Why is a ground grid extended beyond the main system?
Worker protection
What is the minimum insulation-resistance test voltage for a metal-oxide surge arrester rated 15kV with an MCOV rating of 12.7kV per NETA standards?
2,500 VDC
At what voltage does an arc flash hazard not exist?
None
Cable limiters and other current limiting devices should not be connected to the supply side of a service disconnect.(T/F)
False
What is the preferred method of performing primary-injection testing on a low voltage circuit breaker with ground fault protection?
Use manufacturers kit or rewire neutral
A given feeder supplies a continuous load of 20 amperes and a non-continuous load of 10 amperes. The minimum overcurrent device rating is:
35A
What instrument would normally be used to measure the winding resistance of a transformer?
Kelvin bridge
Liquid samples for dissolved gas analysis should be collected in:
Very specific containers
You have a 3-phase circuit with 250kvar and 480v, what is your current?
300.7 A
Help: I = kVAR / (V*sqrt(3))
Least likely reason for a fused low voltage circuit breaker to trip free.
Lubrication of Trip Mechanism
Types NM, NMC, and SE cables can be used for feeder temporary installations without height limitation and without concealment.
True
What would be the appropriate maintenance test voltage for an AC withstand test on a 15kV, 1600A rated metal-enclosed interrupter switchgear with stress cones?
27kVAC
A wye-delta transformer has a turns ratio of 2:1. It has a secondary line voltage of 480 V. The secondary is connected to a wye-connected three-phase resistive load of 50 ohms in each phase. How much is the secondary line current?
5.54A
Y Circuits:
V_Line = sqrt(3) * V_Phase
I_Line = I_phase
Delta Circuits:
V_Line = V_Phase
I_Line = sqru(3) * I_Phase
Which is the “Can’t Let Go” range of current flow?
9-25 mA
What is the Restricted Approach Boundary for a 50V system?
Avoid contact