Review to Date Flashcards

1
Q

What will trip AFN-P01?

A
  • LOP
  • SIAS (need to override before restarting pump)
  • CTA-HV-1 or 4 <80% open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is minimum pump speed for AFA-P01 for adequate oil lubrication?

A

1000 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does is the SG D/P lockout value and what does it affect?

A
  • 185 psid
  • Lower pressure SG will not be fed
  • (steam supply to AFA is not affected)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where are AFA-P01 potentiometers located and how are they set?

A
  • Control room, at the turbine (local), RSDP

- Pre-set by surveillance for approx. 3600 rpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will cause a DAFAS actuation?

A
  • SPS actuation on high PZR pressure (2409 psia) & SG level of 20.3% (2 of 4)
  • NO AFAS or MSIS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the risks of operating with SG NR level <27%

A

Downcomer feed ring damage may occur with flowrates <250 gpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What condenser pressures will cause ARN-P01D (standby condenser air removal pump) to start and take suction on the associated shell?

A

-4.2” HgA in shell A
-4.8” HgA in shell B
-5.3” HgA in shell C
(rule of 8’s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What conditions are required to receive the red light corresponding to the post filter unit being in the through filter mode?

A
  • Blower received start signal

- All (3) valves are properly aligned (13,19A, 19B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

At what speed should vacuum not be broken in the turbine unless an emergency exists?

A

1200 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What will isolate Aux Steam to the Aux Building?

A

1 psid in any 1 of 20 areas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What will close the Blowdown Containment Isolation Valves & Blowdown Sample Containment Isolation Valves?

A
  • SIAS
  • AFAS
  • MSIS
  • Loss of IA
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Describe interlocks and trips associated with the Condensate Pumps?

A
  • Pump will start if level > LO-LO level of 30” in associated hotwell half
  • B pump requires min of 1 suction valve to be open to start
  • Trip on low flow (<3600 gpm for 45s)
  • Trip on LO-LO hotwell level of 30” in associated half
  • Trip on bus undervoltage our lockout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How do the Condensate pump mini flow valves fail?

A

Open on a loss of air or power to the solenoid.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the motive force for the condenser vacuum breakers?

A

Spring close, air open.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What will cause the CD demin bypass valve (PDV-195) to auto-open?

A
  • -all conditions valid, even if controller in manual–
  • Demin inlet or oulet valve not fully open
  • Demin high DP (>55 psid)
  • IA low header pressure (reverse acting controller)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How does a Heater Drain Pump trip affect Condenser level?

A

Condenser level will drop (up to 9”), therefore condenser level should be maintained near 41”.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What stator cooling conditions will initiate a turbine trip?

A
  • LO inlet water pressure (549 gpm) (2 of 3)
  • HI oulet temperature (85 C) (2 of 3)
  • LO stater inlet flow, rectifier flow, bushing X flow, connecting ring flow
  • -Trip will occur after 70s delay. NKN-D41 power required to initiate trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What is the Upper Electrical Limit (UEL) and what determines if it is reached?

A
  • 200 steps or 150” withdrawn

- Reed Switch Position Transmitters (RSPTs)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

How many Reed Switch Position Transmitters are there and how do they function?

A
  • There are (2) RSPTs for each of the 89 CEAs

- A magnet closes reed switches on the voltage divider network

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What is the purpose of the MG Sets and what precautions must be observed if 1 is lost?

A
  • Receive 480V from L03 & L10 and transform it to reliable 240V
  • CEAs must be moved in MI to prevent overload
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

How do the CEDMCS UV relays operate?

A
  • Detect voltage on the CEDM bus. If 2 of 4 detect less than 180V,
  • energize K1 & de-energize K2 relays
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What will cause a CWP?

A
  • 2 of 4 pre-trip of hi PZR pressure
  • 2 of 4 CPC channel pre-trip on HI LPD or LO DNBR
  • RPCB flag from CEAC or CEA deviation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What will cause an AMI?

A
  • Reactor power <15%

- Reactor power < AMI threshold & TLI<15% & no CEA withdrawal demand from RRS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What will cause a CMA?

A
  • 30s motion in high rate (30 “/m)

