a detection system installed in the same areas as the sprinklers.
A Deluge Valve is?
A water supply control valve intended to be operated by actuation of an automatic detection system that is installed in the same area as the discharge devices.
What is a Dry Sprinkler?
A sprinkler secured in an extension nipple that has a seal at the inlet to prevent water from entering the nipple until the sprinkler operates. May be configured with an upright, pendent or sidewall sprinkler.
What is a Dry Pipe Sprinkler System?
A sprinkler system employing automatic sprinklers that are attached to a piping system containing air or nitrogen under pressure. The release of the air or nitrogen (as from the opening of a sprinkler) results in the water pressure opening a valve called a dry pipe valve, resulting in the flow of water into the piping system and out of the fused sprinkler heads.
What is a Discharge Device?
A device designed to discharge water or foam-water solution in a predetermined, fixed or adjustable pattern. Examples include, but are not limited to, sprinklers, spray nozzles, and hose nozzles.
What is an Early Suppression Fast Response Sprinkler (ESFR) ?
A type of fast response sprinkler that is listed for its capability to provide fire suppression of specific high fire challenge hazards.
An Extra Large Orifice Sprinkler (ELO) is?
a sprinkler head with an orifice size equal to or greater than 1”. Particularly for protection of high piled storage in warehouses and less pressure is required to achieve a given discharge density.
Define Extended Coverage Sprinklers:
A type of spray sprinkler with a maximum area of coverage of 400 sq ft (20 foot by 20 foot spacing between sprinklers) for light hazard occupancies to a maximum of 144 square feet (12 foot by 12 foot spacing between sprinklers) for extra hazard occupancies.
Define Fire depart connection:
A connection, normally on the exterior of the building, through which the fire department can pump supplemental water into the sprinkler system, standpipe, or other system furnishing water for fire extinguishment to supplement existing water (Formerly known as Siamese connection).
What is a hydraulic placard?
A sign attached to a hydraulically calculated system indicating the design density, required gallons per minute and pressure for the system to operate properly.
Define Hydraulically calculated systems:
A method of sizing automatic sprinkler piping using a prescribed amount of water to be distributed over a specific area
Define impairment coordinator:
The person responsible for ensuring that proper safety precautions are taken when a fire protection system is placed out of service.
Define intermediate level sprinkler/Rack Storage Sprinkler:
A sprinkler equipped with integral shields to protect the operating element from discharge from sprinklers installed at higher elevations.
Define Large orifice sprinkler:
A sprinkler head with an orifice size equal to or greater than 3/4” and less than 1”
Define listed device:
A fire protection component that had been tested to perform under parameters specified for its use by a nationally recognized testing agency.
Underwriter’s (UL) and factory mutual are the two most common