RULE 12 - GENERAL DESIGN REQUIREMENTS Flashcards
Excavations
Excavations must not endanger life or
property
Any person undertaking an excavation
shall ensure that the soil of the adjoining
property will not cave in or settle.
Cut slopes shall no be steeper than 2:1
(horizontal:vertical).
Number of exits
Every building shall have at least one exit
Upper floors with occupant load of more
than 10 shall have at least two exits
A mezzanine floor bigger than 185sqm or
having more than 18.00m in any dimension
shall have at least two stairways to an
adjacent floor
Every floor with occupant load of 500-999
shall have at least 3 exits.
Every floor with occupant load of 1000 or
more shall have at least 4 exits.
50% of floor above + 25% of floor above that
Width of exits
Total width of exits = Occupant load/165
Note: This is the total width in meters
Again, +50% of occupant load of storey
above + 25% of occupant load of storey
above that
Arrangement of exits
If two exits are required, the two exits must
be apart by at least 1/5 of the perimeter of
the area served.
If three or more are required, they shall be
arranged a reasonable distance apart
Distance to exits
If without a sprinkler system, 45.00m
maximum
If with a sprinkler system, 60.00m
maximum
Measured from any point in a building,
measured along the line of travel
Exit Doors
When serving an occupant load of 50 or
more, must swing in the direction of exit
travel
Double acting doors shall not be used as
exits when serving a tributary load of more
than 100. Must be provided with a view
panel of not less than 1300 sq. cm.
Type of locks
Exit doors shall be openable from the inside
without the use of a key or any special
knowledge or effort
Size of doors
Minimum width of doorway: 0.90mm
Minimum height of doorway: 2.00m
Minimum clear width of exitway: 0.70m
Shall be capable of opening at least 90
degrees
Maximum door leaf width: 1.20m
Prohibited door
The following shall not be used as exit
doors:
Revolving doors
Sliding doors
Overhead doors
Change in floor level at doors
There shall be a floor or a landing on each side
of an exit door
The floor/landing shall not be more than
50mm lower than the door threshold
Exception: For Group A or B occupancies, a
door may open over the top step provided that
the landing is not more than 200mm from the
floor level and the door does not swing over
the top step.
Corridors
Minimum width: 1.10m
This width shall be unobstructed, except
that trim handrails and doors when fully
opened shall not reduce the required with
by more than 200mm.
Doors in any position shall not reduce the
width by more than ½.
Dead ends
Maximum length: 6.00m
Stairways Widths
Occupant load more than 50: 1.10m
Occupant load of 50 or less: 0.90m
Occupant load of less than 10 (private): 0.75m
Handrails shall not reduce the width of
stairways by more than 100mm
Riser and tread
Maximum riser: 200mm
Minimum tread: 250mm
Stairway headroom
Not less than
2.00m measured
from the nosing