- 60s motion in low rate (3 “/m)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
How is the Group Middle Average number calculated for the CEA display on B04?
Average of all CEAs in group except for highest and lowest CEA.
26
How does CEDMCS respond to a failure of PNA-D25 or PNB-D26?
CEAC failure and (2) RTSGs will open.
27
How does CEDMCS respond to a failure of PNC-D27?
(2) RTSGs will open. Core mimic lights in PacMan shape.
28
How does CEDMCS respond to a failure of PND-D28?
(2) RTSGs will open. Core mimic lights in D shape. CWP signal also.
29
How does CEDMCS respond to failures of NNN-D11 and/or NNN-D12?
- Loss of NNN-D11 or 12 will have no effect. | - Loss of both will drop all rods, and loss of UEL, LEL, & DRC (mimic)
30
What is the purpose of Flow Control Valve, FCV-27, in the control oil system?
Diverts portion of hydraulic fluid to be cleaned up.
31
What will auto start the backup control oil pump?
CO pressure of 1300 psig.
32
At what control oil pressure will the main turbine trip?
1100 psig (2 of 3).
33
How does the Boronometer/Rad Monitor Flow Control Valve, CHE-FV-204 fail?
Fails Open - AOV, NK power to solenoid. | bypassing flow to boronometer
34
How does the Seal Injection Temperature Isolation Valve, CHN-UV-231P, fail and what auto actuations does it have?
Fails Open - AOV, NK power to solenoid. | Closes on Seal Inj temperature HI-HI (150F) or LO-LO (70F)
35
How do the Seal Injection Flow Control Valves, CHE-FV-241thru244, fail?
Fail Open - AOVs, NK power to solenoid
36
How does the Seal Bleedoff RV Isolation Valve Fail?
Fails Open - AOV, PK power
37
How does the BAMP Suction Isolation Valve, CHN-UV-532, fail?
Fails Open - AOV, NK power | Normally hand-jacked open with air isolated
38
What are the auto actions associated with the Boric Acid Makeup to Charging Pump Suction Valve, CHN-UV-514?
-Opens on a VCT LO-LO level of 5% -Closes when VCT LO-LO level clears at 15% MOV,fails as is
39
What are the auto actions associated with the RWT makeup to Charging Pump Suction Valve, CHE-UV-536?
-Opens on a VCT LO-LO level of 5% if CHN-UV-514 has no power. MOV, NHN-M72 power, fails as is
40
What are the auto actions associated with the RDT Isolation Valve, CHA-UV-560?
-Closes on CIAS -Closes on HI-HI RDT pressure of 10 psig (no override) AOV, PK powered to solenoid, fails closed
41
What are the auto actions associated with the RDT Vent Valve, CHN-UV-540?
-Closes on HI-HI RDT pressure of 10 psig (no override)
42
What are the auto actions associated with the EDT Inlet, Outlet, and Vent Valves, CHN-UV-563,562 & 564?
-Close on HI-HI EDT pressure of 7 psig (no override)
43
What will put a Charging pump into an anti-pump condition if green flagged?
-Low suction pressure trip -Overload or load shed Can clear anti-pump by taking to stop.
44
How is VCT level normally controlled?
Auto makeup of 34% & stops at 44% based on CHN-LI-226.
45
How is VCT HI & LO levels controlled?
- Diverts to HUT @ 60%, resets at 58% | - @ 5%, CHN-UV-514 opens, CHN-UV-501 closes, a BAMP starts (536 opens if 514 has lost power). Resets at 15%
46
What will occur if Seal Injection is isolated to RCPs?
HP Seal Cooler inlet temperature will rise to 200-220F, all other temperatures remain normal.
47
What are the design bases of the AF system?
Cooldown @ 75F/hr to 350F
48
What are the available control power sources for AFN?
``` PKA-D21 A class battery charger ```
49
What will auto start the AFB pump?
SIAS CSAS LOP AFAS 1/2
50
What CR indication will you see on a manual electrical trip of AFA-HV-54?
Switch top light green | Switch bottom light red
51
When AFA-HV-54 trips on overspeed, what is the status of the latch lever?
It will be raised to the reset position.
52
What supplies governor power for AFA?
PKA-M41
53
What happens to the steam supply valves on AFA after a start?
134A/138A open | 134/138 open 30 sec later
54
What happens on an AFAS 1/2 (related to AF)?
``` Both class AF pumps start Isolation & Control valves to 1/2 SGs open and cycle to maintain level between 25.8-40.8% WR. ```
55
What is the max amp limit for AFB?
151 amps | 122 amps for N
56
If the RMWT is supplying AF, how are the recirc lines aligned?
Still aligned to the CST. Contamination path exists.
57
When do the AR pump suction valves receive a permissive to open?
When the pump's breaker closes
58
During hogging operation, is the release monitored?
No. RU-141 & the post filter are both bypassed.
59
What cools the condensate receiver tank?
NC via the AS vent condenser.
60
What happens if RU-7 alarms?
Effluent from the AS vent condenser will divert from the condenser to the LRS low TDS HUT.
61
What cools the BD HX?
Condensate
62
Where is high rate blowdown normally aligned?
Condenser, BFT cannot handle it.
63
How are BOP ESFAS cabinets cooled?
Each cabinet cooled by (2) fans, one powered from PN and the other from PK.
64
Which rad monitors initiate a FBEVAS?
RU-31, A train, SFP | RU-145, B train, FB exhaust
65
What cross trips exist on a FBEVAS initiation?
``` One channel will cross trip to the other channel (A/B) FBEVAS cross trips to CREFAS (A to A, B to B) Manual initiation (B05) will not cause cross trips. ```
66
What is unique about manual initiation of A vs. B on FBEVAS?
A will trip fan (A in fan) | B closes dampers
67
What happens if both trains of FBEVAS, CREFAS, CRVIAS, or CPIAS are placed in bypass?
Each train will block the other from being put in bypass. Neither will be in bypass.
68
What is the power supply to the BOP ESFAS cabinets?
PNA(B) and PKA(B) auctioneered.
69
How do you reset the latch lever after a manual/electrical trip of AFA-HV-54?
Take the HS to jog closed to get both green lights and reset the latch lever
70
Which RU monitors will initiate a CPIAS?
RU-37 & RU-38
71
If you get a single CPIAS RU monitor to trip, what signals will initiate?
Both trains of CPIAS and both trains of CREFAS.
72
What will trip the CP exhaust fans?
CIAS isolate the dampers which trips the fans.
73
What RU monitors are associated with CREFAS?
RU-29 & RU-30.
74
What will initiate a CREFAS?
Cross trip from FBEVAS or CPIAS, RU-29/30, Test initiation of any of the above, or manual from B05
75
What is unique about initiating a CREFAS A vs. B from B05?
A train will trip the normal supply/exaust fans. | B will close the dampers.
76
What will indicate a LOP in relation to the LOP/LS module?
2 of 4 trip of UV/DV relays. Each channel is comprised of 1 UV and 1DV relay in the following scheme: 1 & 5, 2 & 6, 3 & 7, 4 & 8.
77
For ESF actuations, what system starts pumps and which moves valves?
The BOP ESFAS will only start pumps/motors. The PPS ESFAS repositions valves.
78
If a CS pump is starts on a CSAS with no SIAS, how can the pump be stopped?
Override is for SIAS only, therefore the HS can be taken to stop to anti-pump the pump.
79
Describe modes of the BOP ESFAS.
``` 0 - normal mode, no input 1 - SIAS/CSAS no LOP 2 - SIAS/CSAS & LOP, DG BKR closed 3 - LOP no SIAS/CSAS, DG BKR closed 4 - Misc (DG RUN, CREFAS, CRVIAS, FBEVAS, etc) ```
80
How does a loss of PN affect BOP ESFAS?
Cabinets get backup power from PK, but RU monitors powered from PN may trip and initiate.
81
Why do you need to wait to reset equipment after BOP ESFAS is reenergized?
If a spurrious LOP signal is present, it will stay in for 60s and needs to clear first.
82
What will happen on a HI-HI level in one of the LP FW heaters?
The inlet & outlet valves for that entire string will isolate.
83
What will close the hotwell drawoff valve?
LO suction pressure on either FWP | High condenser cation conductivity
84
How can the auto-start of a CE pump be simulated?
A pushbutton on B06 simulates a LO-LO discharge pressure (equated to 549 gpm). Pump will run until secured.
85
What will prevent auto-start of a CE pump?
Electrical fault | Generator differential or stator ground
86
What will happen to CE trips if NKN-D41 is lost?
Power to the CE panel is lost, the CE trips will not function to trip the turbine.
87
What will open the load contactor downstream of the MG sets?
SPLA trip base on 2409 psia in the PZR.
88
What are the CEA movement speeds in manual?
30"/min = 40 steps/min
89
Where do the CEDM UV relays measure voltage and how/what do they actuate?
They measure bus voltage a CEDM cabinets. 2 of 4 relays sensing < 180V, K1 denergize & K2 energize to: signal EHC to trip turbine signal RK/RJ/PC for RX trip signal FWCS for RTO signal SBCS for QO block
90
What will cause an AWP?
Tav-Tref>6F Tcold>575F SBCS demand
91
What will cause a CWP?
2 of 4 pretrips on Lo DNBR, Hi LPD, or Hi PZR pressure | RPCB flag input from or CEAC/CEA deviation
92
What will cause an AMI?
``` Tavg mismatch > 5 F when in avg TLI mismatch > 5% when in avg RX power mismatch >5% when in avg RX power <15% TLI < 15% & RX power < AMI threshold ```
93
What modes of rod motion will function without the plant computer?
MI & MG. Pulses are sent to PC, sequential and auto will not function without pulses.
94
What must be done if cooling is lost to CEDMS?
If RCS temp > 300F, cooling must be restored within 10 minutes or a rapid shutdown and cooldown is required. If cooling is restored within 40 minutes of loss, shutdown may stop.
