RQ-C-KNOW ESF Actuations Flashcards
Commit to Memory
1
Q
SI Trips
A
Manual Containment Pressure, High Pressurize Pressure Low SG Differential Pressure Steam Generator Pressure Low
2
Q
Manual SI Coincidence
A
1 of 2/ Train
3
Q
Containment Pressure High Setpoint
A
1 psig increasing
4
Q
Containment Pressure High Coincidence
A
2 of 3
5
Q
Pressurizer Pressure Low Setpoint
A
1775 psig lowering
6
Q
Pressurizer Pressure Low Coincidence
A
2 of 3
7
Q
Pressurizer Pressure Low Interlock
A
Man Block with P-11
8
Q
SG Differential Pressure Setpoint
A
100 psid
9
Q
SG Differential Pressure Coincidence
A
2 of any 3 on any steam line
10
Q
SG Pressure Low Setpoint
A
500 psig lowering
11
Q
SG Pressure Low Coincidence
A
1 of 1 on 2 SGs
12
Q
SG Pressure Low Interlock
A
Man Block with P-12
13
Q
Containment Spray Signals
A
Manual
Containment Pressure High-High
14
Q
CTS Manual Coincidence
A
1 of 1/ Train
15
Q
Containment Pressure High-High
A
2.8 psig increasing (delay for 233 seconds in U1)