95
How is the control oil purity maintained?
FCV-27 diverts a controlled portion of the fluid to be cleaned up.
96
What will start the standby control oil pump?
The standby pump will start when system pressure drops to 1300 psig.
97
At what pressure will control oil trip the turbine?
1100 psig, 2 of 3.
98
What is the basis for the COLSS LPD POL?
The POL is based on 13.1 kW/ft to prevent fuel cladding temperature from exceeding 2200 F.
99
What are the general functions of COLSS & CPCs?
COLSS - monitor & alarm | CPCs - auto trips
100
What is displayed on the power limit margin meter?
Smoothed plant power is compared to the most restricitve of: License power (typical) DNBR POL LPD POL
101
Why must COLSS compensate for incores?
Time delay for rhodium decay | Depletion of rhodium in detectors
102
How do temperature changes affect radial peaking factors in COLSS?
Peaking factors are based on Tcold of 555F. A deviation (hot or cold) will be conservatively increase the peaking factors, reducing the LPD POL.
103
What does the COLSS CPC Az Tilt Alarm indicate?
COLSS calculated tilt is > the value inputted in to CPCs and the CPCs should be updated.
104
Which detectors will be substituted for in COLSS?
Those located in containment (Pzr Press, Th, Tc, RCP delt P)
105
If RCP delta P increases, how will this affect the POLs?
DNBR will decrease (high delta P indicates lower flow)
106
If all else is held constant and the blowdown constant in COLSS is increased, what will happen to JSCALOR?
It will decrease.
107
What concerns are there with restarting COLSS?
Only start 1 computer at a time and allow 10-15 minutes for values to normalize before determined operable.
108
Hos is Az Tilt affected in COLSS if a rod slips to 10" withdrawn?
Incores will see the flux shift and calculate increased tilt.
109
What happens to the LPD POL if rods are withdrawn?
It will generally increase.
110
What is the purpose of the CPCs
Ensure SAFDLs are not exceeded during AOOs.
111
What is an output of CPCs?
- LPD DNBR trips and pre-trips - Aux trips - Calibrated neutron flux
112
Name the CPC aux trips.
``` Conditions outside analyzed range: -PZR pressure 1860 to 2388 psia -ASI -.05 to .05 -Tcold 505 to 590 F -Hot pin (radial peak) 1.28 to 7 Asymmetric SG transient Thot within 19 F of saturation <2 RCPs running VOPT (1%/min ramp) ```
113
What is the purpose of the 95% RCP speed trip/pretrip?
Loss of 4 RCP's not detected fast enough by normal calcs, so 95% speed covers blind spot and trips HI LPD/LO DNBR (not aux trip).
114
When do CPCs shift to/from canned value of ASI going up/coming down?
- When sum of 3 excore safety channels = 51% going up | - When sum of 3 excore safety channels = 45% coming down
115
What parameters are used to calculate mass flow rates calculated in CPCs?
RCP speed sensors, Thot, Tcold and Pzr Pressure
116
How/why do CEA deviation penalty factors build in over time in CPCs?
12 finger rods build in penalty factors that peak at 6 hours to account for Xenon redistribution.
117
What will illuminate the CEA Deviation lamp?
CEA deviation in a subgroup beyond 5.5"
118
What happens to excore count rates as Tcold decreases?
The colder water will absorb neutrons, reducing count rates. CPCs will account for this and boost the signal to compensate.
119
What must be done when energizing a CPC channel (restoring PN)?
All parameters should be bypassed to prevent inadvertant trips.
120
What signals will auto start a CT pump?
SIAS LOP CREFAS CRVIAS
121
What will close CHB-UV-515. LD to RHX?
SIAS | RG HX outlet of 413 F.
122
What will close CHA-UV-516, LD RG HX Iso?
SIAS | CIAS
123
What will close CHB-UV-523, LD outside Cont Iso?
CIAS | LD HX outlet of 135 F
124
How do the LDCVs 110P/Q fail?
Closed on loss of air Closed on loss of NNN-D11 for PLCS Loss of indication only on NKN-D42
125
What will isolate the BP CVs 201P/Q?
Loss of air Loss of NNN-D12 to BP controller LD HX outlet T of 148 F (backup to 523) Loss of indication on NKN-D42
126
What is the relationship between VCT outlet valve CHN-UV-501 and RWT MU to CHG pump valve CHE-UV-536?
501 will close at VCT level of 5%. If 514 (which would normally open) has loss of power, 536 will open. If 501 is then opened, 536 will close.
127
What type of valves are aux spray valves CHA-HV-203 and CHB-HV-205 and how do they fail?
SOVs, powered from PK and they fail closed.
128
What will close the seal injection temperature isolation valve, CHN-UV-231P?
Seal injection temp <70 F or >150F | Fails open on loss of air
129
How do the seal injection flow control valves, CHE-FV-241 through 244 fail?
Open (aov's)
130
What will close the CHA-UV-506 and CHB-UV-505 seal bleedoff containment isolation valves?
CSAS Loss of air (fail closed) Bleedoff will continue to RDT through 507.
131
What is the normal position of the BAMP suction isolation valve, CHN-UV-532?
Hand jacked open with air isolated to prevent isolating boration flow path.
132
What automatic functions are associated with Boric Acid Makeup to Chg Pump suction valve, CHN-UV-514?
Opens on VCT LO-LO of 5% | Closes when VCT level recovers to 15%
133
What will close the RDT isolation valve, CHA-UV-560?
CIAS HI-HI RDT pressure of 10 psig, no override AOV, fails closed
134
What will close the RDT Vent valve, CHN-UV-540?
HI-HI RDT pressure of 10 psig, no override | AOV, fails closed
135
What will close the EDT inlet, outlet and vent valves, CHN-UV-563, 562, and 564?
HI-HI EDT pressure of 7 psig, no override | AOV, fail closed
136
What type of rad monitor is RU-155D and what type of radiation does it measure?
Area monitor | Gammas
137
What must be done to the PZR when RCS boron concentration is changed by 50 ppm or more?
Initiate PZR spray and heaters to equalize boron concentration within 10 ppm.
138
What are the quench volumes required in the EDT? RDT?
35% EDT | 58% RDT
139
How are the the PZR safety valve locations monitored?
Acoustic monitors which light up in CR at 9% and 100% open.
140
What will happen to letdown boron concentration if temperature of flow through IX's increases?
Resin affinity for boron will decrease and concentration of flow exiting IX will increase.
141
Will the charging pumps respond to the PLCS if red flagged, auto after start?
No. Must be green flagged.
142
What will anti-pump the charging pumps if they are currently green flagged?
Low suction pressure trip Overload Load shed Clear by taking to stop.
143
What equation relates Letdown, Charging, Seal Injection and/or Bleedoff to determine possible RCS leakage? (Not all may be needed)
Charging = Letdown + Bleedoff Any deviation represents leakage.
144
What signal is sent to the Charging pumps from the BOP ESFAS sequencer when entering mode 1?
The sequencer will prohibit auto start of any charging pump for 40s. This will not trip any running pumps.
145
What signal is sent to the Charging pumps from the BOP ESFAS sequencer when entering mode 2?
All pumps are load shed. After the DG breaker closes on the bus, charging pumps will be prohibited from starting for 40s. PLCS will control after that.
146
What signal is sent to the Charging pumps from the BOP ESFAS sequencer when entering mode 3?
All pumps are load shed. Running pumps will be anti-pumped.
147
What type of level detector is CHN-LI-226 and what controls does it provide for the VCT?
Dry reference leg | Maintains level between 34-44%
148
What type of level detector is CHN-LI-227 and what controls does it provide for the VCT?
Wet reference leg Diverts to HUT at 60% (resets at 58%) At 5%: closes 501, opens 514, starts a BAMP
149
What will occur on a leak of CHN-LI-227 reference leg?
Indicated level will peg high and divert. Level will decrease and 226 will control between 34-44%
150
What will auto stop a RMW pump?
Signal from controller RMWT LO-LO level (both pumps and blue light) Flow deviation from setpoint Low discharge pressure (10s alarm, 24s trip) Loss of control power Elec protection Same as BAMP
151
What is the design basis of the RWT?
Support ECCS operation of all pumps running with full flow rate until boil off rate can be matched by 75% flow through single HPSI pump.
152
What are the tech spec bases of the RWT?
20 min (plus 10% margin) full flow from all ESF pumps before switching over to the RAS sump.
153
What will auto stop a BAMP?
Signal from controller RMWT LO-LO level (both pumps and blue light) Flow deviation from setpoint Low discharge pressure (10s alarm, 24s trip) Loss of control power Elec protection Same as RMW pump
154
How will reactor power be affected if VCT level lowers to 5%?
Reactor power will lower. 501 will close, 514 will open and a BAMP will start which will borate the RCS.
155
How will the RCPs be affected if seal injection is isolated at power?
HP Seal cooler inlet temperature will rise to 200-220F, all other seal temperatures will remain as is.
156
Where can the CW pumps be emergency stopped and what occurs? How does this differ from the normal stop?
There is a PB on B07 and at the switchgear that will open the pump breaker and send a signal to close the discharge valve. The normal stop closes the discharge valve and trips the breaker when the valve is at 8% open.
157
What happens when the second CW pump in a loop is started (assume cross tie closed)?
Pump starts,discharge valve opens to 44%. After 3 minute delay, the discharge valve opens to 100%. Finally, the discharge valve for the first pump opens to 100%.
158
What interlocks are associated with the dischcharge valve and stopping a CW pump?
The pump trips when the valve is 8% open. The valve is interlocked closed for 2 minutes.
159
If the A, B, and D pumps are running with the cross tie open, what will happen if the B pump is secured?
The A and D discharge valves will throttle to 44% to prevent runout.
160
What is required to open the condenser outlet valves, CWN-UV-9/10?
Waterbox pressure must meet setpoint indicatingn waterbox is full.
161
What override is active when a cooling tower fan is started?
A 30s override of the high vibration trip is inserted to allow the fan to come up to speed.
162
How is steam flow in DFWCS affected if a single transmitter is removed from service?
The remaining transmitter will be doubled to approximate steam flow.
163
For DFWCS 1, what NR SG level transmitter value is used?
Normally the highest valve from LT-1111/1112 is used.
164
What will happen if UIC #1 (control channel NI) is placed in Maintenance on the DFWCS and UIC #2 fails low at rated power?
DFWCS will go through swapover, resulting in a reactor trip.
165
How is an ATUN lockout removed?
Manually by the operator on the DFWCS screen.
166
When will DFWCS use a canned value for FW temperature and what is it?
If there is an 8% deviation in transmitters, a value of 425 F will be used.
167
In what DFWCS modes does SBCS input a signal?
1E control only (anticipatory input)
168
What is the purpose of RTO?
Prevent overcooling of the RCS after a trip.
169
What does the ATUN logic do and what modes it functional?
It adjusts the proportional and integral controllers based on FW temp and flow, RX power and steam flow. Active in 1E and 3E control
170
When do are the Main Feed Pump controllers only recieving control signals from their associated DFWCSs?
RTO Normally the MFP controllers recieve the higher of the 2 DFWCS.
171
List what happens to the DFWCS at the following power levels 14%, 15-16.5%, 50% increasing
14% Changes to 3E control if selected previously 15-16.5% Swapover if either downcomer>80% open, swapover at 16.5% if not already occured. (15min) 50% Downcomers open to 65% (10% of total flow, 15min)
172
List what happens to the DFWCS at the following power levels 50%, 15%, 13.5% decreasing?
50% Downcomers close 15% swapover 13.5% 1E control
173
What will cause DFWCS to shift to 1E control?
8% deviation feed flow transmitters 8% deviation steam flow transmitters Decreasing to 13.5% power
174
After a reactor trip, DFWCS shifts to RTO, what does this mean?
RTO feeds based Tave (not level) | Shifts out of RTO at 51.9% and will go back into RTO if it reduces back to 26%
175
What will happen if you are feeding in RTO and all reactor pumps trip (natural circulation)?
Tave will rise and you will overfeed unless you take manual control.
176
SG level rises to 89%, what happens to DFWCS?
DFWCS shifts to HLO at 88% which closes economizer and downcomer valves on the affected generator. ONLY IF THE VALVES ARE IN AUTO
177
When will the RX power input for DFWCS be a canned value and what is it?
If deviation between channels>8% canned values of: | 5% below swapover and 60% above swapover are used
178
What DG loads are cooled by the spray pond?
Jacket water cooler Lube oil cooler Intercooler
179
Without the spray pond, how long can the DG run?
15 minutes unloaded | 2.6 minutes loaded
180
How many days of operation are supported by the DG fuel oil storage tanks?
7 days (+15% margin for testing)
181
What is the minimum time the DG can run using the fuel in the day tanks?
60 min at rated power + 10% margin
182
At the TS level of 550 gal (2.75ft) how long will the DG run?
1.5 hours at rated load
183
How many DG starts can the air recievers support without recharge?
5
184
How do the starting air control valves function to start the DG?
They open on a start signal and stay open until 280 rpm.
185
What will trip the overspeed butterfly valve on the DG and how is it reset?
Overspeed at 660 rpm | Reset manually
186
When does the DG essential exhaust and AHU start/stop?
Starts 15 min after the DG | Stops after DG stop and room temperature <110 F
187
What is the purpose of the DG turbocharger and what provides its motive force?
It increases DG efficiency | It is driven by the DG exhaust
188
What are the DG emergency mode trips?
Overspeed Low Engine Oil Pressure (bypassed during start, 20s) Gnerator Differential
189
If the DG is taken to override, what trips are re-established?
(3) breaker trips | generator overcurrent, neutroal overvoltage, neg sequence
190
What conditions are required to auto close the DG output breaker?
LOP DG at rated speed and voltage Normal and Alt breakers open No 86 lockout present
191
What is required to manually close the DG output breaker?
DG at rated speed and voltage Alt breaker open No 86 lockout
192
If you try to start the DG and nothing happens (no start attempt at all), what is the likely cause?
Turning gear not disengaged
193
What will happen to the DG if class control power is lost while running?
The DG will trip, but the output breaker will not open causing it to motor. Breaker must be tripped manually.
194
What affect does a loss of control air have on a running DG?
No affect, control air is required to stop DG. Only available trip is overspeed valve.
195
What are the design run times and capacity for the DG?
5500 kW continuous | 6050 kW for 2 hours in 24
196
If the DG was running in test and was stopped, but is currently in its cooldown, what will happen if a SIAS is recieved?
The DG will switch to emergency run without resetting trip header, which will bring in alarms.
197
What does the hot gas bypass line do and what does it prevent?
A portion of the refrigerant goes from the compressor to the bottom of the cooler (bypassing the condenser and flash economizer). This will prevent surging.
198
What is the RHPCV and where is it located?
The RHPCV is located on the EW outlet to the condenser and regulates flow to reduce stacking.
199
What are the makeup sources to the EC system?
DW CST backup Fire water backup to backup
200
What happens to an essential chiller on a loss of EW?
The unit will trip on high condenser pressure
201
What will occur on a HI-HI level in one of the LP FW heaters?
BTV's for that train open (#3 and #4) CD side inlet and outlet valves isolate High level dumps for that train will open Extraction steam supply drain lines for that train open
202
When do the 1st and 2nd stage reheater drain tank high level dump valves close on startup?
1st stage closes at 10% | 2nd stage closes at 20%
203
What will close on a HI-HI level in the #7 FWH?
Normal level control valve from 2nd stage RDT 2nd stage drain tank vent valve to extraction line BTV and extraction steam MOV from #7 FWH
204
What is the purpose of the bleeder trip valves (BTVs)?
Prevent turbine blade damage Prevent reverse steam flow Prevent moisture carryover to turbine
205
What will trip the heater drain tank pumps?
HDT LO-LO level of 4 ft LO-LO flow of 711 gpm for 15s Electrical protection
206
How do the heater drain pump discharge valves fail?
closed on loss of air or power
207
What happens to the BTVs and extraction drains on a turbine trip?
BTVs all depressurize (critical and non critical and redundant PSL-76). All extraction drain valves open.
208
Which signal does the load control unit (LCU) send to the flow control unit (FCU)?
The lowest (via LVG) of - load limit pot - setback signal from RPCB - Load set reference
209
When the decrease button is pressed for the load set reference, at what speed with the load set drive motor lower the signal?
130%/minute
210
What is the purpose of the Power Load Unbalance (PLUB) and what does it measure?
The PLUB will trip the turbine to prevent overspeed after a lod reject. It compares generator output and cross under pressure.
211
What does the RPCB runback signal do and when is it recieved?
It is sent concurrent with a setback signal (but at 130%/min, much slower than setback) to move load set motor to 60%. Subsequently it adjusts to match primary and secondary based on Tave and Main steam header pressure.
212
What is the RPCB setback signal and how is it cleared?
Control valves are set to 60% at 480%/min. | Signal clears by turning load limit pot until load limit light illuminates.
213
How is the turbine placed in standby?
The standby pot signal is matched to CV flow signal and the standby on PB is depressed.
214
What occurs to overspeed trips when standby is selected for the Turbine control?
Backup overspeed lowers to 105% Mechanical overspeed at 110% is now the backup (loss of both speed signal trips is deactivated)
215
When do slave valves open/close based on the master CIV valve positions?
Open when master is 90% open | Close when master is 50% closed
216
When is chest warming performed and what is the valve positions?
Performed after shell warming | MSV-2 is throttled, all other valves closed.
217
How is EHC power supplied?
NNN-D15 provides powwer until turbine speed is high enough. | The permanent magnent generator (PMG) supplies normal power.
218
List the main turbine trips.
``` CE generated (several, 70s delay) Low MSOP pressure of 100 psig at >75% speed High vibration = 12 mil High exhaust hood temp = 225 Low EHC pressure = 1100 MSR high level 2/3 for 10s Low vacuum = 7.5" 2/3 Thrust bearing wear = 40 mil Low bearing oil pressure = 12 psig Manual RX trip from UV relays (2 of 4 selective) Mech overspeed 110% (backup at 112%) Loss of both speed signals Loss of 24V power, 125V power (>75%) or crosstrip ```
219
How will the EHC respond to a RPCB if in standby?
No setback or runback (rods will drop)
220
When flashing the field for startup, why is the button pressed twice?
First time tests shorting breaker | Second time energizes field
221
Following closure of the first output breaker, what loading rate is selected by EHC?
10%/min automatically selected.
222
How will ERFDADS indicate an RCS leak and for how long?
Indicated will be less than actual for 7.5 minutes.
223
List the NC priority loads that can be supplied by EW.
RCPs (seal coolers, thrust bearing cooler, motor cool, etc) CECM Normal ACUs Nuclear sample coolers Normal chillers
224
When EW is aligned to NC, which may need to be done to clear the low NC flow alarms?
Throttle flow through the SDCHX.
225
What auto actions will isolate EW to NC (A train only)?
SIAS Low EW surge tank level May override SIAS only
226
What other non priority NC load can be picked up by EW?
Spent Fuel Pool HX.
227
How will a loss of NNN-D15(16) affect the FW Pumps?
The control valves close (15 for A, 16 for B) and the pump will trip. If 16 is lost, indication is lost for both feed pumps.
228
What supplies steam to the MFPT at power?
Hot reheat (off MSR D)
229
What indication informs operator that MFWPT HP CV is closed?
Green light at the MFWPT
230
What is the power supply to the MFWP emergency lube oil pump and can it supply continus operation?
NKN-M46 | It is for coastdown only.
231
At what percent steam flow is Main steam supplying the MFPT?
approx 35%
232
What happens to the MFP mini flow valve on a trip of the pump?
It fails closed (prevent freewheel)
233
List the MFPT trips.
``` Overspeed - 6350 Lo suction P - 245, 10s for B, 15s for A, 2 of 3 HI discharge P - 1780, 2 of 3 Lo Cdsr Vac - 13.5" LO CO P - 75 psig Hi Act & Inact thrust brg P - 40 Lo turb Brg oil P - 4 Manual - B06 or local ```
234
What is required for MFP turning gear operation?
adequate oil pressure
235
How do SG DC CV's fail?
Locked as is.
236
How will a loss of NNN-D15 affect FWP's? D16?
CVs will drift close and FWP will stop. D15 for A and D16 for B. RPCB will not receive low lube oil signal, reactor trip is likely result.
237
What will close the HP and LP containment isolation valves for nitrogen?
CIAS.
238
What are the main HP nitrogen loads?
SITs, ADVs, Turb. Bldg Tank for DC IVs
239
Why is aux steam the preferred source to GS during operation?
GS will not be lost on an MSIS.
240
At 100% power, what are the status of valves GS valves 28A, 28B and 27?
28A - Closed 28B - Closed 27 - Throttled
241
How does PCV-27 respond to a loss if air or power?
It is unaffected. It operates off of GS pressure.
242
How do the GS pressure control valves fail on loss of IA?
Fail open to supply header.
243
What should be done to the condenser if GS is lost?
Break vacuum to protect labyrinth seals.
244
What is the normal operating range for the IA compressors?
109 to 119 psig
245
What type of drying is accomplished in the IA dryers after the accumulators?
dessicant towers
246
What will cause the IA UV-2, Instrument Air to containment valve, to close?
CSAS
247
What are the approximate amps that can be seen on loaded and unloaded IA compressors?
150 amps loaded | 75-90 amps unloaded
248
What happens when IA pressure reduces to 95 psig? 85 psig?
alarm at 95 | Nitrogen backup at 85
249
What is the normal and backup cooling to the IA compressors?
TC for normal cooling | Temporary DS lineup to single compressor for backup
250
How many ICIs are there? What type of detectors are they and how many levels?
61 self powered rhodium 5 (10,30,20,70,90)
251
What does the compensation filter accomplish for the ICIs?
Compensates for 42s half life of rhodium
252
What is the power supply the the LPVMS?
NNN-D11
253
Where do the CET's enter the core and where do they measure?
The enter the bottom of the core with the ICIs and measure temperature at the outlet plenum.
254
What is the relationship between the Core Monitor and the Pryoysate collector?
The Core Monitor continuously monitors and the Pryolysate collector will take a sample when the Core Monitor alarms.
255
What causes the main transformer cooling fans to start for each phase?
1st stage - transformer energized (generator exited) 2nd stage - transformer oil T = 70C 3rd stage - transformer oil T = 75C
256
What is the concern with excessive circulation of oil in the transformer?
Static electrification, which can create large potentials and eventual spark. Cooling pumps auto trip when a transformer is tripped/current is removed.
257
What will a trip of the unit Aux tranformer cause?
Gen/Turbine trip | Fast bust transfer of NAN-S01 and S02
258
What indications do you have of a coast down trip?
NAN-S01/2 load shed except for RCPs | Aux XMR still energized (20s)
259
When can the sync protection be bypassed when paralleling the generator to the grid?
After the first breaker is closed in, the bypass may be used to close the second breaker.
260
What will happen if the reverse power relay fails to trip the trip the main turbine?
The backup reverse power relay will trip it 30s later.
261
What action is required if cooling fans are lost on a main transformer?
Decrease MVARS to maintain oil temp < 100C
262
How is excitation removed from the generator?
shorting breaker closes | shunt SCRs fired full on.
263
When do the P-bars provide excitation to the generator?
When it is off-line
264
When will the Volt/Hertz regulator take action and what does it do?
When a high voltage (25.99kV) or drop in frequency is detected. The regulator overrides the setpoint adjuster and limits output voltage.
265
What conditions are required for a Volts/Hertz trip to occur?
V/Hz value of 26.3 kV lights timing LED. | If 26.328.3kV, trip in 2s
266
What does the MEL do and what if it fails?
MEL reduces field amps <105%. | If does not succeed in 1s, Fixed Field Circuit takes over.
267
What does the Fixed Field Circuit do?
Reduces field amps <100%. If does not succeed in 1s, generator trips. Fixed field must be reset at regulator cubicle.
268
What does the URAL protect against and how is it accomplished?
It protects against low excitation, possible pole slippage. The URAL overrides the AC regulator to maintain acceptable level. Only works in AC mode.
269
What two methods are used to de-excite the field?
SCRs fire full on (MINEX) | Shorting breaker closes
270
What is the source of field flashing power?
NH
271
What are the VAR limits with the main generator?
710 MVAR boost | 310 MVAR buck
272
How many rectifier bridges are required to supply the rectifier?
3 of 4
273
What is the generator min/max pressures? | What is the min hydrogen purity?
30-75 psig for cooling | 90% to prevent explosive mixture
274
How many banks of fans are required on the main transformer for continued operation?
If less than 2 banks are avaialble for 30 min, all load must be stripped.
275
What oil temperature on the Aux Transformer requires it to be taken out of service immediately?
80C
276
What are the possible power supplies to the MSIVs and what is the normal arrangement?
Directly off the battery or off the PKA/B bus. | Normal arrangement off the battery.
277
How do the MSIVs fail on loss of power? Air?
Fail closed on loss of all power, typically aligned to battery. Fail as is on loss of air, still able to fast close.
278
At what pressures will the MSSVs lift?
``` #1 - 1250 psig #2 - 1290 psig #3,4,5 - 1315 psig ```
279
How do the ADVs fail on loss of air? power?
Fail closed on loss of air and N2 backup (10.5 hr supply) | Fail closed on loss of power
280
What power supplies are required to control the ADVs from the control room?
SG1 L1 SG1 L2 SG2 L1 SG2 L2 PN: A B B A PK: A B B A PK: C D D C
281
How do the Downcomer isolation valves fail on a loss of air? power?
Fail closed on loss of air and N2 backup (8 hr supply, accumulator in Turb building) Fail OPEN on loss of power
282
How do the Economizer isolation valves fail on a loss of air? power?
Fail closed on loss of all power. | Fail as is on loss of air, still able to fast close.
283
Which valves close on an MSIS?
``` Downcomer IVs Economizer IVs MSIVs MSIV bypass valves Steam trap IVs Blowdown and sample containment IVs ```
284
What will limit flow during a MSLB?
Flow restrictors on SG nozzles.
285
How do Economizer and Downcomer CVs fail on a loss of air?
As-is.
286
How do the MSR drain tank normal level control valves fail?
closed on loss of air or power
287
When do the MSR drain tank hi level CVs close on a startup?
Fail open until 10% as sensed by hot reheat pressure.
288
What MSR drain tank level will trip the turbine?
-3" from from bottom of MSR.
289
How do all hi level dump valves fail, except for LP Htr 1?
Fail open on loss of air or power.
290
When do the reheater drain tank hi level valves close on a startup?
1st stage failed open until 10% | 2nd stage failed open until 20%
291
How do the vent valves for the reheater drain tanks fail? What will cause auto actions?
Fail open to the main condenser on loss of air/power. | If HI-HI level and/or BTV comes off open seat, vent to condenser opens, vent to extraction closes.
292
What condenser pressure will trip the turbine?
7.5" HgA
293
What thrust bearing wear will trip the turbine?
40 mils
294
What stator cooling flow will trip the turbine?
549 gpm with 70s delay.
295
Where do the 3rd and 5th stage HP turbine extraction go?
3rd stage - 1st stage reheat and #7 FWH | 5th stage - #6 FWH
296
What LP turine stages have extraction steam?
8, 9, 11, 12
297
How is second stage reheat steam regulated using the RSLLV and RSHLV?
The RSLLV is ramped from 15 to 65% power. The RSHLV opens at 65% and the RSLLV remains open.
298
At what power level can the RSSV be opened?
A pressure switch set at 10% controls steam to the source valves for 2nd stage steam.
299
What is the sequence for starting the turning gear motor on the main turbine?
Piggyback motor starts TG engages (if <2rpm) Slow speed motor starts
300
When should MSRs be placed in service following an outage?
If load will be >15% for 12 hours to prevent last stage bucket erosion.
301
What is the power limit for placing 2nd stage reheat in service?
95% power since 2nd stage reheat is approximately 5% steam flow.
302
How can you lose electrical protection to a bus?
lose control power
303
For 4160V breakers and above, when do the closing springs charge?
When the breaker closes (springs are always charged)
304
What will cause the WRF supply breakers to load shed?
degraded voltage with SIAS (prevent double sequence event)
305
What is required to initiate a fast bust transfer on NAN-S01/2?
``` Xfr switch in auto Generator trip Early b contact on normal supply breaker closed synch check relay no lockout voltage on S03/4 ```
306
Name the NC priority loads.
CEDM normal ACUs RCP coolers Nuclear sample coolers Normal chillers
307
What is normal NC discharge pressure and when does the backup pump start?
100 psig normal. | Backup starts at 79 psig.
308
What RU monitor normally monitors NC flow? What if EW is aligned?
RU-6 | RU-2 or 3
309
What will close the NC containment isolation valves (401,402 and 403)?
CSAS
310
What do the safety relief valves (615 and 615) on the NC return lines inside containment protect against?
They ensure closure capability of isolation valves during RCP high pressure seal cooler tube rupture. Setpoint = 135-150 psig.
311
What will isolate EW if aligned to NC? Which train?
A SIAS or low EW surge tank level will isolate EW A only, since B has manual vavles.
312
What order should the NC supply and return valves be opened?
Return should be opened first to prevent reliefs from lifting.
313
If the standby NC pump is started at the switchgear, will the CR recieve an amber lignt?
Yes. The amber light circuitry compares if the pump is running vs. CR switch position.
314
NC containment isolation valve has (2) breakers, why?
To protect the containment penetration. Typical for most/all containment penetrations.
315
What type of detectors are the startup channel excores and what are the power supplies?
BF3 proportional detector NNN-D11 for channel 1 NNN-D12 for channel 2
316
What does the high CPS bistable do in relation to the NIs?
At 10,000 CPS (used to be 2000) an annunciator is triggered to alert the operator to turn off the startup channel detectors.
317
What type of detectors are the control channel excores and what is the power supplies?
Boron 10 lined ion chambers NNN-D11 for channel 1 NNN-D12 for channel 2
318
What would be indicated if a linear amplifier on a single control channel excore were to fail?
1/2 of actual power.
319
What type of detectors are the safety channels and what are the power supplies?
U-235 fission chambers | PNA-D
320
What does the BDAS alarm indicate?
Possible inadvertant boron dilution, or power increasing, since setpoint does not automatically adjust. Alarm can be reset to clear when power increase is desired.
321
What is the result of a lower safety channel failing to 0?
Linear power will decrease, log power is unaffected.
322
What is the result of a middle safety channel failing to 0?
Linear power will decrease, log power will be 0
323
What is the normal operating voltage of the non class batteries and how long will they supply power?
135DC for 2 hours.
324
What is unique about unit 3s NNN busses?
NNN-D16 has a class backup power supply instead of a load shed similar for D15 and D16 on other units.
325
What happens if NNN-D11 loses its normal power source?
Auto transfer to backup.
326
What is required if closing the normal supply breaker to the class 4160V class bus locally?
Normal and alternate supply must be open.
327
What is required to close the alternate supply breakers to the 4160V class busses?
The DG supply breaker must be open (prevents cross tie of DGs)
328
What is the purpose of the B train disconnect switches?
Disables CR operation in ase of a CR fire.
329
What is the normal and backup cooling for the spent fuel pool pool cooling system?
NC is normal, EW is backup.
330
What will the status of the pool cooling pumps on a LOOP once it is restored?
Not running but may be manually started.
331
What is the basis for the 23' above irradiated fuel requirement in the SFP?
Iodine absorption.
332
What is the battery and or charger requirement when operating SDC valves 653/654?
The battery must be connected to the bus to prevent overloading the charger.
333
If grounds are detected on the PK bus where will alarms be recieved?
Local and CR
334
How is the swing charger prevented from supplying both PK busses?
Mechanical interlock
335
What will start/stop the normally running charging pump?
Stop if PZR level +15% increasing Start if PZR level +14% decreasing Must be green flagged
336
What will start/stop the standby charging pump?
Start if PZR level -23% decreasing Stop if PZR level -14% increasing Must be green flagged
337
At what levels will the PLCS level transmitters alarm in the CR?
25% low | 60% high
338
What PZR level increase will start the backup heaters and why?
3% increase in anticipation of an insurge.
339
What happens to the PLCS if Tc input fails high at 15% power?
Setpoint goes to max standby charging pump starts letdown goes to min
340
What happens to PLCS if TC fails low at 100% power?
Setpoint goes to min normally running charging pump stops letdown flow to max backup heaters energize (assumes 3% insurge)
341
What happens to PLCS if the selected PZR level transmitter fails low?
All heaters trip (<25% level) Standby charging pump starts LD to minimum Level will increase until other channel selected.
342
What happens to PLCS if the selected PZR level transmitter fails high?
backup heaters energize (3% insurge) Normally running charging pump trips LD to maximum PZR level decreases until other channel selected or RX trip if no action.
343
What happens to PLCS if NNN-D11 is lost?
Master controller loses power = 0 output signal LD will isolate Normally running and standby charging pump stop
344
What happens to PLCS if NNN-D12 is lost?
PZR level control channel X loses power (buffered signal lost). LD will isolate (loss of power to LD isolation valve 523)
345
What happens to PLCS if NKN-D42 is lost?
PLCS control circuit loses power. LD isolates, charging pumps stop (manual control avail) Loss of remote heater control Loss of LDCV and BPCV indication
346
What happens to PLCS if IA is lost?
LD will isolate | Chg pumps manually controlled to maintain pzr level
347
What do the red, black, and white on black pointers typically indicate on a controller?
Red = Actual/measured parameter Black = Local setpoint Black on White = Remote setpoint
348
How does a loss of the PC affect the plant monitoring system?
Annunciators work, but alarm points do not show up on alarm screen. Operator to verify alarms at RK cabinets.
349
What is unique about the Unit 1 if the supply to PN is lost?
For A and C, there is no auto transfer switch, so PNA or C will be de-energized until manual switch to the voltage regulator is accomplished.
350
What does the FORWARD TRANSFER and REVERSE TRANSFER BUTTONS do on the static transfer switches do?
Forward transfers to the inverter (normal source) | Reverse transfers to the voltage regulator (backup)
351
What precautions are involved with cycling PN?
CEAC and CPC computers shall be turned off first.
352
What is the PPCS high and low pressure alarm values and do they have any functions?
``` 2285 high - heater cutout (reset at 2275) 2160 low (reset at 2200) ```
353
What are the setpoints and functions for the backup heater control bistables?
2200 - heaters turn on | 2225 - heaters turn off
354
What is the heater cutout level and where is it reset?
Cutout at 25% | reset at 27%
355
What is the high pressure heater cutout?
2285
356
What does the backup heater setpoint override do and how is it initiated/reset?
It allows backup heaters to be energized above the 2225 psi backup heater setpoint. It is operated by an on/off switch. There is a 10s delay to cancel or re-initiate.
357
If the B class heaters are taken to local at the RSDP, will they respond to level and/or pressure cutouts/starts?
No.
358
What is the status of the pressurizer spray valves and proportional heaters with the following PPCS controller outputs: 0% 16.5% 33% 50% 100%
0% (25 psid error) - heaters full on, spray valves closed 16.5% (0 error, normal) - heaters at 50%, spray valves closed 33% (25 psid error) - heaters off, spray valves off 50% - heaters off, spray valves full open 100% - no change, same as 50%
359
What is unique about the class backup heaters?
They will trip on a SIAS. There is a separate override. | Remains in effect until SIAS clears.
360
What is the result of the selected PZR pressure transmitter failing low with no operator action?
Heaters energize, spray valves stay closed. Eventual trip on hi PZR pressure (2383 psi).
361
What happens to PPCS if the non selected pressure transmitter fails hi?
PZR trouble annunciatior PZR pressure hi-lo annunciator no actions
362
How does a loss of NNN-D11 affect PPCS?
Pzr press transmitter 100Y fails low Pzr level transmitter 100Y fails low, heaters cut out (3) selectors switches need to be taken to X channel
363
How does a loss of NNN-D12 affect PPCS?
Master controller fails - 0 output Pzr press transmitter 100X fails low Pzr level transmitter 100X fails low, heaters cut out
364
How does a loss of NKN-D42 affect PPCS?
Loss of bistable control, all heaters off on low level cutout.
365
How does a loss of PKA/B affect PPCS?
Aux spray valves 205/203 fail closed and valve position is lost.
366
How many PPS trips are required for a reactor trip?
2/4 on the same parameter.
367
How does a loss of a single PN channel affect CPCs?
3 matrix relays de-energize (2) initiation circuits, (2) RTSG breakers open, no reactor trip.
368
How does a loss of a single PK channel affect CPCs?
(1) RTSG initiation circuit is de-energized, (1) RTSG breaker opens.
369
What is the purpose of the DNBR/LPD operational bypass? When is it placed in service and when is it automatically removed from bypass?
It bypasses CPC trips (rod position) to allow startup | The bypass is placed in service manually below 10-4% and is automatically removed from bypass above 10-4%.
370
What is the purpose of the low PZR pressure operational bypass? What are the limits of placing it in service?
Allows for RCS heat up/cool down. Is only permitted when RCS pressure < 400 psia and is removed automatically >500 psia.
371
What is the purpose of the Hi log power operational bypass? When is it placed in service and when is it automatically removed from bypass?
Allows power increase during startup. Must be manually placed in bypass above 10-4% (interlock) and below trip setpoint of 10-2%. Bypass is automatically removed when power is reduced below 10-4%.
372
What will happen if a single PPS trip parameter is placed in bypass?
The logic becomes 2/3 for trip. This allows for maintenance or testing.
373
How and where are the ESFAS signals reset?
Only 1 PB needs to be pressed at the ARC cabinet.
374
What will pressing the Low SG pressure reset PB do?
The SG low SG pressure trip and pretrip setpoints will lower by 200 and 100 psi below current pressure.
375
What RPS controls are available at the RSDP?
PZR: low press bypass switch and permissive indicator, low press reset switch, low press pretrip indicator SG: press reset switch, pretrip indicator
376
What is unique about the AFAS logic circuits and why?
There are (2) parallel relay paths allowing the valves to cycle on level while the pumps run continuous until the condition is reset.
377
What is unique about manual initiation of the AFAS and what issues could this cause?
The switches on B05 are maintained. If not returned to normal position, feed valves will remain open and overfeed is possible.
378
How is DAFAS bypassed?
8 keys located in ARC 5 and 8.
379
If RCP speed starts to slowly lower, what will happen to DNBR as calculated by CPCs?
It will gradually decrease until 95% RCP speed and then a trip will be generated.
380
Which ESFAS actuation does not have an initiation reset at the PPS cabinet?
AFAS
381
What is the result of a loss of PW?
Loss of cooling AOP directs crew to trip reactor.
382
Where can PW return to CW?
Normally to the CW header | Alt, to tower #2.
383
What auto functions are associated with the PW pumps?
Standby pump auto starts on low discharge pressure of 40 psi.
384
What is the minimum required level in the CW canal to prevent PW pump air binding?
19'
385
Where can an 86 lockout be reset for the PW pumps?
At the switchgear only.
386
How will PW pumps be affected on a loss of power and restoration to the NB bus?
The PW pump will be sequenced back on with TC and NC pumps as follows: ``` NC = 10s TC = 15s PW = 20s ```
387
What are the power supplies to QSPDS?
PNA - train A | PNB - train B
388
What does the TEMP SAT MARGIN-RCS recorder display and where is it located?
It displays the most limiting of RCS or upper head saturation margin and is located on B02.
389
How is an out of range CET indicated in QSPDS?
???????
390
What conditions for a heated junction thermocouple indicate a void?
When 200F (90F is normal) is sensed between the 2 thermocouples or an unheated thermocouple is at 700F.
391
What does a step change on the QSPDS level indicate?
The next HJTC is uncovered, the void is increasing. This is not an indication of an increased leak.
392
What is the range of the thermocouples?
200F to 1800F required, but accuracy is expected up to 2300F.
393
What is the pressure input into QSPDS?
PZR pressure only and is compared against other parameters to determine subcooling margin.
394
How is upper head saturation margin determined?
Using the hottest 3 HJTCs.
395
How is REP CET saturation margin determined?
By a representative CET temperature.
396
Which QSPDS parameter is invalid with RCPs running?
Plenum reactor vessel level.
397
If the seal bleedoff isolation valve is taken to close, what happens?
It will not close if the RCP is running.
398
What starts/stops an RCP oil lift pump?
IT will auto start on an RCP trip. It will run until secured by the operator. The lift pump needs to be manually started to satisfy permissive for RCP start.
399
What are the temperature restrictions for running 2 RCPs? 3 RCPs?
Only 2 RCPs allowed up to 200F (LTOP) | Only 3 RCPs allowed 200-500F (Brittle Fracture/Core LIft)
400
What electrical concerns are there with starting an RCP?
If a deisel is paralled to the same SU XM, deisel damage is possible. If any PK battery is disconnected from its bus, PN distribution panel may be lost.
401
What speed must the RCP reach in 14s to avoid auto trip after start?
600 rpm.
402
What causes the pressure drop across the RCP seals?
Capillary tube seal cooler
403
What is the RCS design pressure? Safety limit?
Design = 2500 psi | Safety Limit = 2750 psia
404
Where can the reactor vessel head vents be vented?
RDT or containment atmosphere
405
What type of detectors are the ICIs and what do the background detectors provide?
Rhodium detectors, self powered. | Background detectors provide flux compensation (interactions with bare wire)
406
What is the power supply to the class annunciators?
PKA/B
407
What will the status of the RK system on a loss of NKN-M45 and a SIAS in the 3 units?
``` Units 1 and 2 will lose all annunciators. Unit 3 will lose half since NNN-D16 has a class backup. ```
408
Which RU-1 containment building atmosphere monitor channels are tech spec related for leakage detection?
Channels 1 and 3. Particulate and gaseous (not iodine)
409
How does a loss of IA affect AR?
The suction valves fail closed and the discharge fails to through filter mode.
410
What does a hi-hi alarm on RU-7, AS Condensate Receiver tank monitor?
Diverts condensate to LRS.
411
Which RU monitors will initiate a CREFAS?
RU-29/30
412
Which RU monitors will initiate a FBEVAS?
RU-31/145
413
Which RU monitors will initiate a CPIAS?
RU-37/38
414
What does a hi-hi alarm on RU-141, Condenser Vacuum Pump/GS exhaust monitor, do?
Shifts exhaust to through filter mode
415
Which RU monitor is not normally in service at power?
RU-17, ICI
416
What is the status of RPCB when the TEST/RESET button is depressed? What happens if it is pressed twice?
It will not actuate. | Selected CEAs will be de-selected.
417
What is the status of RPCB if the AUTO ACTIVATE OUT OF SERVICE is depressed?
No RPCB auto actions.
418
What events will cause a RPCB and which one will generate a QO block?
LLR | Loss MFP - causes QO block
419
What is the status of CEA control after a RPCB?
The RPCB signal is locked in for 10s which blocks CEA control. After this clears, CEAs can respond to RRS or operator action.
420
What will happen on a RPCB if a group 5 rod is on the hold bus or does not drop?
Immediate reactor trip.
421
What does a setback do and how is it cleared?
Moves turbine CVs to 60% at 480%/min. | Cleared by reducing load limit pot to illuminate light.
422
How does RPCB respond to a loss of NNN-D11 and NNN-D12?
D11 - No rod drop or runback/setback | D12 - Rods drop, setback and no runback. RX trip.
423
What signals are sent from RPCB to EHC during a RPCB?
Setback Runback Load set increase inhibit
424
What will occur on a RPCB if PT-1024 fails low?
RPCB will occur and turbine will continuously runback. Reactor trip.
425
What RPCB signal is sent to RRS?
CWP
426
What is the RRS design basis (in conjunction with RPCB)?
Control reactor and turbine power for the following: Any size load rejection (100%) 10% step change in NSSS load 5%/min ramp in NSSS load
427
How is CEA motion demand determined in RRS?
Temperature error compensated by rate of change of power error.
428
How is Tref determined in RRS?
Tref program based on TLI.
429
How many excore control channels are there and what is the range?
2 | 0-125%
430
At what total error (degrees F) will RRS initiate a withdraw or insert signal?
3 F
431
What will occur if RRS sends a high rate withdraw signal?
The high rate demand light will be lit, but rods will withrdraw in slow rate.
432
What is required for RRS to be placed in test?
CEDMCS must not be in AS PLCS must be in LOCAL or MANUAL RRS will come out of test if above is violated.
433
How will a loss of NNN-D12 affect RRS?
No input to rod control | Tave fails low
434
What happens to RRS if a SBCV drifts open?
CEAs will step out. | RCS will cool from increased steam demand
435
What signals does RRS send to CEDMCS?
Speed and Direction
436
What are the safety hazards associated with the GEN SEAL OIL/H2 DIFF PRESS/ LO HYDROGEN alarms?
Hydrogen escaping the generator (explosive hazard)
437
What is the likely result of prolonged operation of the emergency seal oil pump?
Decreased hydrogen purity. | ESOP does not pull from vac tank
438
Where does the hydrogen side of the generator seals drain to?
Hydrogen detraining tank
439
Where does the main seal oil pump take suction?
Vacuum tank
440
Where does the emergency SO pump take suction?
Bearing oil return header
441
During normal operations, what is the SO flow path?
SO header, Vacuum Tank, SO pump, Seals, LO tank
442
How is SO vacuum tank level maintained?
By SDN-LCV-25
443
What is the difference between the SSE and the OBE?
The SSE is the max seismic activity for shutdown, OBE is the max that allow continued operation.
444
What limits are placed with aligning CS to SDC?
Cannot be aligned when RCS temperature >200F and pressure >250 pisa
445
How are SITs filled?
HPSI B only
446
What can be used to augment pool cooling during high heat load?
SDC
447
During an ESD, why is SI throttled as soon as throttle criteria is met?
Prevents pressurized thermal shock.
448
What is one indication of RCS voiding (PZR reaction)?
PZR level increase when spray is activated
449
What is the concern for SI with a LOCA outside of containment?
Not enough containment sump inventory during RAS
450
What is a possible consequence of stopping HPSI pump and not closing SIT fill/drain valve?
SIT will flow to RWT.
451
How does having the SDC bypass valve open do to indicated flow?
Flow will be read but will be bypassing the core | actual cooling < indicated
452
Where is the LTOP located?
Between 653 and 655
453
Where can the HPSI pump discharge?
All 4 cold legs and 1 hot leg
454
What is the SDC max heat up rate and what is the limiting component?
19 F/min which is based on the SDC HX.
455
What is the SDC temperature design limit?
350 F
456
What are the temperature limits for the LPSI pump regarding seal life?
RCS should be < 300F | and <135F if operated longer than 4 days.
457
If the CS pump breaker is anti pumped and a SIAS occurs, how can the pump be started?
Take to start twice | once to clear anti pump, once to start
458
What pressure will lift the LTOP?
467 psia
459
What interlock is associated with SI valves 651, 653, 655?
385 psi or greater will keep valves closed.
460
What is the LPSI shutoff head?
210 psia | most questions just require that you know it is less than 300-400
461
How much flow is provided by LPSI mini flow and how much is required for continued operation?
100 gpm from mini flow (good for 1 hour) | 2400 gpm required for continued operation
462
What is the shutoff head for the CS pump?
290 psia
463
How much flow is provided by CS mini flow and how much is required for continued operation?
150 gpm from mini flow (good for 1 hour) | 2100 gpm required for continuous operation
464
What is the CS rumble region and what will occur if operated there?
1800-2800 gpm | pump damage
465
What is the shutoff head of the HPSI pump?
1800-1950 psia (rough numbers)
466
What are the 5 design criteria of the ECCS?
``` Peak cladding T <2200 Clad oxidation <17% thickness Max H2 generation <1% if all clad reacted Coolable geometry Long term cooling ```
467
What is the design bases of SDC?
75F/hr cool down/heat up
468
What are the containment design temperature and pressure (CS designed to maintain this)?
Containment temperature <300 | Pressure <60psig
469
What is the pressure reduction design of CS?
Reduce containment pressure by half in 24 hours.
470
If you have a SIAS and HPSI has a brighter than normal green, what happens if you take pump to start?
Override light comes in, no start yet.
471
What does a white light on the SESS system indicate?
Equipment inoperatble
472
If you initiate a manual SESS alarm, what color light do you get?
White
473
How does PPS interact with SESS?
It sends signals so you know if equipment should be in actuated position.
474
If SBCS master controller is in LOCAL-AUTO and steam pressure is lowered via manual operation, how does the permissive setpoint change?
Permissive setpoint will increase based on lower pressure. | Permissive is inaffected by master controller.
475
With a RPCB, what occurs if PT-1024 fails high?
Rods drop, Setback and runback to 60% only.
476
If SBCS valves are throttling open and the SBCS is selected to EMERGENCY OFF, what occurs?
Bottom of cylinder is vented, IA is applied to top and valves close.
477
What is the SBCS condenser inerlock and what does it do to the valves?
5.5 " HgA (2 of 3 shells) | Closes SBCS valves to condenser
478
How does SBCS know there has been a load rejection?
Compares Steam flow vs. PZR pressure
479
What happens if FT-1011 fails low?
Modulation setpoint raises.
480
If PZR pressure transmitter 100Y fails low, how is SBCS affected?
Downward bias on setpoint.
481
What happens to the SBCS master contoller if power is lost and then restored?
Goes to Manual if <2s | Goes to emergency off if >2s
482
How many SBCS permissives may be in manual at one time?
Only 1 to prevent multiple valves opening on single failure.
483
What happens to the SBCS controllers when a QO signal is generated?
They are set to 83.3% (6 valves open) then then modulate to desired position based on pressure.
484
When is a quick open block generated?
Loss of feed pump Reactor trip (group Y) Reactor trip with Tave<573.5F (group X)
485
How do you reset the condenser interlock for SBCS?
EMERGENCY OFF to RESET
486
Howe does SBCS fail on loss of power or air?
Closed
487
What is the TS required spray pond level? What about CR indication?
13'-6" (12' useable required per TS, which equates to 1'-6" extra required) 14'-0" required in CR to account for uncertainty
488
What is indicated by a flow mismatch on spray pond supply and return?
Pipe break/leak.
489
What cools CW pump motor lube oil coolers?
TC
490
What will auto start a TC pump?
Low header pressure (55 psig)
491
How is temperature control obtained in TC?
Throttling HX outlet and bypass valves.
492
What will result on a loss of TC?
Reactor trip will be required because MFPs cannot continue to operat.
493
What administrative interlock is associated with the TC HX outlet and bypass valves (similar for NC)?
At least 1 must be full open.
494
What are primary concerns with loss of normal chillers?
Containment temp. rise (tech spec) Main generator collector housing temp. rise CEDCMCS cabinet room temp. rise
495
What will close the containment isolation valves for WC? Is there an override?
CIAS | There is an overide.
496
What will trip the A normal chiller?
SIAS (powered from PBA-S03)
497
How do the supply valves for charging pump ACUs fail?
Fail open.
498
How will a loss of NC affect the normal chillers?
They trip on low NC flow
499
Who is required in the CR during fuel handling?
RO and Reactor Engineering Representative
500
If count rates are increased 5x after an assembly is placed, what should be done?
Withdraw last placed assembly and observe response.
501
What is the overload for the fuel transfer machine?
800#
502
If the A supply and exhaust are being run on the Aux building, what happens if B supply is taken to start?
A supply trips, B starts.
503
What are the AF supply dampers and how do they fail?
PK powered and they fail closed.
504
What will start the elec. penetration room essentials?
LOP or SIAS.